QDTB®变压器官网

港口起重机与冶金电力系统计算器

为岸桥、港口设备及电弧炉设计供电方案 — 冲击负载无功补偿(SVC/SVG)、谐波滤波及电机启动电压跌落校验,附 BOM 与单线图。

开始计算 港口起重机与冶金解决方案
智能化与监控
在 BOM 与架构图中加入保护、计量与 SCADA(监控与二次)层。

为什么使用此计算器

起重机和电弧炉属于极端冲击负载:快速波动会引起电压闪变,且 VFD/ 整流器驱动会注入大量谐波。本计算器按平均需求为变压器选型,校验最大驱动启动时的电压跌落,并确定动态无功补偿及失谐谐波滤波的容量。

Worked Examples

Example 1 — 4 × 500 kW Quay Cranes (Impact Load, SVC + Harmonics) · FOB $438,818
Port crane / metallurgy power system · 35kV/0.4kV
1,600 kVA transformer
S13-M-1600/35 · impact 2,600 kW · THDi 30%
Connected load
2,000 kW
Impact peak
2,600 kW
Reactive comp.
1798 kvar
Start dip
2.2%
Est. total (FOB)
POA
📦 Bill of Materials
EquipmentModelSpecQty
HV incoming panelKYN61-40.5-1250-251250 A / 25 kA · vacuum1
Main transformerS13-M-1600/351600 kVA · Oil-Immersed · Copper · S131
LV incoming panelGGD-25002500 A busbar · In 2309 A1
LV feeder panelGGD-2500distributes 4 circuits1
Main feeder cable (TX→LV)YJV 0.6/1kV 300 mm² ×55× 300 mm² Cu · ΔU 1.50% @ 100 m · $154.0/m5
Feeder cable — Quay crane 1 (×4)YJV 185 mm² ×33× 185 mm² Cu · 1031 A · ΔU 1.8% · $103.0/m12
Main busbar (Cu)Cu 125×10125×10 · 2500 A rating · ref $147.8/mincluded
Grounding electrodeΦ20mm × 2.5m rodR₁ 39.6 Ω → 13 rod(s) ≤ 4 Ω13
Dynamic reactive compensation (SVC/SVG)±5 MvarStatic Var Generator · fast response for impact loads · FOB reference1
Detuned PFC capacitor bank1798 kvarautomatic · 7% detuned · 0.4 kV1
Series detuning reactor (7%)125.9 kvar189 Hz tuning · below 5th harmonic1
Quay crane regenerative drive500 kW four-quadrantregenerative VFD (energy feedback on lowering) · per crane4
Shore power supply (岸电)300 kVA50/60 Hz frequency converter + shore connection panel · IEC/ISO 80005-1 · quoted per project1
📐 Single-line diagram
CTCT 30/5APTPT 35kV/100V50/5151NHV incomingKYN61-40.5-1250-251250 A / 25 kA - vacuumS13-M-1600/351600 kVAZ = 4%Oil-Immersed - Copper - S13kWhmeteringLV incomingGGD-25000.4 kV LV busbar125x10 Cu - 2500 ASPDLV feeder panel x1 - 4 circuitsQuay crane 1 - 1031 AYJV 185 mm2Quay crane 2 - 1031 AYJV 185 mm2Quay crane 3 - 1031 AYJV 185 mm2Quay crane 4 - 1031 AYJV 185 mm2Grounding 13xdia20mmx2.5m rod
LEGENDBreaker (52)DisconnectorCTCT (current transformer)PTPT (voltage transformer)50/51Protection relay 50/51/51N/87kWhMeter (kWh)SPD (surge protection)Transformer
⚙️ Electrical schematic (protection & metering)
ELECTRICAL SCHEMATIC - PROTECTION & METERING35 kV / 0.4 kV - 1600 kVA - secondary circuits (schematic)INCOMING 35 kVCT30/5Aprotection CT5250/5151Novercurrent / earth-faultPT35kV/100Vbus PT (voltage)TRANSFORMER1600 kVAZ = 4%kWhrevenue meteringLV 520.4 kV LV BUSSPDCT.../5AQuay crane 1 - 1031 A50/51CT.../5AQuay crane 2 - 1031 A50/51CT.../5AQuay crane 3 - 1031 A50/51CT.../5AQuay crane 4 - 1031 A50/51
⛳ Grounding grid layout
SUBSTATION GROUNDING GRID LAYOUTsite 12 m x 8 m - ring earth electrode (schematic)TRANSFORMERR1R2R3R4R5R6R7R8R9R10R11R12R1312 mGround rods: 13 x dia 20 mm x 2.5 m copper-bonded steelRod spacing: 5 m (= 2 x rod length, ring electrode)Target resistance: <= 4 ohm (measure after installation)Standard: IEEE 80 / GB-T 50065 (earthing design) - indicative layout
