矿山电力系统计算器
设计矿山供电系统——破碎机、提升机、通风机和输送机负载,变压器与开关柜选型,大电机启动校验,VFD 谐波治理及高海拔/粉尘降容,附 BOM 和单线图。
为什么使用此计算器
矿山兼具最严苛的运行环境和极大且间歇性的电机负载。此计算器汇总破碎机、提升机、风机和输送机负载,应用需用系数和高海拔降容,校验最大电机启动电压跌落,并按 GB 50070 和 IEC 60034 选型变压器、无功补偿和谐波滤波。
Worked Examples
Example 1 — Surface Mine (Crusher + Hoist + Fans + Conveyors) · FOB $313,963
| Equipment | Model | Spec | Qty |
|---|---|---|---|
| HV incoming panel | KYN28A-12-630-315 | 630 A / 31.5 kA · vacuum | 1 |
| Main transformer | S13-M-1600/10 | 1600 kVA · Oil-Immersed · Copper · S13 | 1 |
| LV incoming panel | GGD-2500 | 2500 A busbar · In 2309 A | 1 |
| LV feeder panel (×2) | GGD-2500 | distributes 10 circuits | 2 |
| Cable branch box (LV) | DFW-0.4 | 1-in / 4-out · 0.4 kV · 630 A | 2 |
| Main feeder cable (TX→LV) | YJV 0.6/1kV 300 mm² ×5 | 5× 300 mm² Cu · ΔU 1.80% @ 120 m · $154.0/m | 5 |
| Feeder cable — Crusher 1 (×10) | YJV 120 mm² | 120 mm² Cu · 238 A · ΔU 2.3% · $68.8/m | 10 |
| Branch trunk cable (LV → branch box 1) | YJV 300 mm² ×2 | 2× 300 mm² Cu · 953 A · ΔU 1.9% · $154.0/m | 2 |
| Branch trunk cable (LV → branch box 2) | YJV 300 mm² | 300 mm² Cu · 477 A · ΔU 1.9% · $154.0/m | 1 |
| Main busbar (Cu) | Cu 125×10 | 125×10 · 2500 A rating · ref $147.8/m | included |
| Grounding electrode | Φ20mm × 2.5m rod | R₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω | 13 |
| Soft starter cabinet (largest motor) | 500 kW | Soft starter (3.0× In) · start dip 5.0% | 1 |
| Detuned PFC capacitor bank | 626 kvar | automatic · 7% detuned · 0.4 kV | 1 |
| Series detuning reactor (7%) | 43.8 kvar | 189 Hz tuning · below 5th harmonic | 1 |
| Active harmonic filter (APF) | 300 A | VFD harmonic mitigation (40% VFD load) · GB/T 14549 | 1 |
| Circuit | Protection | Setting | Time | Standard |
|---|---|---|---|---|
| HV incoming 10 kV | 50 instantaneous | 739 A | inst | IEC 60255-151 / IEEE 242 |
| HV incoming 10 kV | 51 overcurrent | 111 A | 0.5 s | IEC 60255-151 / IEEE 242 |
| HV incoming 10 kV | 51N earth-fault | 18 A | 0.5 s | IEC 60364-4-41 |
| Transformer 1600 kVA | 49 thermal overload | 87% of rated | alarm 90% | IEC 60076-7 / IEEE C57.91 |
| LV incoming 0.4 kV | 50 instantaneous | 18475 A | inst | IEC 60947-2 |
| LV incoming 0.4 kV | 51 overcurrent | 2771 A | 0.3 s | IEC 60947-2 / IEC 60255 |
| LV incoming 0.4 kV | 51N earth-fault | 462 A | 0.3 s | IEC 60364-4-41 |
| Crusher 1 | 50/51/51N (MCCB) | Ir 262 A - Im 1907 A - Ig 48 A | 0.1 s (grading) | IEC 60947-2 / IEC 60255 |
| Crusher 2 | 50/51/51N (MCCB) | Ir 262 A - Im 1907 A - Ig 48 A | 0.1 s (grading) | IEC 60947-2 / IEC 60255 |
