Système de distribution pour bâtiments commerciaux de 1 250 kVA
1600 kVA · SCB13-1600/10
Un système de distribution par transformateur de type sec typique de 1 250 kVA pour les bâtiments commerciaux et les centres de données.
Nomenclature
| Equipment | Model | Specification | Qty | Price |
|---|---|---|---|---|
| HV incoming panel | KYN28A-12-630-315 | 630 A / 31.5 kA · vacuum | 1 | Devis en temps réel |
| Main transformer | SCB13-1600/10 | 1600 kVA · Dry-Type · Copper · SCB13 | 1 | Devis en temps réel |
| LV incoming panel | GGD-2500 | 2500 A busbar · In 2309 A | 1 | Devis en temps réel |
| LV feeder panel (×2) | GGD-2500 | distributes 8 circuits | 2 | Devis en temps réel |
| PFC capacitor bank | 400 kVAR | automatic · GCK LV cabinet | 1 | Devis en temps réel |
| Cable branch box (LV) | DFW-0.4 | 1-in / 4-out · 0.4 kV · 630 A | 1 | Devis en temps réel |
| Series reactor (detuned) | CKSG-24.0/0.4 | 24.0 kVAR · 6% · 0.4 kV | 1 | Devis en temps réel |
| Main feeder cable (TX→LV) | YJV 0.6/1kV 300 mm² ×5 | 5× 300 mm² Cu · ΔU 0.90% @ 60 m · $154.0/m | 5 | Devis en temps réel |
| Feeder cable — LV feeder circuit 1 (×8) | YJV 240 mm² | 240 mm² Cu · 361 A · ΔU 0.9% · $123.0/m | 8 | Devis en temps réel |
| Branch trunk cable (LV → branch box 1) | YJV 240 mm² ×4 | 4× 240 mm² Cu · 1443 A · ΔU 0.9% · $123.0/m | 4 | Devis en temps réel |
| Main busbar (Cu) | Cu 125×10 | 125×10 · 2500 A rating · ref $147.8/m | included | Devis en temps réel |
| Grounding electrode | Φ20mm × 2.5m rod | R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω | 13 | Devis en temps réel |
Les prix exacts sont calculés en temps réel par le calculateur de sélection et de devis instantané — entrez vos paramètres réels pour un devis FOB précis.
Étapes de conception
1. Loads: P=1,700 kW, PF 0.85, 8 circuits
2. Demand: 1,700 × 0.7 = 1,190 kW
3. PFC: Qc = 1,190 × (0.620 − 0.329) = 346 kVAR → 400 kVAR bank
4. Transformer: S = 1,190 ÷ 0.95 = 1252.6 kVA → 1,600 kVA standard
4b. Loading: 1,253 ÷ 1,600 = 78% (good range)
4c. Voltage regulation: 78% × 6% × sinφ ≈ 1.5% at full load
5. HV: In 92.4 A, Isc 28.9 kA → KYN28A-12-630-315
6. LV: In 2309 A, Isc 36.5 kA (Xfmr Z 6% + system 0.3%) → GGD-2500, 2 feeder panel(s)
6b. Cable branch boxes: 1 × DFW-0.4 (1-in/4-out) for feeder grouping
7. Grounding: R₁ 39.6 Ω → 13 rod(s)
8. Main feeder: 5× 300 mm² · ΔU 0.90% — OK
Notes de conception
Pricing basis: FOB Qingdao (EXW) equipment price. Freight, duty and installation are not included — add for landed economics.
Transformer loading: 78% at design demand — good range.
Short-circuit check: HV 28.9 kA vs 31.5 kA (1.1× margin) · LV 36.5 kA vs 50 kA (1.4× margin).
Voltage regulation: ≈ 1.5% at full load (typical limit 5%).
Power factor correction: 400 kVAR automatic bank corrects PF to 0.95.
Copper price linkage: Copper-wound transformer price tracks LME copper (current $14,219/t · 2026-09-12 · LME Copper (Sina hf_CAD)).
Parallel conductors: Single-cable ampacity exceeded — parallel conductors specified: main feeder 5× 300 mm², branch trunk 1 4× 240 mm² (per IEC 60364-5-52 / GB 50054).
Cable & grounding pricing: Cable conductors and grounding are priced from the confirmed cables-trays-grounding price reference (per-metre copper YJV; aluminium remains POA). The main copper busbar is POA — its length is project-specific.
Busway (high-current feeders): For LV feeders above ~2500 A, a busway (母线槽) trunking system is recommended instead of parallel cables.
Diagramme unifilaire
Concevoir et devis ce système en temps réel
Entrez vos paramètres de charge réels pour obtenir la liste exacte des équipements et le prix FOB.