电机启动与电压暂降计算器

检查电机启动时的母线电压暂降 — 启动电流、暂降 %、启动方式对比及保持在限值内所需的最小电源或变压器容量。

开始计算

结果

输入您的负载 → 数秒内获得完整设计与 BOM

示例输出
Bus voltage dip at start
6.8 %
90 kW motor · 380 V · Direct-on-line (DOL) · limit 15% · Within limit ✓
Rated current
178.7 A
Starting current
1162 A
Starting kVA
765 kVA
Bus short-circuit
10.5 MVA
Starting calculation
QuantityValue
Motor rated current InP ÷ (√3·U·cosφ·η) = 90 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 178.7 A
Starting current multiple6.5× (Direct-on-line (DOL))
Starting current Ist178.7 × 6.5 = 1162 A
Starting apparent power90 ÷ (0.9 × 0.85) × 6.5 = 765 kVA
Bus short-circuit capacity630 kVA ÷ 6% = 10.5 MVA
Voltage dipSstart ÷ (Sstart + Ssc) = 6.8% vs limit 15%
Starting-method comparison
MethodkstVoltage dipVerdict
Direct-on-line (DOL)6.5×6.8%OK
Star-delta (Y-Δ)2.2×2.4%OK
Soft starter3.0×3.3%OK
VFD (variable speed)1.3×1.4%OK
Recommendation
Direct-on-line (DOL)
Current method keeps the bus voltage dip within the limit.
Bill of materials
EquipmentSpecQtySubtotal
DOL starter cabinet90 kW · 380 V · Direct-on-line (DOL) (6.5× In)1POA
Total equipmentPOA

适用于在 LV/MV 系统上选型电机启动器并检查电机启动期间电压暂降的电气工程师和承包商。

使用计算器

计算示例

预先计算的参考示例(可抓取——无需 JavaScript)。在上方输入您自己的参数即可获得实时结果。

计算示例 — 90 kW 电机、DOL 启动、630 kVA 变压器

Bus voltage dip at start
6.8 %
90 kW motor · 380 V · Direct-on-line (DOL) · limit 15% · Within limit ✓
Rated current
178.7 A
Starting current
1162 A
Starting kVA
765 kVA
Bus short-circuit
10.5 MVA
Starting calculation
QuantityValue
Motor rated current InP ÷ (√3·U·cosφ·η) = 90 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 178.7 A
Starting current multiple6.5× (Direct-on-line (DOL))
Starting current Ist178.7 × 6.5 = 1162 A
Starting apparent power90 ÷ (0.9 × 0.85) × 6.5 = 765 kVA
Bus short-circuit capacity630 kVA ÷ 6% = 10.5 MVA
Voltage dipSstart ÷ (Sstart + Ssc) = 6.8% vs limit 15%
Starting-method comparison
MethodkstVoltage dipVerdict
Direct-on-line (DOL)6.5×6.8%OK
Star-delta (Y-Δ)2.2×2.4%OK
Soft starter3.0×3.3%OK
VFD (variable speed)1.3×1.4%OK
Recommendation
Direct-on-line (DOL)
Current method keeps the bus voltage dip within the limit.
Bill of materials
EquipmentSpecQtySubtotal
DOL starter cabinet90 kW · 380 V · Direct-on-line (DOL) (6.5× In)1POA
Total equipmentPOA

计算示例 — 250 kW 电机、软启动器、20 MVA 电网

Bus voltage dip at start
4.7 %
250 kW motor · 380 V · Soft starter · limit 15% · Within limit ✓
Rated current
496.5 A
Starting current
1490 A
Starting kVA
980 kVA
Bus short-circuit
20.0 MVA
Starting calculation
QuantityValue
Motor rated current InP ÷ (√3·U·cosφ·η) = 250 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 496.5 A
Starting current multiple3.0× (Soft starter)
Starting current Ist496.5 × 3.0 = 1490 A
Starting apparent power250 ÷ (0.9 × 0.85) × 3.0 = 980 kVA
Bus short-circuit capacity20 MVA (grid) = 20.0 MVA
Voltage dipSstart ÷ (Sstart + Ssc) = 4.7% vs limit 15%
Starting-method comparison
MethodkstVoltage dipVerdict
Direct-on-line (DOL)6.5×9.6%OK
Star-delta (Y-Δ)2.2×3.5%OK
Soft starter3.0×4.7%OK
VFD (variable speed)1.3×2.1%OK
Recommendation
Soft starter
Current method keeps the bus voltage dip within the limit.
Bill of materials
EquipmentSpecQtySubtotal
Soft starter cabinet250 kW · 380 V · Soft starter (3.0× In)1POA
Total equipmentPOA

计算过程

  • · 额定电流:In = P ÷ (√3 · U · cosφ · η)。
  • · 启动电流:Ist = In × kst,其中 kst 为启动电流倍数(≈6.5× DOL,≈2.2× 星-三角,≈3× 软启动,≈1.3× VFD)。
  • · 启动视在功率:Sstart = P ÷ (cosφ · η) × kst。
  • · 母线电压暂降:ΔU% = Sstart ÷ (Sstart + Ssc) × 100,其中 Ssc 为母线处的短路容量。
  • · 满足限值 L 所需的最小电源/变压器容量:S ≥ Sstart × (1 − L) ÷ L × uk。

引用标准

StandardScope
IEC 60034旋转电机 — 额定值与性能
GB/T 755旋转电机的额定值与性能
IEEE 3002.7-2018电力系统电动机启动分析

常见问题

电机启动时可接受的电压跌落是多少?

多数标准(IEC 60034、GB/T 755)允许电机启动时电压跌 15-20%,即母线电压保持在 80-85% 以上。低于 80% 可能使电机失速或接触器跳闸。计算器计算启动压降并在超限时提示。

电机直接启动会拉多大电流?

直接启动(DOL)在数秒内拉额定电流 5-7 倍。100 kW、0.4 kV 电机(约 180 A 额定)启动时拉 900-1260 A。该涌流造成压降;计算器计算压降并对比直接、星三角、软启动和变频。

软启动器能把启动电流降到多少?

软启动器斜坡升压,通常把启动电流限制在额定 2.5-3.5 倍(对比 DOL 5-7 倍),按比例减小压降。启动转矩也随电流平方下降,故软启动适合离心类负载。计算器对比各启动方式。

带大电机需要多大供电变压器?

变压器须在不造成过大压降的前提下供出电机启动 kVA。160 kW 电机软启动 3 倍时启动需量约 480 kVA,630 kVA 变压器可把压降控制在约 10-12%。计算器按启动需量和压降限值选供电。

什么是星三角启动?何时使用?

星三角启动先以星形连接启动(电压降到 58%、电流和转矩降到 1/3),再切到角形运行。启动电流降到约 2-2.5 倍,但转矩下降使其仅适合风机、泵等轻启动负载。计算器把它与直接启动、软启动对比。

嵌入此计算器

将此计算器免费添加到您自己的网站。iframe 可自适应任何宽度,并完全在访问者的浏览器中运行。

相关工具

参考估算值(FOB 青岛,EXW)仅供初步设计使用——并非最终报价。请根据您的项目和当地标准确认选型。

发送我的完整设计报告

免费获取完整设备清单(BOM)、单线图、计算步骤与 FOB 报价的 PDF 报告,无需注册。

💬 WhatsApp 咨询

您的信息仅用于回复询盘,不用于任何其他用途。