| Hoist 1 | 50/51/51N (MCCB) | Ir 262 A - Im 1907 A - Ig 48 A | 0.1 s (grading) | IEC 60947-2 / IEC 60255 |
| Vent fan 1 | 50/51/51N (MCCB) | Ir 262 A - Im 1907 A - Ig 48 A | 0.1 s (grading) | IEC 60947-2 / IEC 60255 |
| Vent fan 2 | 50/51/51N (MCCB) | Ir 262 A - Im 1907 A - Ig 48 A | 0.1 s (grading) | IEC 60947-2 / IEC 60255 |
| Vent fan 3 | 50/51/51N (MCCB) | Ir 262 A - Im 1907 A - Ig 48 A | 0.1 s (grading) | IEC 60947-2 / IEC 60255 |
| +4 more feeders | 50/51/51N (MCCB) | per feeder load | 0.1 s (grading) | IEC 60947-2 |
| Parameter | Formula | Value |
|---|---|---|
| Connected load | P = sum(kW) | 1,321 kW |
| Demand factor | Kd | 1 |
| Demand power | Pd = P x Kd | 1,321 kW |
| Power factor | cos(phi) before -> after | 0.80 -> 0.95 |
| Design apparent power | Sd = Pd / cos(phi) | 1,391 kVA |
| Transformer loading | Sd / Srated | 87% |
| Parameter | Formula | Value |
|---|---|---|
| System impedance (pu) | Zs = S / Ssc | 0.32% (on 1600 kVA base) |
| Transformer impedance | Zt = Z% | 4% |
| Total impedance | Z = Zt + Zs | 4.32% |
| LV prospective Isc | Isc = In / Z | 53.5 kA |
| HV prospective Isc | Isc = Ssc / (sqrt(3) x V) | 28.9 kA |
| Breaking check | Icu >= Isc | LV 65 kA (1.2x margin) PASS |
| Parameter | Formula | Value |
|---|---|---|
| Main feeder | dU = sqrt(3) x I x L x R / V | 300 mm2 - dU 1.80% @ 120 m |
| Limit | max 3% | within limit |
| Transformer volt. reg. | dU ~ loading x Z% x sin(phi) | 1.1% at full load |
| Parameter | Formula | Value |
|---|---|---|
| Required compensation | Qc = Pd x (tan1 - tan2) | 0 kvar |
| PFC bank | standard step | 0 kvar |
| Detuned reactor | p = 6% | n/a |
| Parameter | Formula | Value |
|---|---|---|
| Single rod resistance | R1 = rho/(2 x pi x L) x ln(4L/d) | 39.6 ohm |
| Rods required | n = R1 / (target x 0.8) | 13 rod(s) <= 4 ohm |
| Rod spec | dia x length | 20 mm x 2.5 m |
| Parameter | Value |
|---|---|
| Motor | 500 kW · started Soft starter (3.0× In) |
| Starting kVA | 1,961 kVA |
| Feeder short-circuit | 500 MVA |
| Voltage dip | 5.0% vs limit 15% — OK ✓ |
| Parameter | Value |
|---|---|
| Reactive compensation | 626 kvar detuned bank (7% reactor) |
| VFD load | 40% (528 kW) |
| Harmonic current | Ih 241 A @ 30% THDi |
| APF required | Yes — VFD load ≥ 30% |
| Parameter | Value |
|---|---|
| Altitude | 1500 m → derating factor 0.97 |
| Dust level | Heavy dust → IP54 enclosure |
| Transformer | S13-M-1600/10 (10/0.4 kV) |
| Topic | Standard |
|---|---|
| Standard basis | IEC · IEC 60364-5-52 |
