🔗 PV Kablo Gerilim Düşümü Hesaplayıcısı

Bir PV dizisinin DC tarafı gerilim düşümünü ve hat kaybını kontrol edin, kablo ampasitesini (1.25 × Isc) doğrulayın ve %2 düşüm yönergesinin altında kalan minimum kesiti seçin.

Hesaplamaya Başla
⚠️ DC drop guideline < 2% per IEC 60364 / 62548.

🔗 String & Cable

📊 Voltage-Drop Result

Enter the string current and distance — voltage drop and cable sizing appear here instantly.

DC ana hat kablolarını ve konnektörleri boyutlandıran güneş enerjisi montajcıları için.

Nasıl hesaplanır

· Gidiş-dönüş direnç: R = 2 × ρ × L ÷ A (ρ bakır 0.0175 Ω·mm²/m).

· Gerilim düşümü: VD = I × R; VD% = VD ÷ V_string × 100.

· Ampasite kontrolü: gerekli ≥ I × 1.25; konnektör (MC4) anma ≥ I × 1.25.

Referans standartlar

StandardScope
IEC 60364Alçak gerilim elektrik tesisatları (kablo ampasitesi)
NEC 690Güneş fotovoltaik sistemleri (iletken ampasitesi 1.25 × Isc)

Çözümlü örnek — 50 m üzerinden 13 A → 4 mm²'de %1.42

1. Dizi akımı 13 A, mesafe 50 m, 4 mm², dizi gerilimi 400 V.

2. R = 2 × 0.0175 × 50 ÷ 4 = 0.44 Ω; VD = 13 × 0.44 = 5.7 V = %1.42.

3. Ampasite: 13 × 1.25 = 16.3 A ≤ 32 A (4 mm²) uygun.

4. %1.42, %2 yönergesi içindedir — 4 mm² yeterlidir.

FAQ

What voltage drop is acceptable in a PV DC cable?

Design practice limits total DC-side voltage drop to about 2% (IEC 60364 and common PV guidelines), split roughly 1% in the string cabling and 1% in the DC run to the inverter. Higher drop means lost energy — every 1% of drop is roughly 1% of lost annual yield. The calculator checks the drop and recommends the minimum cross-section.

How do I size a PV cable for ampacity?

PV DC cables must carry the string short-circuit current with a safety factor (usually 1.25x Isc, and 1.56x per NEC). For a 550 W module with Isc ~13.9 A and a two-parallel-string combiner, the combined current is ~35 A, so a 6 mm2 copper cable (rated ~40-45 A) is typical. The calculator verifies ampacity and derating.

Copper or aluminum for PV DC cabling?

PV string and DC cables are almost always copper because DC circuits are low-voltage and ampacity-sensitive; aluminium would need a much larger cross-section for the same drop. Copper is also easier to terminate on MC4 connectors. Aluminium appears only in long AC medium-voltage collector runs. The calculator defaults to copper for DC.

How long can a PV DC cable run be?

DC run length is limited by the 2% voltage-drop budget. For a 10 kW string at 500 V DC and 20 A, a 4 mm2 copper cable can run roughly 40-60 m before exceeding 2%. Longer runs need 6-10 mm2 cable or a higher system voltage. The calculator computes the maximum length for a given cross-section.

What DC cable type is used for solar arrays?

PV arrays use double-insulated, UV-resistant solar cable (H1Z2Z2-K / EN 50618, rated 1.5 kV DC and -40 to +90 deg C) for outdoor runs. Single-core copper, usually 4-6 mm2 for strings and 10-35 mm2 for DC mains. The calculator selects cable by ampacity and drop and cites the applicable standard.

Bu hesaplayıcıyı gömün

Bu hesaplayıcıyı kendi web sitenize ücretsiz ekleyin. iframe her genişliğe uyum sağlar ve tamamen ziyaretçinizin tarayıcısında çalışır.

İlgili araçlar

Yalnızca ön tasarım için referans tahminler (FOB Qingdao, EXW) — nihai teklif değildir. Boyutlandırmayı projenize ve yerel standartlara göre doğrulayın.

Send my complete design report

Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.

💬 Chat on WhatsApp

Your data stays private. No spam — only a reply to your enquiry.