Hệ thống trạm biến áp kiểu hộp 1600 kVA
1600 kVA · YB-S11-1600/10
Trạm biến áp loại hộp (nhỏ gọn) 1600 kVA điển hình dành cho các khu thương mại lớn và tải công nghiệp nhẹ.
Hóa đơn vật liệu
| Equipment | Model | Specification | Qty | Price |
|---|---|---|---|---|
| Main substation | YB-S11-1600/10 | 1600 kVA · Box-Type · oil internal · S11 | 1 | Báo giá thời gian thực |
| LV feeder panel | GGD-2500 | distributes 6 circuits | 1 | Báo giá thời gian thực |
| PFC capacitor bank | 600 kVAR | automatic · GCK LV cabinet | 1 | Báo giá thời gian thực |
| Series reactor (detuned) | CKSG-36.0/0.4 | 36.0 kVAR · 6% · 0.4 kV | 1 | Báo giá thời gian thực |
| Main feeder cable (TX→LV) | YJV 0.6/1kV 300 mm² ×5 | 5× 300 mm² Cu · ΔU 0.90% @ 60 m · $154.0/m | 5 | Báo giá thời gian thực |
| Feeder cable — LV feeder circuit 1 (×6) | YJV 120 mm² ×2 | 2× 120 mm² Cu · 481 A · ΔU 1.2% · $68.8/m | 12 | Báo giá thời gian thực |
| Main busbar (Cu) | Cu 125×10 | 125×10 · 2500 A rating · ref $147.8/m | included | Báo giá thời gian thực |
| Grounding electrode | Φ20mm × 2.5m rod | R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω | 13 | Báo giá thời gian thực |
Giá chính xác được tính toán theo thời gian thực bằng công cụ tính toán lựa chọn và báo giá tức thì — nhập các thông số thực tế của bạn để có báo giá FOB chính xác.
Các bước thiết kế
1. Loads: P=1,600 kW, PF 0.80, 6 circuits
2. Demand: 1,600 × 0.8 = 1,280 kW
3. PFC: Qc = 1,280 × (0.750 − 0.329) = 539 kVAR → 600 kVAR bank
4. Transformer: S = 1,280 ÷ 0.95 = 1347.4 kVA → 1,600 kVA standard
4b. Loading: 1,347 ÷ 1,600 = 84% (good range)
4c. Voltage regulation: 84% × 4% × sinφ ≈ 1.1% at full load
5. HV unit integrated in substation (In 92.4 A)
6. LV: In 2309 A, Isc 53.5 kA (Xfmr Z 4% + system 0.3%) → GGD-2500 (integrated), 1 feeder panel(s)
7. Grounding: R₁ 39.6 Ω → 13 rod(s)
8. Main feeder: 5× 300 mm² · ΔU 0.90% — OK
Ghi chú thiết kế
Pricing basis: FOB Qingdao (EXW) equipment price. Freight, duty and installation are not included — add for landed economics.
Transformer loading: 84% at design demand — good range.
Short-circuit check: HV 28.9 kA vs 31.5 kA (1.1× margin) · LV 53.5 kA vs 65 kA (1.2× margin).
Voltage regulation: ≈ 1.1% at full load (typical limit 5%).
Power factor correction: 600 kVAR automatic bank corrects PF to 0.95.
Parallel conductors: Single-cable ampacity exceeded — parallel conductors specified: main feeder 5× 300 mm², LV feeder circuit 1 2× 120 mm², LV feeder circuit 2 2× 120 mm², LV feeder circuit 3 2× 120 mm², LV feeder circuit 4 2× 120 mm² … +2 more (per IEC 60364-5-52 / GB 50054).
Cable & grounding pricing: Cable conductors and grounding are priced from the confirmed cables-trays-grounding price reference (per-metre copper YJV; aluminium remains POA). The main copper busbar is POA — its length is project-specific.
Busway (high-current feeders): For LV feeders above ~2500 A, a busway (母线槽) trunking system is recommended instead of parallel cables.
Sơ đồ đường đơn
Thiết kế và báo giá hệ thống này trong thời gian thực
Nhập thông số tải thực tế của bạn để có được danh sách thiết bị chính xác và giá FOB.