One-Stop Supply of Conventional & Solar Power Equipment · Power Distribution System Design

500kW 油田供电系统(2026年第三季度中国供应商价格)

500 kW Oilfield Power System Cost Breakdown (Q3 2026 China Supplier Pricing) — itemized bill of materials and FOB pricing for a typical configuration.

Last updated: 2026-09-12 · copper-linked items track the daily LME copper price

Estimated total (FOB): $65,065 · 315 kVA transformer

Bill of materials

ItemSpecificationQtyPrice (USD)
HV incoming panel (XGN15-12)630 A · SF6 · 4-way1$2,350
Main transformer (S13-M-315/10)315 kVA · Oil-Immersed · Copper · S131$5,341
LV incoming panel (GGD-630)630 A busbar · In 455 A1$2,676
LV feeder panel (×2) (GGD-630)distributes 10 circuits2$5,352
PFC capacitor bank (100 kVAR)automatic · GCK LV cabinet1$1,800
Cable branch box (LV) (DFW-0.4)1-in / 4-out · 0.4 kV · 630 A2$1,260
Series reactor (detuned) (CKSG-6.0/0.4)6.0 kVAR · 6% · 0.4 kV1$41
Main feeder cable (TX→LV) (YJV 0.6/1kV 300 mm²)300 mm² Cu · ΔU 1.77% @ 120 m · $154.0/m1$18,480
Feeder cable — Beam pump 1 (×10) (YJV 25 mm²)25 mm² Cu · 63 A · ΔU 2.9% · $12.6/m10$15,120
Branch trunk cable (LV → branch box 1) (YJV 120 mm²)120 mm² Cu · 251 A · ΔU 2.4% · $68.8/m1$8,256
Branch trunk cable (LV → branch box 2) (YJV 50 mm²)50 mm² Cu · 126 A · ΔU 2.9% · $25.2/m1$3,024
Main busbar (Cu) (Cu 40×4)40×4 · 480 A rating · ref $18.9/mincludedPOA
Grounding electrode (Φ20mm × 2.5m rod)R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω13$125
Soft starter cabinet (largest motor) (37 kW)Soft starter (3.0× In) · start dip 1.9%1$1,240

Single-line diagram

CTCT 30/5APTPT 10kV/100V50/5151NHV incomingXGN15-12630 A - SF6 - 4-wayS13-M-315/10315 kVAZ = 4%Oil-Immersed - Copper - S13kWhmeteringLV incomingGGD-6300.4 kV LV busbar40x4 Cu - 480 ASPDPFC 100 kVAR+ detuned reactorLV feeder panel x2 - 10 circuitsBeam pump 1 - 63 AYJV 25 mm2Beam pump 2 - 63 AYJV 25 mm2Beam pump 3 - 63 AYJV 25 mm2Beam pump 4 - 63 AYJV 25 mm2Beam pump 5 - 63 AYJV 25 mm2Beam pump 6 - 63 AYJV 25 mm2Beam pump 7 - 63 AYJV 25 mm2Beam pump 8 - 63 AYJV 25 mm2Beam pump 9 - 63 AYJV 25 mm2Beam pump 10 - 63 AYJV 25 mm2Grounding 13xdia20mmx2.5m rodCable branch box DFW-0.4 x2 (1-in / 4-out)
LEGENDBreaker (52)DisconnectorCTCT (current transformer)PTPT (voltage transformer)50/51Protection relay 50/51/51N/87kWhMeter (kWh)SPD (surge protection)Transformer

How it was calculated

成本敏感因素

  • 设备 — 变压器/开关柜/逆变器是最大单项。
  • 储能 — 电池是最大变量。
  • 铜价与运费 — 铜价联动线缆与运费使到岸成本 ±5–10% 波动。

常见问题

油田游梁式抽油机电机用多大电压?
游梁式抽油机电机 45 kW 以下典型用 0.4 kV,更大机组用 0.66 kV 或 1.14 kV 以降低分散井场的电缆损耗。37 kW 机组用 0.4 kV;井距 1-2 km 的井场宜采用 10/0.66 kV 或 10/1.14 kV 配电,每簇配一台箱式变电站。
油田电机为什么需要软启动?
直接启动电流为额定值的 5-7 倍,会使弱而长的馈线电压跌到 85% 以下,导致相邻泵停机。软启动器把启动电流限制在 2.5-3.5 倍、10-30 秒内斜坡升矩。这在离网或长放射式油田馈线上尤其重要;计算器校核电机启动压降并推荐软启动或变频。
什么是电潜泵(ESP),它如何供电?
电潜泵(ESP)是由潜油电机驱动的井下离心泵,地面经升压变压器和变频器供电。典型 90 kW ESP 由专用 10/0.66-3.3 kV 馈线经变频器供电,使泵速匹配井的供液能力。ESP 对电压质量敏感,因此谐波与压降控制很重要。
油田什么时候适合用离网供电系统?
离网(柴油/燃气发电 + 储能)适合偏远井场,因为电网接入每公里线路成本约 2-5 万美元。典型离网油田负荷 50-500 kW。用伴生气发电可比柴油省 60-80% 燃料费;计算器对离网方案与并网方案并列报价。
多井油田该取多大的需用系数?
20 台抽油机不会同时满载运行,需用系数典型取 0.7-0.8;注水泵和 ESP 负荷更连续,取 0.8-0.9。计算器默认 0.75 并可现场调整,避免变压器超配 25-35%。
油田箱式变电站遵循哪些标准?
油田箱式变电站遵循 GB/T 17467(预装式变电站)和 IEC 62271-202(高/低压预装式变电站),外壳按危险区域分级做防爆或全天候防护。变压器遵循 IEC 60076;计算器 BOM 会逐项标注适用标准依据。

计算你自己的配置

输入你的实际负荷,获得完整 BOM 与 FOB 报价。

Open calculator Request a Quote

相关页面