SBH15-M-160/10/0.48
SBH15-M Serie • 160kVA • 10/0.48 kV
SBH15-M-160/10/0.48 is a 160 kVA, 10/0.48 kV transformadore de aleación amorfa manufactured by Shandong Yaqing Electric Power Technology Co., Ltd. (QDTB) in Qingdao, China, designed and tested in accordance with IEEE C57 / ANSI C84.1, vector group Delta-Wye (IEEE Std), short-circuit impedance 4.5%, approximate weight 800 kg. Available on FOB Qingdao terms; datasheet, routine test report and GA drawing issued with each unit.
Technical Specifications
| Model | SBH15-M-160/10/0.48 |
|---|---|
| Rated Capacity | 160kVA |
| HV Voltage | 10 kV |
| LV Voltage | 0.48 kV |
| Frequency | 60 Hz |
| Vector Group | Delta-Wye (IEEE Std) |
| Short-circuit Impedance | 4.5% |
| Cooling | ONAN |
| Insulation | A (105°C) |
| Temperature Rise | 65 K |
| No-load Loss | 60 W |
| Load Loss | 2310 W |
| Efficiency | 1Class 5 |
| Weight | 800 kg |
| Dimensions | 1110×970×1290 mm |
| Applied Standard | IEEE C57 / ANSI C84.1 |
Puntos de operación típicos
Calculado a partir de las pérdidas de placa de este modelo (P₀ 60 W, P_k 2310 W), u_k 4.5%, con factor de potencia 0.9.
| Carga | Salida (kW) | Pérdida en vacío (kW) | Pérdida de carga (kW) | Pérdida total (kW) | Rendimiento (%) | Regulación de tensión (%) |
|---|---|---|---|---|---|---|
| 50% | 72.0 | 0.060 | 0.578 | 0.637 | 99.12 | 1.59 |
| 75% | 108.0 | 0.060 | 1.299 | 1.359 | 98.76 | 2.40 |
| 100% | 144.0 | 0.060 | 2.310 | 2.370 | 98.38 | 3.21 |
| 125% | 180.0 | 0.060 | 3.609 | 3.669 | 98.00 | 4.03 |
Rendimiento máximo en torno a 26 kVA (16.1% de la potencia nominal) — β* = √(P₀ / P_k).
Imagen y parámetros del producto

Las imágenes son sólo para fines ilustrativos.
SBH15-M-160/10/0.48
SBH15-M Serie
TECHNICAL DRAWING
Modelo: SBH15-M-160/10/0.48 | Tipo: Transformador de aleación amorfa | Capacidad: 160 kVA
FRONT ELEVATION
ELECTRICAL SCHEMATIC
EFFICIENCY vs LOAD
SIDE VIEW
TOP VIEW
TERMINAL BLOCK
CORE & WINDING
Especificaciones técnicas
LEGEND:
Descripción del Producto
Transformador trifásico sumergido en aceite de 160 kVA, 60 Hz, primario 10 kV (HV 10 kV), secundario 480 V (LV 480 V), S15, aislamiento A, impedancia 4,5 %
Palabras clave relacionadas
Calculadora de cotización y selección instantánea
Seleccione sus especificaciones para obtener un precio estimado al instante.
Más opciones(2)
Certificación
Los valores a continuación se calculan a partir de lo que seleccionó arriba. Todo lo que aún no se puede calcular se muestra como un guion largo — nunca como cero.
Iₙ = S / (√3·U) · I_sc = 100·Iₙ / uₖ · S_sc = √3·U·I_sc · I_p = k·Iₖ
Aún se requiere para completar el cálculo: capacidad nominal S,tensión de impedancia uₖ,corriente admisible de corta duración o de cresta.
Los valores por modelo (P0 / Pk / uₖ declarados por fábrica, pérdidas, ruido, elevación de temperatura, dimensiones, peso) no están en la biblioteca de productos: esas filas permanecen con un guion largo hasta que se suministre la hoja de parámetros de fábrica. Un guion largo significa que el valor no está disponible — nunca se representa como cero.
Read-only: no price factor, not part of the sum — the loss-grade cost is already carried by the efficiency (subtype) base price, so charging here would double-bill. Values come from the product library type-test data, interpolated between published capacities; grades the library does not cover show an em dash, never zero.
油浸非晶(SBH15-M / SH16)
Los precios de referencia son sólo para estimación y no constituyen una oferta formal.
3 · Solicita esta cotización
Le responderemos con la última cotización al instante.
SBH15-M-160/10/0.48 - Preguntas frecuentes
Q¿Cuáles son las principales aplicaciones de SBH15-M-160/10/0.48?
SBH15-M-160/10/0.48 (serie SBH15-M, Transformadores de aleación amorfa) se usa ampliamente en Distribución de energía industrial, edificios comerciales y sistemas de energía de servicios públicos.. Se puede configurar de forma flexible según los requisitos reales del proyecto.
Q¿Cuáles son las principales especificaciones técnicas de SBH15-M-160/10/0.48?
Especificaciones clave: Capacidad: 160kVA, HV 10 kV, LV 0.48 kV, Frecuencia 60 Hz, Impedancia 4.5%, Conexión Delta-Wye (IEEE Std), Enfriamiento ONAN, Estándar IEEE C57 / ANSI C84.1.
Q¿Se puede pedir SBH15-M-160/10/0.48 a medida?
Sí. QDTB® proporciona servicios integrales de personalización OEM/ODM. Se pueden ajustar parámetros como capacidad, relación de voltaje, método de enfriamiento, grupo de conexión y clase de protección. Más de 25 años de experiencia en fabricación garantizan una calidad constante.
Q¿Cómo conseguir presupuesto y documentación técnica?
Póngase en contacto a través del botón "Enviar consulta" a continuación, o comuníquese con ventas en Alice@qdtb-transformer.com / +86 13698683193. Le proporcionamos cotizaciones detalladas y documentación técnica al instante.
Productos relacionados en la Serie SBH15-M
¿Interesado en SBH15-M-160/10/0.48?
Contáctenos para conocer precios, soporte técnico o requisitos personalizados.