Sistem Distribusi Industri 500 kVA
500 kVA · S13-M-500/10
Sistem distribusi trafo terendam oli 500 kVA yang umum untuk pabrik industri — trafo, switchgear HV/LV, koreksi faktor daya, dan perkabelan.
Daftar Bahan
| Equipment | Model | Specification | Qty | Price |
|---|---|---|---|---|
| HV incoming panel | KYN28A-12-630-315 | 630 A / 31.5 kA · vacuum | 1 | Kutipan waktu nyata |
| Main transformer | S13-M-500/10 | 500 kVA · Oil-Immersed · Copper · S13 | 1 | Kutipan waktu nyata |
| LV incoming panel | GGD-1000 | 1000 A busbar · In 722 A | 1 | Kutipan waktu nyata |
| LV feeder panel | GGD-1000 | distributes 6 circuits | 1 | Kutipan waktu nyata |
| PFC capacitor bank | 200 kVAR | automatic · GCK LV cabinet | 1 | Kutipan waktu nyata |
| Cable branch box (LV) | DFW-0.4 | 1-in / 4-out · 0.4 kV · 630 A | 1 | Kutipan waktu nyata |
| Series reactor (detuned) | CKSG-12.0/0.4 | 12.0 kVAR · 6% · 0.4 kV | 1 | Kutipan waktu nyata |
| Main feeder cable (TX→LV) | YJV 0.6/1kV 240 mm² ×2 | 2× 240 mm² Cu · ΔU 0.88% @ 60 m · $123.0/m | 2 | Kutipan waktu nyata |
| Feeder cable — LV feeder circuit 1 (×6) | YJV 50 mm² | 50 mm² Cu · 150 A · ΔU 1.8% · $25.2/m | 6 | Kutipan waktu nyata |
| Branch trunk cable (LV → branch box 1) | YJV 150 mm² | 150 mm² Cu · 301 A · ΔU 1.2% · $86.0/m | 1 | Kutipan waktu nyata |
| Main busbar (Cu) | Cu 63×6.3 | 63×6.3 · 900 A rating · ref $47/m | included | Kutipan waktu nyata |
| Grounding electrode | Φ20mm × 2.5m rod | R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω | 13 | Kutipan waktu nyata |
Harga pasti dihitung secara real-time melalui kalkulator pilihan dan penawaran instan — masukkan parameter aktual Anda untuk mendapatkan penawaran FOB yang tepat.
Langkah desain
1. Loads: P=500 kW, PF 0.80, 6 circuits
2. Demand: 500 × 0.8 = 400 kW
3. PFC: Qc = 400 × (0.750 − 0.329) = 169 kVAR → 200 kVAR bank
4. Transformer: S = 400 ÷ 0.95 = 421.1 kVA → 500 kVA standard
4b. Loading: 421 ÷ 500 = 84% (good range)
4c. Voltage regulation: 84% × 4% × sinφ ≈ 1.1% at full load
5. HV: In 28.9 A, Isc 28.9 kA → KYN28A-12-630-315
6. LV: In 722 A, Isc 17.6 kA (Xfmr Z 4% + system 0.1%) → GGD-1000, 1 feeder panel(s)
6b. Cable branch boxes: 1 × DFW-0.4 (1-in/4-out) for feeder grouping
7. Grounding: R₁ 39.6 Ω → 13 rod(s)
8. Main feeder: 2× 240 mm² · ΔU 0.88% — OK
Catatan desain
Pricing basis: FOB Qingdao (EXW) equipment price. Freight, duty and installation are not included — add for landed economics.
Transformer loading: 84% at design demand — good range.
Short-circuit check: HV 28.9 kA vs 31.5 kA (1.1× margin) · LV 17.6 kA vs 25 kA (1.4× margin).
Voltage regulation: ≈ 1.1% at full load (typical limit 5%).
Power factor correction: 200 kVAR automatic bank corrects PF to 0.95.
Copper price linkage: Copper-wound transformer price tracks LME copper (current $14,219/t · 2026-09-12 · LME Copper (Sina hf_CAD)).
Parallel conductors: Single-cable ampacity exceeded — parallel conductors specified: main feeder 2× 240 mm² (per IEC 60364-5-52 / GB 50054).
Cable & grounding pricing: Cable conductors and grounding are priced from the confirmed cables-trays-grounding price reference (per-metre copper YJV; aluminium remains POA). The main copper busbar is POA — its length is project-specific.
Busway (high-current feeders): For LV feeders above ~2500 A, a busway (母线槽) trunking system is recommended instead of parallel cables.
Diagram Garis Tunggal