结果
输入您的负载 → 数秒内获得完整设计与 BOM
示例输出Bus voltage dip at start
6.8 %
90 kW motor · 380 V · Direct-on-line (DOL) · limit 15% · Within limit ✓
Rated current
178.7 A
Starting current
1162 A
Starting kVA
765 kVA
Bus short-circuit
10.5 MVA
Starting calculation
| Quantity | Value |
|---|---|
| Motor rated current In | P ÷ (√3·U·cosφ·η) = 90 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 178.7 A |
| Starting current multiple | 6.5× (Direct-on-line (DOL)) |
| Starting current Ist | 178.7 × 6.5 = 1162 A |
| Starting apparent power | 90 ÷ (0.9 × 0.85) × 6.5 = 765 kVA |
| Bus short-circuit capacity | 630 kVA ÷ 6% = 10.5 MVA |
| Voltage dip | Sstart ÷ (Sstart + Ssc) = 6.8% vs limit 15% |
Starting-method comparison
| Method | kst | Voltage dip | Verdict |
|---|---|---|---|
| Direct-on-line (DOL) | 6.5× | 6.8% | OK |
| Star-delta (Y-Δ) | 2.2× | 2.4% | OK |
| Soft starter | 3.0× | 3.3% | OK |
| VFD (variable speed) | 1.3× | 1.4% | OK |
Recommendation
Direct-on-line (DOL)
Current method keeps the bus voltage dip within the limit.
Bill of materials
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| DOL starter cabinet | 90 kW · 380 V · Direct-on-line (DOL) (6.5× In) | 1 | POA |
| Total equipment | POA |
适用于在 LV/MV 系统上选型电机启动器并检查电机启动期间电压暂降的电气工程师和承包商。
使用计算器
计算示例
预先计算的参考示例(可抓取——无需 JavaScript)。在上方输入您自己的参数即可获得实时结果。
计算示例 — 90 kW 电机、DOL 启动、630 kVA 变压器
Bus voltage dip at start
6.8 %
90 kW motor · 380 V · Direct-on-line (DOL) · limit 15% · Within limit ✓
Rated current
178.7 A
Starting current
1162 A
Starting kVA
765 kVA
Bus short-circuit
10.5 MVA
Starting calculation
| Quantity | Value |
|---|---|
| Motor rated current In | P ÷ (√3·U·cosφ·η) = 90 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 178.7 A |
| Starting current multiple | 6.5× (Direct-on-line (DOL)) |
| Starting current Ist | 178.7 × 6.5 = 1162 A |
| Starting apparent power | 90 ÷ (0.9 × 0.85) × 6.5 = 765 kVA |
| Bus short-circuit capacity | 630 kVA ÷ 6% = 10.5 MVA |
| Voltage dip | Sstart ÷ (Sstart + Ssc) = 6.8% vs limit 15% |
Starting-method comparison
| Method | kst | Voltage dip | Verdict |
|---|---|---|---|
| Direct-on-line (DOL) | 6.5× | 6.8% | OK |
| Star-delta (Y-Δ) | 2.2× | 2.4% | OK |
| Soft starter | 3.0× | 3.3% | OK |
| VFD (variable speed) | 1.3× | 1.4% | OK |
Recommendation
Direct-on-line (DOL)
Current method keeps the bus voltage dip within the limit.
Bill of materials
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| DOL starter cabinet | 90 kW · 380 V · Direct-on-line (DOL) (6.5× In) | 1 | POA |
| Total equipment | POA |
计算示例 — 250 kW 电机、软启动器、20 MVA 电网
Bus voltage dip at start
4.7 %
250 kW motor · 380 V · Soft starter · limit 15% · Within limit ✓
Rated current
496.5 A
Starting current
1490 A
Starting kVA
980 kVA
Bus short-circuit
20.0 MVA
Starting calculation
| Quantity | Value |
|---|---|
| Motor rated current In | P ÷ (√3·U·cosφ·η) = 250 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 496.5 A |
| Starting current multiple | 3.0× (Soft starter) |
| Starting current Ist | 496.5 × 3.0 = 1490 A |
| Starting apparent power | 250 ÷ (0.9 × 0.85) × 3.0 = 980 kVA |
| Bus short-circuit capacity | 20 MVA (grid) = 20.0 MVA |
| Voltage dip | Sstart ÷ (Sstart + Ssc) = 4.7% vs limit 15% |
Starting-method comparison
| Method | kst | Voltage dip | Verdict |
|---|---|---|---|
| Direct-on-line (DOL) | 6.5× | 9.6% | OK |
| Star-delta (Y-Δ) | 2.2× | 3.5% | OK |
| Soft starter | 3.0× | 4.7% | OK |
| VFD (variable speed) | 1.3× | 2.1% | OK |
Recommendation
Soft starter
Current method keeps the bus voltage dip within the limit.
Bill of materials
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Soft starter cabinet | 250 kW · 380 V · Soft starter (3.0× In) | 1 | POA |
| Total equipment | POA |
计算过程
- · 额定电流:In = P ÷ (√3 · U · cosφ · η)。
- · 启动电流:Ist = In × kst,其中 kst 为启动电流倍数(≈6.5× DOL,≈2.2× 星-三角,≈3× 软启动,≈1.3× VFD)。
- · 启动视在功率:Sstart = P ÷ (cosφ · η) × kst。
- · 母线电压暂降:ΔU% = Sstart ÷ (Sstart + Ssc) × 100,其中 Ssc 为母线处的短路容量。
- · 满足限值 L 所需的最小电源/变压器容量:S ≥ Sstart × (1 − L) ÷ L × uk。
引用标准
| Standard | Scope |
|---|---|
| IEC 60034 | 旋转电机 — 额定值与性能 |
| GB/T 755 | 旋转电机的额定值与性能 |
| IEEE 3002.7-2018 | 电力系统电动机启动分析 |
常见问题
电机启动时可接受的电压跌落是多少?
多数标准(IEC 60034、GB/T 755)允许电机启动时电压跌 15-20%,即母线电压保持在 80-85% 以上。低于 80% 可能使电机失速或接触器跳闸。计算器计算启动压降并在超限时提示。
电机直接启动会拉多大电流?
直接启动(DOL)在数秒内拉额定电流 5-7 倍。100 kW、0.4 kV 电机(约 180 A 额定)启动时拉 900-1260 A。该涌流造成压降;计算器计算压降并对比直接、星三角、软启动和变频。
软启动器能把启动电流降到多少?
软启动器斜坡升压,通常把启动电流限制在额定 2.5-3.5 倍(对比 DOL 5-7 倍),按比例减小压降。启动转矩也随电流平方下降,故软启动适合离心类负载。计算器对比各启动方式。
带大电机需要多大供电变压器?
变压器须在不造成过大压降的前提下供出电机启动 kVA。160 kW 电机软启动 3 倍时启动需量约 480 kVA,630 kVA 变压器可把压降控制在约 10-12%。计算器按启动需量和压降限值选供电。
什么是星三角启动?何时使用?
星三角启动先以星形连接启动(电压降到 58%、电流和转矩降到 1/3),再切到角形运行。启动电流降到约 2-2.5 倍,但转矩下降使其仅适合风机、泵等轻启动负载。计算器把它与直接启动、软启动对比。