EV Şarj İstasyonu Tasarım Hesaplayıcısı
Bir EV şarj istasyonu için trafo ve dağıtımı boyutlandırın — talep yükü, eşzamanlı kullanım faktörü, besleme gerilimi ve referans malzeme listesi.
AC ve DC EV şarj istasyonları için elektrik servisini ve trafoyu boyutlandıran danışmanlar ve montajcılar için.
Hesaplayıcıyı kullanın
Çözümlü örnek
Önceden hesaplanmış bir referans örneği (taranabilir — JavaScript gerekmez). Canlı sonuç için yukarıya kendi parametrelerinizi girin.
Çözümlü örnek — 4×7 kW + 2×22 kW AC + 2×60 kW + 1×120 kW DC
| Quantity | Value |
|---|---|
| Connected load | 312 kW (Σ chargers × rated power) |
| Diversity factor | 0.8 (simultaneous-use factor) |
| Demand load | 312 × 0.8 = 250 kW |
| Demand (apparent) | 250 ÷ 0.95 = 263 kVA |
| Required transformer | next standard ≥ 289 kVA → 315 kVA |
| Supply voltage | 10 kV (MV feed) — recommended for this size |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| AC charger (7 kW) | 7 kW · 1-phase/3-phase | 4 | POA |
| AC charger (22 kW) | 22 kW · 3-phase | 2 | POA |
| DC fast charger (60 kW) | 60 kW · CCS/GB-T | 2 | POA |
| DC fast charger (120 kW) | 120 kW · CCS/GB-T | 1 | POA |
| Distribution transformer | 315 kVA · 10 kV / 0.4 kV · S13 | 1 | POA |
| Total equipment (reference) | POA |
Çözümlü örnek — 4×120 kW DC hızlı şarj merkezi
| Quantity | Value |
|---|---|
| Connected load | 480 kW (Σ chargers × rated power) |
| Diversity factor | 0.9 (simultaneous-use factor) |
| Demand load | 480 × 0.9 = 432 kW |
| Demand (apparent) | 432 ÷ 0.95 = 455 kVA |
| Required transformer | next standard ≥ 500 kVA → 630 kVA |
| Supply voltage | 10 kV (MV feed) — recommended for this size |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| DC fast charger (120 kW) | 120 kW · CCS/GB-T | 4 | POA |
| Distribution transformer | 630 kVA · 10 kV / 0.4 kV · S13 | 1 | POA |
| Total equipment (reference) | POA |
Nasıl hesaplandı
- · Bağlı yük: Σ (şarj cihazı sayısı × anma gücü).
- · Talep yükü: Pdemand = Pconnected × çeşitlilik faktörü.
- · Talep kVA: S = Pdemand ÷ güç faktörü.
- · Trafo: bir sonraki standart kVA ≥ S × 1,1 (tasarım marjı).
- · Hat akımı: I = S ÷ (√3 · U).
Referans alınan standartlar
| Standard | Scope |
|---|---|
| IEC 61851 | Elektrikli araç iletken şarj sistemi |
| GB/T 51313 | EV dağıtılmış şarj tesisleri için teknik standart |
| GB/T 18487 | Elektrikli araç iletken şarj sistemi (Çin) |
Sıkça sorulan sorular
How do I size the transformer for an EV charging station?
Sum the charger ratings with a coincidence factor: AC Level 2 chargers are 7-22 kW each, DC fast chargers 60-360 kW. A 10-charger DC station can peak near 500-1200 kVA. Size the Transformer to the coincident peak plus margin, per IEC 61851 and GB/T 51313. The calculator computes demand and transformer kVA.
What is the difference between AC and DC EV charging?
AC charging (Level 2, 7-22 kW) uses the vehicle's onboard charger and takes hours; DC fast charging (60-360 kW) bypasses it and charges to 80% in 20-40 minutes. DC stations need much larger electrical supply and cooling. The calculator models both and sizes supply accordingly.
What is the typical demand factor for an EV charging station?
EV charging is time-correlated, so the demand factor is higher than other loads — 0.7-1.0 for a busy DC fast-charging hub. A fleet depot charging overnight runs 0.8-1.0 simultaneously. The calculator applies a coincidence factor to avoid undersizing the supply.
What supply voltage does a DC fast charging station need?
A small station (a few 60-120 kW chargers) runs on 0.4 kV; a larger hub (500 kW-1.5 MW) needs a 10 kV feed and a dedicated transformer, per GB/T 51313. The calculator selects the supply voltage and transformer from the aggregated charger load.
What charging standard should the station support?
Global standards: CCS (Combined Charging System) and CHAdeMO for DC, GB/T 20234 for China, and Type 2 for AC. A station serving mixed fleets usually offers CCS2 DC plus Type 2 AC. The calculator's design basis assumes IEC 61851-compliant chargers.
Bu hesaplayıcıyı yerleştirin
Bu hesaplayıcıyı kendi web sitenize ücretsiz ekleyin. iframe her genişliğe uyum sağlar ve tamamen ziyaretçinizin tarayıcısında çalışır.
İlgili araçlar
Yalnızca ön tasarım için referans tahminler (FOB Qingdao, EXW) — nihai teklif değildir. Boyutlandırmayı projenize ve yerel standartlarınıza göre doğrulayın.
Send my complete design report
Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.
Your data stays private. No spam — only a reply to your enquiry.