One-Stop Supply of Conventional & Solar Power Equipment · Power Distribution System Design

1 MW Oilfield Power System Cost Breakdown (Q3 2026 China Supplier Pricing)

1 MW Oilfield Power System Cost Breakdown (Q3 2026 China Supplier Pricing) — itemized bill of materials and FOB pricing for a typical configuration.

Last updated: 2026-09-12 · copper-linked items track the daily LME copper price

Estimated total (FOB): $434,382 · 2000 kVA transformer

Bill of materials

ItemSpecificationQtyPrice (USD)
HV incoming panel (XGN15-12)630 A · SF6 · 4-way1$2,350
Main transformer (S13-M-2000/10)2000 kVA · Oil-Immersed · Copper · S131$22,331
LV incoming panel (GGD-3150)3150 A busbar · In 2887 A1$7,225
LV feeder panel (×5) (GGD-3150)distributes 29 circuits5$36,126
PFC capacitor bank (500 kVAR)automatic · GCK LV cabinet1$5,800
Cable branch box (LV) (DFW-0.4)1-in / 4-out · 0.4 kV · 630 A7$4,410
Series reactor (detuned) (CKSG-30.0/0.4)30.0 kVAR · 6% · 0.4 kV1$143
Busway trunking (LV main feeder) (Busway 4000 A)4000 A · Cu/Al busway · 120 m · $1329/m1$159,480
Feeder cable — Beam pump 1 (×29) (YJV 50 mm²)50 mm² Cu · 128 A · ΔU 3.0% · $25.2/m29$87,696
Branch trunk cable (LV → branch box 1) (YJV 120 mm² ×2)2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m2$16,512
Branch trunk cable (LV → branch box 2) (YJV 120 mm² ×2)2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m2$16,512
Branch trunk cable (LV → branch box 3) (YJV 120 mm² ×2)2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m2$16,512
Branch trunk cable (LV → branch box 4) (YJV 120 mm² ×2)2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m2$16,512
Branch trunk cable (LV → branch box 5) (YJV 120 mm² ×2)2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m2$16,512
Branch trunk cable (LV → branch box 6) (YJV 120 mm² ×2)2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m2$16,512
Branch trunk cable (LV → branch box 7) (YJV 50 mm²)50 mm² Cu · 128 A · ΔU 3.0% · $25.2/m1$3,024
Main busbar (Cu) (Cu 125×10)125×10 · 2500 A rating · ref $147.8/mincludedPOA
Grounding electrode (Φ20mm × 2.5m rod)R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω13$125
Soft starter cabinet (largest motor) (250 kW)Soft starter (3.0× In) · start dip 2.3%1$6,600
Injection pump soft starter / protection (250 kW)high-pressure injection pump · soft-start + overload/underload protection4POA
ESP variable-frequency drive (VFD) (90 kW)ESP soft-start + speed control · downhole pump protection5POA

