ESH working point
Operating point study — SCB14-250/10/0.4
Change the load and the ambient temperature; the hot-spot and winding temperature are recomputed from the reference network. Values are precomputed at build time on the same network used across this catalogue (10 m HV cable, 20 m LV cable, IEC 60909), so they match the figures on the product page.
SCB14-250/10/0.4
250 kVA · 10 kV / 0.4 kV · uk 4.5 %- Hot-spot
- 90.4 °C
- limit 140 °C
- Winding rise
- 42.4 K
- natural cooling
- LV voltage drop
- 2.30 %
- min V 0.977 pu
Short-circuit current stays at 8.32 kA regardless of load — it is set by the transformer impedance, not by loading. Grid strength moves it by under 6 % across 100–2000 MVA, so there is no slider for it.