One-Stop Supply of Conventional & Solar Power Equipment · Power Distribution System Design

500 kW Pumping Station Power System Cost Breakdown (Q3 2026 China Supplier Pricing)

500 kW Pumping Station Power System Cost Breakdown (Q3 2026 China Supplier Pricing) — itemized bill of materials and FOB pricing for a typical configuration.

Last updated: 2026-09-12 · copper-linked items track the daily LME copper price

Estimated total (FOB): $72,070 · 500 kVA transformer

Bill of materials

ItemSpecificationQtyPrice (USD)
HV incoming panel (KYN28A-12-630-25)630 A / 25 kA · vacuum1$2,226
Main transformer (SCB13-500/10)500 kVA · Dry-Type · Copper · SCB131$9,201
LV incoming panel (GGD-1000)1000 A busbar · In 722 A1$3,479
LV feeder panel (GGD-1000)distributes 3 circuits1$3,479
PFC capacitor bank (100 kVAR)automatic · GCK LV cabinet1$1,800
Series reactor (detuned) (CKSG-6.0/0.4)6.0 kVAR · 6% · 0.4 kV1$41
Main feeder cable (TX→LV) (YJV 0.6/1kV 240 mm² ×2)2× 240 mm² Cu · ΔU 1.17% @ 80 m · $123.0/m2$19,680
Feeder cable — Pump 1 (×3) (YJV 150 mm²)150 mm² Cu · 272 A · ΔU 1.4% · $86.0/m3$20,640
Main busbar (Cu) (Cu 63×6.3)63×6.3 · 900 A rating · ref $47/mincludedPOA
Grounding electrode (Φ20mm × 2.5m rod)R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω13$125
Soft starter cabinet (×3) (160 kW)Soft starter (3.0× In)3$11,400
Pump units (motor + impeller) (160 kW)centrifugal pump · duty/standby3POA
Control valves & actuators (DN (per line))flow control / isolation valves + actuators2POA

Single-line diagram

CTCT 30/5APTPT 10kV/100V50/5151NHV incomingKYN28A-12-630-25630 A / 25 kA - vacuumSCB13-500/10500 kVAZ = 6%Dry-Type - Copper - SCB13kWhmeteringLV incomingGGD-10000.4 kV LV busbar63x6.3 Cu - 900 ASPDPFC 100 kVAR+ detuned reactorLV feeder panel x1 - 3 circuitsPump 1 - 272 AYJV 150 mm2Pump 2 - 272 AYJV 150 mm2Pump 3 - 272 AYJV 150 mm2Grounding 13xdia20mmx2.5m rod
LEGENDBreaker (52)DisconnectorCTCT (current transformer)PTPT (voltage transformer)50/51Protection relay 50/51/51N/87kWhMeter (kWh)SPD (surge protection)Transformer

How it was calculated

What drives the cost

  • Equipment — the transformer/switchgear/inverter is the largest single line item.
  • Storage (where applicable) — batteries are the biggest swing factor.
  • Copper & freight — copper-linked cabling and freight shift landed cost ±5–10%.

Frequently asked questions

Soft-starter or VFD — which is better for a pump station?
Soft starters suit constant-flow pumps where only the start is harsh; they cost 40-60% less than a VFD and have lower losses. VFDs pay off when flow varies (average flow below ~80% of rated) because pump power follows the affinity cube law — cutting speed 20% saves nearly 50% of energy. The calculator compares both and estimates payback on variable-speed operation.
How much energy can a VFD save on a pump?
Pump power varies with the cube of speed (affinity laws). Running at 80% speed uses about 51% of full-speed power; at 70% speed it is 34%. For a 160 kW pump running 4000 h/yr at 0.7 average flow, a VFD can save 40-50% energy versus throttling. The calculator quantifies the kWh and cost saving for your duty point.
What transformer size does a multi-pump station need?
Sum pump ratings, apply a simultaneity factor (0.6-0.8 for multiple pumps) and power factor (0.85-0.9), then select the next standard kVA. Six 160 kW pumps at 0.7 simultaneity and 0.88 pf need about 760 kVA, so select 800 kVA. Account for the largest pump starting; the calculator sizes the transformer and switchgear together.
What cable sizing rules apply to pump motor feeders?
Pump feeder cables are sized for ampacity (IEC 60364-5-52) and voltage drop, and to withstand the motor starting current. A 160 kW, 0.4 kV motor draws ~290 A full-load and ~5x on DOL start; the cable must carry the starting current briefly and keep steady-state drop under 5%. The calculator recommends the cross-section and checks the starting dip.
How do I compare fixed-speed vs variable-speed pump energy?
Fixed-speed pumps run at full speed and throttle flow (wasting head), while variable-speed pumps match speed to demand. For a duty point at 70% flow, variable speed cuts energy ~34%. The calculator takes annual operating hours, average flow and tariff to compute both energy costs and the simple payback of a VFD investment.
What protection does a pump motor need?
A pump motor needs overload (thermal), short-circuit, phase-loss and earth-fault protection, plus dry-run protection for submersible pumps. IEC 60947 and GB/T 14048 define the protection devices; motor starters integrate a contactor plus thermal relay. The calculator's BOM includes a motor soft-starter or VFD with integrated protection per pump rating.

Size your own configuration

Run the calculator for your exact load and get a full BOM + FOB price.

Open calculator Request a Quote

Related