ESH working point

Operating point study — SCB14-250/10/0.4

Change the load and the ambient temperature; the hot-spot and winding temperature are recomputed from the reference network. Values are precomputed at build time on the same network used across this catalogue (10 m HV cable, 20 m LV cable, IEC 60909), so they match the figures on the product page.

SCB14-250/10/0.4

250 kVA · 10 kV / 0.4 kV · uk 4.5 %
Hot-spot
90.4 °C
limit 140 °C
Winding rise
42.4 K
natural cooling
LV voltage drop
2.30 %
min V 0.977 pu

Short-circuit current stays at 8.32 kA regardless of load — it is set by the transformer impedance, not by loading. Grid strength moves it by under 6 % across 100–2000 MVA, so there is no slider for it.