Estimated total (FOB): $434,382 · 2000 kVA transformer
Bill of materials
| Item | Specification | Qty | Price (USD) |
|---|---|---|---|
| HV incoming panel (XGN15-12) | 630 A · SF6 · 4-way | 1 | $2,350 |
| Main transformer (S13-M-2000/10) | 2000 kVA · Oil-Immersed · Copper · S13 | 1 | $22,331 |
| LV incoming panel (GGD-3150) | 3150 A busbar · In 2887 A | 1 | $7,225 |
| LV feeder panel (×5) (GGD-3150) | distributes 29 circuits | 5 | $36,126 |
| PFC capacitor bank (500 kVAR) | automatic · GCK LV cabinet | 1 | $5,800 |
| Cable branch box (LV) (DFW-0.4) | 1-in / 4-out · 0.4 kV · 630 A | 7 | $4,410 |
| Series reactor (detuned) (CKSG-30.0/0.4) | 30.0 kVAR · 6% · 0.4 kV | 1 | $143 |
| Busway trunking (LV main feeder) (Busway 4000 A) | 4000 A · Cu/Al busway · 120 m · $1329/m | 1 | $159,480 |
| Feeder cable — Beam pump 1 (×29) (YJV 50 mm²) | 50 mm² Cu · 128 A · ΔU 3.0% · $25.2/m | 29 | $87,696 |
| Branch trunk cable (LV → branch box 1) (YJV 120 mm² ×2) | 2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m | 2 | $16,512 |
| Branch trunk cable (LV → branch box 2) (YJV 120 mm² ×2) | 2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m | 2 | $16,512 |
| Branch trunk cable (LV → branch box 3) (YJV 120 mm² ×2) | 2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m | 2 | $16,512 |
| Branch trunk cable (LV → branch box 4) (YJV 120 mm² ×2) | 2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m | 2 | $16,512 |
| Branch trunk cable (LV → branch box 5) (YJV 120 mm² ×2) | 2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m | 2 | $16,512 |
| Branch trunk cable (LV → branch box 6) (YJV 120 mm² ×2) | 2× 120 mm² Cu · 513 A · ΔU 2.5% · $68.8/m | 2 | $16,512 |
| Branch trunk cable (LV → branch box 7) (YJV 50 mm²) | 50 mm² Cu · 128 A · ΔU 3.0% · $25.2/m | 1 | $3,024 |
| Main busbar (Cu) (Cu 125×10) | 125×10 · 2500 A rating · ref $147.8/m | included | POA |
| Grounding electrode (Φ20mm × 2.5m rod) | R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω | 13 | $125 |
| Soft starter cabinet (largest motor) (250 kW) | Soft starter (3.0× In) · start dip 2.3% | 1 | $6,600 |
| Injection pump soft starter / protection (250 kW) | high-pressure injection pump · soft-start + overload/underload protection | 4 | POA |
| ESP variable-frequency drive (VFD) (90 kW) | ESP soft-start + speed control · downhole pump protection | 5 | POA |
Single-line diagram
How it was calculated
- Beam pumps: 20 × 37 kW = 740 kW
- Injection pumps: 4 × 250 kW = 1,000 kW
- ESP motors: 5 × 90 kW = 450 kW
- Connected load = 2,190 kW → demand P = 2,190 × 0.75 = 1,643 kW
- Largest motor start (motor-starting): Sstart = 250 ÷ (0.9×0.85) × 3.0 = 980 kVA → dip = 2.3% vs limit 15%
- Loads: P=2,190 kW, PF 0.85, 29 circuits
- Demand: 2,190 × 0.75 = 1,643 kW
- PFC: Qc = 1,643 × (0.620 − 0.329) = 478 kVAR → 500 kVAR bank
- Transformer: S = 1,643 ÷ 0.95 = 1728.9 kVA → 2,000 kVA standard
- Loading: 1,729 ÷ 2,000 = 86% (good range)
- Voltage regulation: 86% × 4% × sinφ ≈ 1.1% at full load
- HV: In 115.5 A, Isc 14.4 kA → XGN15-12
成本敏感因素
- 设备 — 变压器/开关柜/逆变器是最大单项。
- 储能 — 电池是最大变量。
- 铜价与运费 — 铜价联动线缆与运费使到岸成本 ±5–10% 波动。
常见问题
油田游梁式抽油机电机用多大电压?
游梁式抽油机电机 45 kW 以下典型用 0.4 kV,更大机组用 0.66 kV 或 1.14 kV 以降低分散井场的电缆损耗。37 kW 机组用 0.4 kV;井距 1-2 km 的井场宜采用 10/0.66 kV 或 10/1.14 kV 配电,每簇配一台箱式变电站。
油田电机为什么需要软启动?
直接启动电流为额定值的 5-7 倍,会使弱而长的馈线电压跌到 85% 以下,导致相邻泵停机。软启动器把启动电流限制在 2.5-3.5 倍、10-30 秒内斜坡升矩。这在离网或长放射式油田馈线上尤其重要;计算器校核电机启动压降并推荐软启动或变频。
什么是电潜泵(ESP),它如何供电?
电潜泵(ESP)是由潜油电机驱动的井下离心泵,地面经升压变压器和变频器供电。典型 90 kW ESP 由专用 10/0.66-3.3 kV 馈线经变频器供电,使泵速匹配井的供液能力。ESP 对电压质量敏感,因此谐波与压降控制很重要。
油田什么时候适合用离网供电系统?
离网(柴油/燃气发电 + 储能)适合偏远井场,因为电网接入每公里线路成本约 2-5 万美元。典型离网油田负荷 50-500 kW。用伴生气发电可比柴油省 60-80% 燃料费;计算器对离网方案与并网方案并列报价。
多井油田该取多大的需用系数?
20 台抽油机不会同时满载运行,需用系数典型取 0.7-0.8;注水泵和 ESP 负荷更连续,取 0.8-0.9。计算器默认 0.75 并可现场调整,避免变压器超配 25-35%。
油田箱式变电站遵循哪些标准?
油田箱式变电站遵循 GB/T 17467(预装式变电站)和 IEC 62271-202(高/低压预装式变电站),外壳按危险区域分级做防爆或全天候防护。变压器遵循 IEC 60076;计算器 BOM 会逐项标注适用标准依据。