🔌 Cable schedule & routing
CABLE SCHEDULEIDFromToCable (model / spec)LengthC0TransformerLV panelYJV 0.6/1kV 300 mm2 (2309 A)100 mC1LV panelQuay crane 1YJV 185 mm2 (1031 A)100 mC2LV panelQuay crane 2YJV 185 mm2 (1031 A)100 mC3LV panelQuay crane 3YJV 185 mm2 (1031 A)100 mC4LV panelQuay crane 4YJV 185 mm2 (1031 A)100 mROUTING (schematic)LV PANELL1L2L3L4L5Cable lengths are indicative (run-length based); confirm on site before installation.
🗄 Switchgear arrangement
SWITCHGEAR ARRANGEMENTpanel lineup (front view, schematic)HV INCOMINGKYN61-40.5-1250-25LV INCOMINGGGD-2500FEEDERGGD-25003 panel(s) - each 213 mm (typical)Clearance / aisle per IEC 61936-1 - layout indicative
🛡 Protection configuration
PROTECTION CONFIGURATION35 kV / 0.4 kV - 1600 kVA - protection zones (schematic)INCOMING 35 kVCTCT 50/5A505151Novercurrent / earth-fault52TRANSFORMER1600 kVA - Z=4%49thermal overloadCTCT 2500/5A505151NLV incoming protection520.4 kV LV BUSCTCT 1200/5A50/5151NQuay crane 11031 ACTCT 1200/5A50/5151NQuay crane 21031 ACTCT 1200/5A50/5151NQuay crane 31031 ACTCT 1200/5A50/5151NQuay crane 41031 AProtection layout & CT ratios are schematic / illustrative final settings per IEC 60255 / IEEE 242.
📋 Protection settings
CircuitProtectionSettingTimeStandard
HV incoming 35 kV50 instantaneous211 AinstIEC 60255-151 / IEEE 242
HV incoming 35 kV51 overcurrent32 A0.5 sIEC 60255-151 / IEEE 242
HV incoming 35 kV51N earth-fault5 A0.5 sIEC 60364-4-41
Transformer 1600 kVA49 thermal overload79% of ratedalarm 90%IEC 60076-7 / IEEE C57.91
LV incoming 0.4 kV50 instantaneous18475 AinstIEC 60947-2
LV incoming 0.4 kV51 overcurrent2771 A0.3 sIEC 60947-2 / IEC 60255
LV incoming 0.4 kV51N earth-fault462 A0.3 sIEC 60364-4-41
Quay crane 150/51/51N (MCCB)Ir 1134 A - Im 8248 A - Ig 206 A0.1 s (grading)IEC 60947-2 / IEC 60255
Quay crane 250/51/51N (MCCB)Ir 1134 A - Im 8248 A - Ig 206 A0.1 s (grading)IEC 60947-2 / IEC 60255
Quay crane 350/51/51N (MCCB)Ir 1134 A - Im 8248 A - Ig 206 A0.1 s (grading)IEC 60947-2 / IEC 60255
Quay crane 450/51/51N (MCCB)Ir 1134 A - Im 8248 A - Ig 206 A0.1 s (grading)IEC 60947-2 / IEC 60255
Settings are illustrative starting points — confirm with a protection coordination study per IEC 60255 / IEEE 242.
📚 Calculation book
CALCULATION BOOK
1600 kVA - 35kV/0.4kV - single - illustrative
1. Load calculation
Standard: IEC 60076 - IEC 60364-5-52
ParameterFormulaValue
Connected loadP = sum(kW)2,000 kW
Demand factorKd0.6
Demand powerPd = P x Kd1,200 kW
Power factorcos(phi) before -> after0.70 -> 0.95
Design apparent powerSd = Pd / cos(phi)1,263 kVA
Transformer loadingSd / Srated79%
2. Short-circuit calculation
Standard: IEC 60909
ParameterFormulaValue
System impedance (pu)Zs = S / Ssc0.32% (on 1600 kVA base)
Transformer impedanceZt = Z%4%
Total impedanceZ = Zt + Zs4.32%
LV prospective IscIsc = In / Z53.5 kA
HV prospective IscIsc = Ssc / (sqrt(3) x V)8.2 kA
Breaking checkIcu >= IscLV 65 kA (1.2x margin) PASS
3. Voltage drop
Standard: IEC 60364-5-52 Annex G
ParameterFormulaValue
