QDTB® Transformatör

500 kVA Endüstriyel Dağıtım Sistemi

500 kVA · S13-M-500/10

Endüstriyel tesisler için tipik bir 500 kVA yağlı transformatör dağıtım sistemi - transformatör, HV/LV şalt donanımı, güç faktörü düzeltmesi ve kablolama.

Malzeme Listesi

EquipmentModelSpecificationQtyPrice
HV incoming panelKYN28A-12-630-315630 A / 31.5 kA · vacuum1Gerçek zamanlı teklif
Main transformerS13-M-500/10500 kVA · Oil-Immersed · Copper · S131Gerçek zamanlı teklif
LV incoming panelGGD-10001000 A busbar · In 722 A1Gerçek zamanlı teklif
LV feeder panelGGD-1000distributes 6 circuits1Gerçek zamanlı teklif
PFC capacitor bank200 kVARautomatic · GCK LV cabinet1Gerçek zamanlı teklif
Cable branch box (LV)DFW-0.41-in / 4-out · 0.4 kV · 630 A1Gerçek zamanlı teklif
Series reactor (detuned)CKSG-12.0/0.412.0 kVAR · 6% · 0.4 kV1Gerçek zamanlı teklif
Main feeder cable (TX→LV)YJV 0.6/1kV 240 mm² ×22× 240 mm² Cu · ΔU 0.88% @ 60 m · $123.0/m2Gerçek zamanlı teklif
Feeder cable — LV feeder circuit 1 (×6)YJV 50 mm²50 mm² Cu · 150 A · ΔU 1.8% · $25.2/m6Gerçek zamanlı teklif
Branch trunk cable (LV → branch box 1)YJV 150 mm²150 mm² Cu · 301 A · ΔU 1.2% · $86.0/m1Gerçek zamanlı teklif
Main busbar (Cu)Cu 63×6.363×6.3 · 900 A rating · ref $47/mincludedGerçek zamanlı teklif
Grounding electrodeΦ20mm × 2.5m rodR₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω13Gerçek zamanlı teklif

Kesin fiyatlar, anlık seçim ve teklif hesaplayıcıyla gerçek zamanlı olarak hesaplanır; kesin bir FOB teklifi için gerçek parametrelerinizi girin.

Tasarım adımları

1. Loads: P=500 kW, PF 0.80, 6 circuits
2. Demand: 500 × 0.8 = 400 kW
3. PFC: Qc = 400 × (0.750 − 0.329) = 169 kVAR → 200 kVAR bank
4. Transformer: S = 400 ÷ 0.95 = 421.1 kVA → 500 kVA standard
4b. Loading: 421 ÷ 500 = 84% (good range)
4c. Voltage regulation: 84% × 4% × sinφ ≈ 1.1% at full load
5. HV: In 28.9 A, Isc 28.9 kA → KYN28A-12-630-315
6. LV: In 722 A, Isc 17.6 kA (Xfmr Z 4% + system 0.1%) → GGD-1000, 1 feeder panel(s)
6b. Cable branch boxes: 1 × DFW-0.4 (1-in/4-out) for feeder grouping
7. Grounding: R₁ 39.6 Ω → 13 rod(s)
8. Main feeder: 2× 240 mm² · ΔU 0.88% — OK

Tasarım notları

Pricing basis: FOB Qingdao (EXW) equipment price. Freight, duty and installation are not included — add for landed economics.
Transformer loading: 84% at design demand — good range.
Short-circuit check: HV 28.9 kA vs 31.5 kA (1.1× margin) · LV 17.6 kA vs 25 kA (1.4× margin).
Voltage regulation: ≈ 1.1% at full load (typical limit 5%).
Power factor correction: 200 kVAR automatic bank corrects PF to 0.95.
Copper price linkage: Copper-wound transformer price tracks LME copper (current $14,219/t · 2026-09-12 · LME Copper (Sina hf_CAD)).
Parallel conductors: Single-cable ampacity exceeded — parallel conductors specified: main feeder 2× 240 mm² (per IEC 60364-5-52 / GB 50054).
Cable & grounding pricing: Cable conductors and grounding are priced from the confirmed cables-trays-grounding price reference (per-metre copper YJV; aluminium remains POA). The main copper busbar is POA — its length is project-specific.
Busway (high-current feeders): For LV feeders above ~2500 A, a busway (母线槽) trunking system is recommended instead of parallel cables.

Tek Hat Şeması

CTCT 30/5APTPT 10kV/100V50/5151NHV incomingKYN28A-12-630-315630 A / 31.5 kA - vacuumS13-M-500/10500 kVAZ = 4%Oil-Immersed - Copper - S13kWhmeteringLV incomingGGD-10000.4 kV LV busbar63x6.3 Cu - 900 ASPDPFC 200 kVAR+ detuned reactorLV feeder panel x1 - 6 circuitsLV feeder circuit 1 - 150 AYJV 50 mm2LV feeder circuit 2 - 150 AYJV 50 mm2LV feeder circuit 3 - 150 AYJV 50 mm2LV feeder circuit 4 - 150 AYJV 50 mm2LV feeder circuit 5 - 150 AYJV 50 mm2LV feeder circuit 6 - 150 AYJV 50 mm2Grounding 13xdia20mmx2.5m rodCable branch box DFW-0.4 x1 (1-in / 4-out)
LEGENDBreaker (52)DisconnectorCTCT (current transformer)PTPT (voltage transformer)50/51Protection relay 50/51/51N/87kWhMeter (kWh)SPD (surge protection)Transformer

Bu Sistemi Gerçek Zamanlı Olarak Tasarlayın ve Teklif Alın

Tam ekipman listesini ve FOB fiyatını almak için gerçek yük parametrelerinizi girin.