🌍 حاسبة مقاومة التأريض
احسب مقاومة قضيب أرضي رأسي من مقاومية التربة وطول القضيب وقطره، وأوجد عدد القضبان اللازمة لتحقيق مقاومة مستهدفة.
⚙️ Electrode
📊 Result
للمهندسين الذين يصممون أنظمة التأريض للمحطات الفرعية والمعدات.
كيف يتم الحساب
· قضيب واحد: R = ρ ÷ (2πL) × ln(4L ÷ d).
· قضبان متعددة: Rn = R ÷ (n × 0.8)، بمعامل استفادة 0.8.
· القضبان المطلوبة: n = ceil(R ÷ (الهدف × 0.8)).
المعايير المرجعية
| Standard | Scope |
|---|---|
| IEEE 80 | دليل السلامة في تأريض محطات التيار المتردد الفرعية |
| IEC 62305 | الحماية من الصواعق — نهاية الأرض |
مثال محسوب — تربة 100 Ω·m → 39.6 Ω لكل قضيب
1. ρ = 100 Ω·m، L = 2.5 م، d = 20 مم.
2. R = 100 ÷ (2π × 2.5) × ln(4 × 2.5 ÷ 0.02) = 6.37 × 6.21 = 39.6 Ω.
3. للوصول إلى ≤ 10 Ω: n = ceil(39.6 ÷ (10 × 0.8)) = 5 قضبان.
FAQ
What is an acceptable earth resistance for a substation?
IEEE 80 recommends Substation ground resistance below 1-5 ohms for large installations, while IEC 60364 allows up to 10 ohms for many LV systems. A 1-ohm target is standard for MV substations; the calculator sizes the number of rods to meet your target.
How many earth rods do I need?
Rod count depends on soil resistivity and target resistance. In 100 ohm-m soil, a single 2.4 m rod gives roughly 35-40 ohms; reaching 10 ohms needs 4-5 rods spaced 2.4 m apart, and 1 ohm needs 40-50 rods (or a grid). The calculator computes the single-rod resistance and the count for the target.
How does soil resistivity affect grounding?
Soil resistivity varies from ~10 ohm-m (wet clay) to 1000+ ohm-m (dry rock). Higher resistivity means more rods or a larger grid for the same resistance. Sandy or rocky sites often need chemical treatment or deep-driven rods. The calculator takes soil resistivity as input and sizes the electrode accordingly.
Why does grounding rod spacing matter?
Rods placed closer than their length interfere, raising the combined resistance. Spacing rods at least one rod length apart (typically 2.4 m) gives nearly independent rods and the full benefit. Closer spacing wastes material. The calculator applies the standard spacing rule.
What is the difference between earth resistance and touch/step voltage?
Earth resistance is the electrode-to-earth impedance; touch and step voltages are the voltages a person can experience during a fault, which depend on the surface layer and grid geometry, not just resistance. IEEE 80 limits touch voltage to ~50-100 V depending on fault duration. The calculator sizes for resistance; full touch/step study needs IEEE 80 grid analysis.
تضمين هذه الحاسبة
أضف هذه الحاسبة إلى موقعك مجانًا. يتكيف إطار iframe مع أي عرض ويعمل بالكامل داخل متصفح زوارك.
أدوات ذات صلة
تقديرات مرجعية (فوب تشينغداو، إكسو) لأغراض التصميم الأولي فقط — وليست عرضًا نهائيًا. تأكد من التحجيم وفقًا لمشروعك والمعايير المحلية.
Send my complete design report
Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.
Your data stays private. No spam — only a reply to your enquiry.