结果
输入您的负载 → 数秒内获得完整设计及 BOM
示例输出Calculated demand load
83.2 kW
97.9 kVA at PF 0.85 · connected 145.0 kW · Ks 0.8
Overall demand factor
72%
Demand current
141 A
Transformer
160 kVA
Load factor
61%
Load schedule
| Load group | Connected kW | Demand factor | Demand kW |
|---|---|---|---|
| Lighting | 20.0 | 90% | 18.0 |
| HVAC / air conditioning | 40.0 | 80% | 32.0 |
| Motors & pumps | 60.0 | 70% | 42.0 |
| Sockets / general purpose | 15.0 | 40% | 6.0 |
| Other / special loads | 10.0 | 60% | 6.0 |
| Subtotal (diversified) | 145.0 | 104.0 | |
| Demand load (× Ks 0.8) | 83.2 kW |
Result
| Demand kVA | 83.2 kW ÷ 0.85 = 97.9 kVA |
| Demand current | 97.9 kVA ÷ (√3 × 0.4 kV) = 141 A |
| Recommended transformer | 97.9 kVA ÷ 0.8 = 122 kVA → 160 kVA (load factor 61%) |
Bill of materials
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Distribution transformer (S13 oil-immersed) | 160 kVA · 10/0.4 kV · Dyn11 | 1 | POA |
| Low-voltage switchgear (GCK/GCS) | 98 kVA demand · 141 A | 1 | POA |
| Total equipment (transformer) | POA |
面向电气设计师和顾问,用于任何配电设计的第一步——根据负载表进行馈线、开关柜和变压器选型。
使用计算器
计算示例
预先计算的参考示例(可抓取——无需 JavaScript)。在上方输入您自己的参数以获取实时结果。
示例 1 — 办公与轻工业负荷表
Calculated demand load
83.2 kW
97.9 kVA at PF 0.85 · connected 145.0 kW · Ks 0.8
Overall demand factor
72%
Demand current
141 A
Transformer
160 kVA
Load factor
61%
Load schedule
| Load group | Connected kW | Demand factor | Demand kW |
|---|---|---|---|
| Lighting | 20.0 | 90% | 18.0 |
| HVAC / air conditioning | 40.0 | 80% | 32.0 |
| Motors & pumps | 60.0 | 70% | 42.0 |
| Sockets / general purpose | 15.0 | 40% | 6.0 |
| Other / special loads | 10.0 | 60% | 6.0 |
| Subtotal (diversified) | 145.0 | 104.0 | |
| Demand load (× Ks 0.8) | 83.2 kW |
Result
| Demand kVA | 83.2 kW ÷ 0.85 = 97.9 kVA |
| Demand current | 97.9 kVA ÷ (√3 × 0.4 kV) = 141 A |
| Recommended transformer | 97.9 kVA ÷ 0.8 = 122 kVA → 160 kVA (load factor 61%) |
Bill of materials
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Distribution transformer (S13 oil-immersed) | 160 kVA · 10/0.4 kV · Dyn11 | 1 | POA |
| Low-voltage switchgear (GCK/GCS) | 98 kVA demand · 141 A | 1 | POA |
| Total equipment (transformer) | POA |
示例 2 — 高 HVAC 占比的商业建筑
Calculated demand load
134.6 kW
149.6 kVA at PF 0.9 · connected 235.0 kW · Ks 0.75
Overall demand factor
76%
Demand current
216 A
Transformer
200 kVA
Load factor
75%
Load schedule
| Load group | Connected kW | Demand factor | Demand kW |
|---|---|---|---|
| Lighting | 30.0 | 90% | 27.0 |
| HVAC / air conditioning | 120.0 | 85% | 102.0 |
| Motors & pumps | 40.0 | 60% | 24.0 |
| Sockets / general purpose | 25.0 | 50% | 12.5 |
| Other / special loads | 20.0 | 70% | 14.0 |
| Subtotal (diversified) | 235.0 | 179.5 | |
| Demand load (× Ks 0.75) | 134.6 kW |
Result
| Demand kVA | 134.6 kW ÷ 0.9 = 149.6 kVA |
| Demand current | 149.6 kVA ÷ (√3 × 0.4 kV) = 216 A |
| Recommended transformer | 149.6 kVA ÷ 0.8 = 187 kVA → 200 kVA (load factor 75%) |
Bill of materials
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Distribution transformer (S13 oil-immersed) | 200 kVA · 10/0.4 kV · Dyn11 | 1 | POA |
| Low-voltage switchgear (GCK/GCS) | 150 kVA demand · 216 A | 1 | POA |
| Total equipment (transformer) | POA |
计算过程
- · 接入负荷:P_conn = Σ P_i。
- · 多样化需量:P_d = Σ (P_i × Kd_i)。
- · 计算需量:P = P_d × Ks(同时系数)。
- · 需量视在功率:S = P ÷ PF;需量电流:I = P ÷ (√3 · U)。
- · 推荐变压器:S_tr = S ÷ 目标负载率(0.8),向上取整至标准容量。
引用标准
| Standard | Scope |
|---|---|
| IEC 60364 | 低压电气装置 |
| IEEE 241 | 商业建筑电力系统推荐规程(灰皮书) |
| GB 50054 | 低压配电设计规范 |
常见问题
装机容量和需用负荷有什么区别?
装机容量是所有设备铭牌功率之和;需用负荷是实际同时取用的最大功率,等于装机 × 需用系数。500 kW 装机、0.7 需用系数得 350 kW 需用。变压器按需用而非装机选型。计算器由装机算需用。
不同建筑类型该用多大需用系数?
典型需用系数:住宅 0.3-0.5、商业办公 0.4-0.6、工业 0.6-0.8、连续流程 0.8-0.9,医院 0.7-0.8。取对系数可避免变压器超配 30-50%。计算器提供参考并算出推荐 kVA。
如何把需用 kW 换成变压器 kVA?
kVA = 需用 kW ÷ 功率因数。350 kW 需用、0.9 pf 需 389 kVA,取 400 kVA。若功率因数未校正为 0.75,同样负荷需 467 kVA——功率因数校正可减小变压器。计算器套用 pf 并选标准容量。
NEC 和 IEC 的需用系数有什么不同?
NEC 第 220 条按设备/负荷类型给查表需用系数;IEC/GB 做法按建筑类型用工程经验系数。两者都旨在避免超配。计算器采用与 GB 50052 和 IEC 实践一致的工程需用系数。
如何为负荷增长留裕量?
在现需用上加 15-25% 增长裕量,再取下一标准变压器容量。现需用 350 kVA 则按约 440 kVA 规划、选 500 kVA(或 2×250 kVA)。计算器的裕量建议使增长后负载率仍保持 70-80%。
嵌入此计算器
将此计算器免费添加到您自己的网站。iframe 可自适应任何宽度,并完全在访问者的浏览器中运行。
发送我的完整设计报告
免费获取完整设备清单(BOM)、单线图、计算步骤与 FOB 报价的 PDF 报告,无需注册。