SFFZ-315/0.4/0.22

Other Series315 kVA • 0.4/0.22 kV

Product Image & Parameters

315kVAOther

SFFZ-315/0.4/0.22

Other Series

Capacity
315kVA
HV Voltage
0.4kV
LV Voltage
0.22kV
Efficiency
2Level
Amorphous Alloy CoreEnergy SavingLow Loss

TECHNICAL DRAWING

Model: SFFZ-315/0.4/0.22 | Type: Dry-Type Transformer | Capacity: 315 kVA

FRONT VIEW

HVLV1U1V1W2U2V2W2N180mm240mm

SIDE VIEW

Ventilation135mm

TOP VIEW

1U1V1W2U2V2W2N180mm135mm

TERMINAL BLOCK

HV TERMINAL BLOCK1U1V1W1N1PELV TERMINAL BLOCK2U2V2W2N2PE2122Terminal Block ConfigurationTin-Plated Copper Busbar

ELECTRIC SCHEMATIC DIAGRAM

HV WINDING (Delta)1U1V1WLV WINDING (Star)2U2V2W2NVector GroupDyn11 (IEC)

SPECIFICATIONS

1. Model:SFFZ-315/0.4/0.22
2. Type:Dry-Type Transformer
3. Capacity:315 kVA
4. Frequency:50 Hz
5. HV Voltage:0.4 kV
6. LV Voltage:0.22 kV
7. HV Current:454.66A
8. LV Current:826.66A
9. Vector Group:Dyn11 (IEC)
10. Impedance:6%
11. Insulation Level:H (180°C)
12. Temperature Rise:65K
13. No-Load Loss:8998W
14. Load Loss:22495W
15. No-Load Current:1%
16. Cooling Method:AN
17. Tap Changer:±2×2.5% 多档
18. Standard:IEC 60076
19. Dimensions:1200×900×1600mm
20. Weight:-
LEGEND:
Iron Core
HV Winding/Bushing
LV Winding/Bushing
Dimension Line

Product Description

315kVA, 3-phase isolation, dry-type transformer, 50Hz, primary 400V (HV 400V), secondary 220V (LV 220V), Standard, insulation H, impedance 6%

Related Keywords

SFFZ-315/0.4/0.22 isolation control transformer315kVA control transformerprimary 0.4kV secondary 0.22kVSFFZ split winding transformer for power plant auxiliary system

SFFZ-315/0.4/0.22 FAQ

What are the main application scenarios for SFFZ-315/0.4/0.22?
The SFFZ-315/0.4/0.22 (Other series special/isolation/control transformers) with rated capacity of 315 kVA, HV side 0.4 kV, LV side 0.22 kV, is widely used in industrial distribution, commercial buildings, and power systems. It can be flexibly configured according to actual project requirements.
What are the technical specifications of SFFZ-315/0.4/0.22?
Key specs: Capacity 315 kVA, HV 0.4 kV, LV 0.22 kV, Frequency 50 Hz, Impedance 6%, Vector Group Dyn11 (IEC), Cooling AN, Standard IEC 60076.
Can SFFZ-315/0.4/0.22 be customized?
Yes. QDTB® offers comprehensive OEM/ODM customization. Parameters such as capacity, voltage ratio, cooling method, vector group, and protection class can be adjusted. 23+ years of manufacturing experience ensures consistent quality.
How to get a quote and technical documentation?
Contact us via the "Send Inquiry" button below, or reach our sales team at Alice@qdtb-transformer.com / +86 13698683193. We will provide detailed quotations and technical documentation within 24 hours.

Interested in SFFZ-315/0.4/0.22?