QDTB® Transformer

🔗 Voltage Drop Calculator

Size a cable by ampacity and voltage drop in one pass. Pick current, length and conductor, and get the minimum cross-section that stays within your voltage-drop limit.

Start Calculating
⚠️ Based on IEC 60364-5-52 reference ampacities. Final cable selection must consider installation method, temperature and local code.

⚙️ Circuit

📊 Result

For electricians and engineers sizing LV feeders and final circuits.

How it is calculated

· Resistance: R = ρ ÷ A (ρ copper 0.0225, aluminum 0.036 Ω·mm²/m).

· Voltage drop: VD = √3·I·L·R (3-phase) or VD = 2·I·L·R (1-phase).

· Voltage drop %: VD% = VD ÷ U × 100 (U = 400 V or 230 V).

Referenced standards

StandardScope
IEC 60364-5-52Wiring systems — current-carrying capacities and voltage drop

Worked example — 100 A over 50 m → 25 mm² copper

1. 100 A, 50 m, 3-phase copper, 3% limit.

2. Ampacity first: 25 mm² copper carries 101 A ≥ 100 A.

3. R = 0.0225 ÷ 25 = 0.0009 Ω/m → VD = √3 × 100 × 50 × 0.0009 = 7.8 V = 1.95%.

4. 25 mm² satisfies both ampacity and the 3% drop limit.

FAQ

What is an acceptable voltage drop in a low-voltage circuit?

IEC 60364-5-52 recommends total voltage drop within 5% (distribution plus final circuit), and 3% for lighting. In practice feeders are sized for 2-3% steady-state drop, leaving margin for motor starting. The calculator computes drop for single and three-phase circuits and recommends a cross-section that meets the limit.

How do I calculate voltage drop for a 3-phase circuit?

Voltage drop = sqrt(3) x I x L x (R cos(phi) + X sin(phi)). For a 100 A, 50 m, 35 mm2 copper feeder (R ~0.524 ohm/km), drop is about 1.73 x 100 x 0.05 x 0.524 = 4.5 V, or 1.1% of 400 V. The calculator computes drop in volts and percent and flags the recommended section.

Copper or aluminum for a feeder cable?

Aluminium is lighter and cheaper (30-50% less) but needs a larger cross-section for the same drop because its resistivity is ~1.6x copper. For a 100 A feeder, 35 mm2 copper roughly equals 50-70 mm2 aluminium. Copper wins in ducts and short runs; aluminium wins in long, cost-driven feeders. The calculator compares both.

How does motor starting affect voltage drop?

Motor starting current is 5-7 times rated, so the starting voltage drop is 5-7 times the steady-state drop. A feeder sized for 2% running drop may dip 10-15% during start, which can stall the motor. Soft-starters or larger cables limit this. The calculator flags starting drop and recommends mitigation.

What cross-section do I need for a 100 A three-phase feeder?

For a 100 A, 0.4 kV three-phase feeder, a 35 mm2 copper cable is the standard choice, carrying ~110-125 A with a 50 m run dropping about 1%. For longer runs or tighter drop limits, use 50 mm2. The calculator picks the minimum section meeting both ampacity and drop per IEC 60364-5-52.

Embed this calculator

Add this calculator to your own website for free. The iframe adapts to any width and runs entirely in your visitor's browser.

Related tools

Reference estimates (FOB Qingdao, EXW) for preliminary design only — not a final quote. Confirm sizing against your project and local standards.

Send my complete design report

Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.

💬 Chat on WhatsApp

Your data stays private. No spam — only a reply to your enquiry.