Single-line diagram

CTCT 120/5APTPT 10kV/100V50/5151NHV incomingXGN15-12630 A - SF6 - 4-wayS13-M-2000/102000 kVAZ = 4%Oil-Immersed - Copper - S13kWhmeteringLV incomingGGD-31500.4 kV LV busbar125x10 Cu - 2500 ASPDPFC 500 kVAR+ detuned reactorLV feeder panel x5 - 29 circuitsBeam pump 1 - 128 AYJV 50 mm2Beam pump 2 - 128 AYJV 50 mm2Beam pump 3 - 128 AYJV 50 mm2Beam pump 4 - 128 AYJV 50 mm2Beam pump 5 - 128 AYJV 50 mm2Beam pump 6 - 128 AYJV 50 mm2Beam pump 7 - 128 AYJV 50 mm2Beam pump 8 - 128 AYJV 50 mm2Beam pump 9 - 128 AYJV 50 mm2Beam pump 10 - 128 AYJV 50 mm2Beam pump 11 - 128 AYJV 50 mm2Beam pump 12 - 128 AYJV 50 mm2Beam pump 13 - 128 AYJV 50 mm2Beam pump 14 - 128 AYJV 50 mm2Beam pump 15 - 128 AYJV 50 mm2Beam pump 16 - 128 AYJV 50 mm2Beam pump 17 - 128 AYJV 50 mm2Beam pump 18 - 128 AYJV 50 mm2Beam pump 19 - 128 AYJV 50 mm2Beam pump 20 - 128 AYJV 50 mm2Injection pump 1 - 128 AYJV 50 mm2Injection pump 2 - 128 AYJV 50 mm2Injection pump 3 - 128 AYJV 50 mm2Injection pump 4 - 128 AYJV 50 mm2ESP 1 - 128 AYJV 50 mm2ESP 2 - 128 AYJV 50 mm2ESP 3 - 128 AYJV 50 mm2ESP 4 - 128 AYJV 50 mm2ESP 5 - 128 AYJV 50 mm2Grounding 13xdia20mmx2.5m rodCable branch box DFW-0.4 x7 (1-in / 4-out)
LEGENDBreaker (52)DisconnectorCTCT (current transformer)PTPT (voltage transformer)50/51Protection relay 50/51/51N/87kWhMeter (kWh)SPD (surge protection)Transformer

How it was calculated

What drives the cost

  • Equipment — the transformer/switchgear/inverter is the largest single line item.
  • Storage (where applicable) — batteries are the biggest swing factor.
  • Copper & freight — copper-linked cabling and freight shift landed cost ±5–10%.

Frequently asked questions

What voltage do oilfield beam-pump motors run at?
Beam-pump (pumping unit) motors are typically 0.4 kV for units under 45 kW and 0.66 kV or 1.14 kV for larger units to cut cable losses across widely dispersed wells. A 37 kW unit uses 0.4 kV; wells spread over 1-2 km favour a 10/0.66 kV or 10/1.14 kV distribution with a pad-mounted substation per cluster.
Why do oilfield motors need soft-start?
Direct-on-line starting draws 5-7 times rated current and can dip the weak, long feeder voltage below 85%, stalling adjacent pumps. Soft starters limit starting current to 2.5-3.5 times and ramp torque over 10-30 seconds. This matters on off-grid or long radial oilfield feeders; the calculator checks motor-starting voltage dip and recommends soft-start or VFD.
What is an ESP and how is it powered?
An electrical submersible pump (ESP) is a downhole centrifugal pump driven by a submersible motor, fed from a step-up transformer and VFD at surface. A typical 90 kW ESP runs on a dedicated 10/0.66-3.3 kV feed through a variable-speed drive that matches pump speed to well inflow. ESPs are sensitive to voltage quality, so harmonic and dip control matter.
When is an off-grid power system right for an oilfield?
Off-grid (diesel or gas generator plus storage) suits remote wells where a grid connection would cost more than roughly $20,000-50,000 per km of line. Typical off-grid oilfield loads are 50-500 kW. Gas-driven generation using associated gas can cut fuel cost 60-80% versus diesel; the calculator prices an off-grid option alongside the grid-fed case.
What demand factor applies to a multi-well oilfield?
A multi-well oilfield with 20 pumping units rarely runs all motors simultaneously at full load; a demand factor of 0.7-0.8 is typical. Injection and ESP loads are more continuous, running 0.8-0.9. The calculator uses 0.75 by default and lets you adjust per site, preventing a 25-35% transformer oversize.
What standards govern oilfield box substations?
Pad-mounted and box-type substations for oilfields follow GB/T 17467 (prefabricated substations) and IEC 62271-202 (high-voltage/low-voltage prefabricated substations), with explosion-proof or weatherproof enclosures per the hazardous-area classification. Transformers follow IEC 60076; the calculator's BOM cites the applicable standard basis for each selected item.

Size your own configuration

Run the calculator for your exact load and get a full BOM + FOB price.

Open calculator Request a Quote

Related