Main feederdU = sqrt(3) x I x L x R / V300 mm2 - dU 1.50% @ 100 m
Limitmax 3%within limit
Transformer volt. reg.dU ~ loading x Z% x sin(phi)1.0% at full load
4. Reactive power / harmonics
Standard: IEC 61921 (PFC) - IEEE 519 (harmonics)
ParameterFormulaValue
Required compensationQc = Pd x (tan1 - tan2)0 kvar
PFC bankstandard step0 kvar
Detuned reactorp = 6%n/a
5. Grounding
Standard: IEC 60364-5-54 earthing arrangements and protective conductors LV earthing target 10 ohm (TN systems); 4 ohm used as a conservative design target - target 4 ohm
ParameterFormulaValue
Single rod resistanceR1 = rho/(2 x pi x L) x ln(4L/d)39.6 ohm
Rods requiredn = R1 / (target x 0.8)13 rod(s) <= 4 ohm
Rod specdia x length20 mm x 2.5 m
This calculation book is illustrative it consolidates the computed values with the referenced standards. A licensed engineer must verify and seal final design documents for construction.
🔧 Secondary schematic (control & signal)
SECONDARY CONTROL & SIGNAL CIRCUIT0.4 kV circuit breaker close/trip + indication + interlock (TYPICAL)+control supplyCS (close)interlock52Cclose coil-TC (trip)prot trip52Ttrip coilSIGNAL (indication)52a (closed)REDbreaker closed-TYPICAL CIRCUITStandard control/signal scheme for Quay crane 1.Project detailing required (wiring, terminal assignment).
🔩 Terminal strip (typical)
TERMINAL STRIP (TYPICAL)X1 secondary wiring terminals (typical project detailing required)TerminalFunctionWireX1:1control supply L+1.5 mm2X1:2control supply L-1.5 mm2X1:3close command1.5 mm2X1:4trip command1.5 mm2X1:5breaker 52a status1.5 mm2X1:6breaker 52b status1.5 mm2X1:7trip circuit healthy1.5 mm2X1:8earth / shield2.5 mm2
⚙️ Impact load & motor starting
ParameterValue
Impact peak2,600 kW (factor 1.3×)
Largest drive500 kW · VFD (1.3× In)
Start voltage dip2.2% vs limit 10% — OK ✓
🌀 Reactive & harmonic compensation
ParameterValue
Reactive compensation1798 kvar SVC/SVG + detuned bank (7% reactor)
Harmonic currentTHDi 30% → Ih 1,608 A
Resonancef_res 189 Hz below 5th harmonic → detuned (safe ✓)
📏 Standard basis (依据标准)
TopicStandard
Standard basisIEC · IEC 60364-5-52
Conductor ampacityIEC 60364-5-52 Table B.52.2–B.52.5 (copper, 3 loaded conductors, 30°C ambient, PVC) — typical/rounded values, conservative (±3%)
Voltage-drop limitIEC 60364-5-52 Annex G · max drop 3%
Winding temp riseIEC 60076-2 — winding temp rise 65 K (Class A insulation, ONAN)
kVA ratingsIEC 60076-1 R10 preferred numbers
Breaker framesIEC 60947-2 frame sizes (In)
Grounding targetIEC 60364-5-54 earthing arrangements and protective conductors — LV earthing target ≤ 10 Ω (TN systems); 4 Ω used as a conservative design target · target 4 Ω
Voltage fluctuation & flickerGB/T 12326 — voltage fluctuation and flicker limits (impact loads)
HarmonicsGB/T 14549 · IEC 61000-3-2 · IEC 61642 — harmonic limits & detuned filters
Rotating machinesIEC 60034 — rotating electrical machines
Power supply designGB 50052 — code for design of electric power supply systems
🧮 How it was calculated
1. Quay cranes: 4 × 500 kW = 2,000 kW
2. Impact peak = 2,000 × 1.3 = 2,600 kW (short-time)
