🔌 Transformer Sizing & Selection Calculator
Enter your connected load and get the standard transformer kVA, recommended model and a copper-linked reference price. Covers oil-immersed, dry-type, amorphous-alloy and box-type substations.
⚙️ Your Load & Specs
📊 Result
For electrical engineers, contractors and buyers sizing a distribution transformer from a load.
How it is calculated
· Sizing — kW mode: kVA = Load (kW) ÷ Power factor; kVA mode: kVA = Load; Amps mode: kVA = √3·U·I (3-phase).
· Design capacity: kVA_design = kVA × (1 + design margin %).
· Selection: next standard kVA from the IEC R10 preferred series; price = base × winding × efficiency × voltage factor, with ±3% per $1,000/t copper for copper windings.
Referenced standards
| Standard | Scope |
|---|---|
| IEC 60076-1 | Preferred kVA ratings (R10 series) for power transformers |
| GB/T 1094 | Chinese equivalent of IEC 60076, power transformer ratings |
Worked example — 500 kW load → 800 kVA transformer
1. Load 500 kW, power factor 0.85 → kVA = 500 ÷ 0.85 = 588 kVA.
2. Design margin 20% → kVA_design = 588 × 1.20 = 706 kVA.
3. Next standard R10 size = 800 kVA (dry-type SCB13, 10/0.4 kV, copper).
4. Reference price from the live price table, copper-linked to the LME price.
FAQ
How do I calculate the transformer kVA I need?
Transformer kVA = total load kW x demand factor / Power Factor. For 300 kW of load at 0.85 pf with 0.8 demand factor: 300 x 0.8 / 0.85 = 282 kVA, so select 315 kVA. Leave 15-20% headroom for growth and select the next standard rating per IEC 60076. The calculator does this and returns the model and price.
What is the difference between oil-immersed and dry-type transformers?
Oil-immersed units are cheaper (10-30% less), quieter under load and better cooled, suited to outdoor and larger ratings; dry-type cast-resin units are fire-safe, suited to indoor, hospitals and high-rises, but cost more and run hotter. Dry-type is mandatory for many indoor installations per fire codes. The calculator prices both types.
What does S13, SCB13 and S20 mean in a transformer model?
S-series is oil-immersed (S11/S13/S20/S22), SCB is dry-type cast-resin. The number is the efficiency/loss grade — higher numbers mean lower No-Load Loss. S13 cuts no-load loss ~20-30% versus S11; S20/S22 are the current GB 20052 energy-efficiency grades. The calculator lets you pick the grade and shows the price delta.
What vector group do I need — Dyn11 or Yyn0?
Dyn11 (delta primary, wye secondary, 30 deg shift) is standard for distribution because it blocks third-harmonic circulation and supports unbalanced load better. Yyn0 is used for small single-phase-heavy loads but passes zero-sequence harmonics. For most modern LV networks choose Dyn11; the calculator defaults to it.
How much does a 500 kVA transformer cost?
A 500 kVA oil-immersed S13 transformer runs roughly $12,000-18,000 FOB, and a dry-type SCB13 roughly $16,000-24,000, varying with copper price (base ~14,200 USD/t), winding material and tap-changer. The calculator returns a live reference FOB price from the QDTB pricing matrix, updated with copper.
Embed this calculator
Add this calculator to your own website for free. The iframe adapts to any width and runs entirely in your visitor's browser.