| Conductor ampacity | IEC 60364-5-52 Table B.52.2–B.52.5 (copper, 3 loaded conductors, 30°C ambient, PVC) — typical/rounded values, conservative (±3%) |
| Voltage-drop limit | IEC 60364-5-52 Annex G · max drop 3% |
| Winding temp rise | IEC 60076-2 — winding temp rise 65 K (Class A insulation, ONAN) |
| kVA ratings | IEC 60076-1 R10 preferred numbers |
| Breaker frames | IEC 60947-2 frame sizes (In) |
| Grounding target | IEC 60364-5-54 earthing arrangements and protective conductors — LV earthing target ≤ 10 Ω (TN systems); 4 Ω used as a conservative design target · target 4 Ω |
| Mining power design | GB 50070 — code for design of electric power supply in mines |
| Rotating machines | IEC 60034 — rotating electrical machines (rating & starting) |
| Harmonics | GB/T 14549 — quality of electric energy supply: harmonics in public supply network |
| Power supply design | GB 50052 — code for design of electric power supply systems |
| Transformers | IEC 60076 — power transformers (altitude / temperature derating) |
| Summary | |||||
|---|---|---|---|---|---|
| Estimated total (FOB Qingdao, EXW) — priced equipment | $313,963 | ||||
计算过程说明
选型计算原理
设备总容量 = Σ(台数 × kW)。计算负荷 = 设备总容量 × Kd(矿山典型值 0.7)。海拔超过 1000 m 时变压器降容(按 IEC 60076 约 0.5%/100 m),因此有效负荷 = 计算负荷 ÷ 降容系数。最大电机启动容量 = P ÷ (η·cosφ) × kst,母线电压跌落 = Sstart ÷ (Sstart + Ssc)。无功补偿 Qc = P × (tanφ₁ − tanφ₂);VFD 谐波电流 Ih 采用调谐电抗器组滤波。
适用标准
选型依据 GB 50070(矿山供电设计)、IEC 60034(旋转电机)、GB/T 14549(谐波)、GB 50052(供电设计)和 IEC 60076(变压器降容)。
常见问题
海拔如何影响变压器和开关柜的额定值?
海拔 1000 m 以上空气稀薄,散热和绝缘强度下降。变压器约每升高 100 m 降容 0.5%,开关柜类似。1500 m 站场约降 2.5%,3000 m 约降 10%。计算器按 IEC 60076 与 IEC 62271 对所选变压器和开关柜施加海拔降容。
井下矿山供电的典型电压是多少?
井下矿山以 10 kV 或 6 kV 配电入井,再降压到 1.14 kV 或 0.66 kV 供破碎机、提升机和输送机,0.4 kV 供辅助。长电缆和电机启动宜用较高低压等级。计算器以 10/0.4 kV 地面厂区建模,并对提升机、破碎机做启动压降校核。
矿井提升机为什么需要特殊启动考虑?
矿井提升机(常 500 kW-3 MW)直接启动电流为额定 5-7 倍,可使井下母线跌到 85% 以下并跳掉其他传动。软启动或变频可限制冲击,变压器须按启动 kVA 选型。计算器校核最大电机的压降并据此选供电。
矿山变频器的谐波如何处理?
变频负载占 40% 时 THDi 可超 20%,需配 7% 去谐电容器组或 APF 以满足 IEEE 519(PCC 处 5% THD)。计算器按变频占比配置无功补偿与去谐;重粉尘工况还需 IP54 及以上外壳。
矿山厂区该取多大需用系数?
破碎机、提升机、风机和输送机不会同时达峰,需用系数典型 0.6-0.75。250 kW 破碎机 + 500 kW 提升机 + 160 kW 风机 + 90 kW 输送机的 1600+ kW 装机很少同时超过 60-70%。计算器在选变压器 kVA 前套用 kd。
矿山开关柜需要什么外壳与防护?
矿山开关柜须防尘防潮:地面厂区 IP54/IP55,井下含瓦斯矿井用隔爆 Ex d(IEC 60079)。重粉尘缩短爬电距离,故需加大电气间隙并采用耐漏电绝缘。计算器按粉尘等级在 BOM 中标注对应外壳等级。
嵌入此计算器
复制下方 iframe 代码,即可将此计算器嵌入任何网站。嵌入页面为 noindex,适配任意宽度。
相关计算器
结果为工程估算,仅供参考。最终设计须由当地持证工程师根据现场条件和适用规范确认。价格为青岛交货价 FOB(EXW),不含运费、关税及安装费。
发送我的完整设计报告
免费获取完整设备清单(BOM)、单线图、计算步骤与 FOB 报价的 PDF 报告,无需注册。
您的信息仅用于回复询盘,不用于任何其他用途。