1600 kVA Kutu Tipi Trafo Merkezi Sistemi
1600 kVA · YB-S11-1600/10
Büyük ticari alanlar ve hafif endüstriyel yükler için tipik bir 1600 kVA kutu tipi (kompakt) trafo merkezi.
Malzeme Listesi
| Equipment | Model | Specification | Qty | Price |
|---|---|---|---|---|
| Main substation | YB-S11-1600/10 | 1600 kVA · Box-Type · oil internal · S11 | 1 | Gerçek zamanlı teklif |
| LV feeder panel | GGD-2500 | distributes 6 circuits | 1 | Gerçek zamanlı teklif |
| PFC capacitor bank | 600 kVAR | automatic · GCK LV cabinet | 1 | Gerçek zamanlı teklif |
| Series reactor (detuned) | CKSG-36.0/0.4 | 36.0 kVAR · 6% · 0.4 kV | 1 | Gerçek zamanlı teklif |
| Main feeder cable (TX→LV) | YJV 0.6/1kV 300 mm² ×5 | 5× 300 mm² Cu · ΔU 0.90% @ 60 m · $154.0/m | 5 | Gerçek zamanlı teklif |
| Feeder cable — LV feeder circuit 1 (×6) | YJV 120 mm² ×2 | 2× 120 mm² Cu · 481 A · ΔU 1.2% · $68.8/m | 12 | Gerçek zamanlı teklif |
| Main busbar (Cu) | Cu 125×10 | 125×10 · 2500 A rating · ref $147.8/m | included | Gerçek zamanlı teklif |
| Grounding electrode | Φ20mm × 2.5m rod | R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω | 13 | Gerçek zamanlı teklif |
Kesin fiyatlar, anlık seçim ve teklif hesaplayıcıyla gerçek zamanlı olarak hesaplanır; kesin bir FOB teklifi için gerçek parametrelerinizi girin.
Tasarım adımları
1. Loads: P=1,600 kW, PF 0.80, 6 circuits
2. Demand: 1,600 × 0.8 = 1,280 kW
3. PFC: Qc = 1,280 × (0.750 − 0.329) = 539 kVAR → 600 kVAR bank
4. Transformer: S = 1,280 ÷ 0.95 = 1347.4 kVA → 1,600 kVA standard
4b. Loading: 1,347 ÷ 1,600 = 84% (good range)
4c. Voltage regulation: 84% × 4% × sinφ ≈ 1.1% at full load
5. HV unit integrated in substation (In 92.4 A)
6. LV: In 2309 A, Isc 53.5 kA (Xfmr Z 4% + system 0.3%) → GGD-2500 (integrated), 1 feeder panel(s)
7. Grounding: R₁ 39.6 Ω → 13 rod(s)
8. Main feeder: 5× 300 mm² · ΔU 0.90% — OK
Tasarım notları
Pricing basis: FOB Qingdao (EXW) equipment price. Freight, duty and installation are not included — add for landed economics.
Transformer loading: 84% at design demand — good range.
Short-circuit check: HV 28.9 kA vs 31.5 kA (1.1× margin) · LV 53.5 kA vs 65 kA (1.2× margin).
Voltage regulation: ≈ 1.1% at full load (typical limit 5%).
Power factor correction: 600 kVAR automatic bank corrects PF to 0.95.
Parallel conductors: Single-cable ampacity exceeded — parallel conductors specified: main feeder 5× 300 mm², LV feeder circuit 1 2× 120 mm², LV feeder circuit 2 2× 120 mm², LV feeder circuit 3 2× 120 mm², LV feeder circuit 4 2× 120 mm² … +2 more (per IEC 60364-5-52 / GB 50054).
Cable & grounding pricing: Cable conductors and grounding are priced from the confirmed cables-trays-grounding price reference (per-metre copper YJV; aluminium remains POA). The main copper busbar is POA — its length is project-specific.