3. Largest drive start (motor-starting): 500 kW × 1.3 → dip 2.2% vs limit 10%
4. Reactive compensation: Qc = 2,600 × (tanφ₁ − tanφ₂) = 1,798 kvar (SVC/SVG + detuned bank)
5. Harmonics: THDi 30% → Ih = 1,608 A · 7% detuned reactor (f_res 189 Hz)
6. Loads: P=2,000 kW, PF 0.70, 4 circuits
7. Demand: 2,000 × 0.6 = 1,200 kW
8. Transformer: S = 1,200 ÷ 0.95 = 1263.2 kVA → 1,600 kVA standard
9. Loading: 1,263 ÷ 1,600 = 79% (good range)
10. Voltage regulation: 79% × 4% × sinφ ≈ 1.0% at full load
11. HV: In 26.4 A, Isc 8.2 kA → KYN61-40.5-1250-25
12. LV: In 2309 A, Isc 53.5 kA (Xfmr Z 4% + system 0.3%) → GGD-2500, 1 feeder panel(s)
13. Grounding: R₁ 39.6 Ω → 13 rod(s)
14. Main feeder: 5× 300 mm² · ΔU 1.50% — OK
Summary
Estimated total (FOB Qingdao, EXW) — priced equipment$438,818
📋 Design notes
Pricing basis: FOB Qingdao (EXW) equipment price. Freight, duty and installation are not included — add for landed economics.
Transformer loading: 79% at design demand — good range.
Short-circuit check: HV 8.2 kA vs 25 kA (3.0× margin) · LV 53.5 kA vs 65 kA (1.2× margin).
Voltage regulation: ≈ 1.0% at full load (typical limit 5%).
Copper price linkage: Copper-wound transformer price tracks LME copper (current $14,115/t · 2026-09-14 · LME Copper (Sina hf_CAD)).
Parallel conductors: Single-cable ampacity exceeded — parallel conductors specified: main feeder 5× 300 mm², Quay crane 1 3× 185 mm², Quay crane 2 3× 185 mm², Quay crane 3 3× 185 mm², Quay crane 4 3× 185 mm² (per IEC 60364-5-52 / GB 50054).
Cable & grounding pricing: Cable conductors and grounding are priced from the confirmed cables-trays-grounding price reference (per-metre copper YJV; aluminium remains POA). The main copper busbar is POA — its length is project-specific.
Busway (high-current feeders): For LV feeders above ~2500 A, a busway (母线槽) trunking system is recommended instead of parallel cables.
Impact load: Impact factor 1.3× — rapid load swings from cranes/arc furnaces cause voltage flicker; dynamic SVC/SVG compensation is required.
Starting: Largest 500 kW drive started via VFD draws a 2.2% bus dip (within the 10% limit).
Harmonics: 30% THDi from VFD/rectifier loads — a 7% detuned filter keeps the branch inductive below the 5th harmonic.
SVC/SVG pricing: Dynamic reactive compensation is priced at $183,000/unit (±5 Mvar, FOB reference).
Crane regenerative drive: Quay cranes use four-quadrant (regenerative) VFDs that feed lowering energy back to the bus — this reduces energy consumption and DC-bus overvoltage, quoted per project.
Shore power (岸电): A shore power supply converts the port grid to the vessel’s voltage/frequency (IEC/ISO 80005-1) so berthed ships shut down their auxiliary engines — quoted per project.

计算过程说明

选型计算方式

冲击峰值 = 连接负载 × 冲击系数。无功补偿 Qc = P × (tanφ₁ − tanφ₂) 用于校正较低的自然功率因数,采用快速 SVC/SVG 抑制闪变,并配置失谐滤波组抑制谐波。最大驱动启动 kVA 需对照电压跌落限值进行校验(对闪变敏感母线通常为 10%)。

适用标准

选型参考 GB/T 12326(电压波动与闪变)、GB/T 14549 和 IEC 61000-3-2(谐波)、IEC 61642(失谐滤波器)、IEC 60034(旋转电机)及 GB 50052(供电设计)。

常见问题

冲击负荷如何影响港口的电能质量?

岸桥和绞车带来快速、大幅的负荷波动(冲击负荷),引起电压闪变。冲击系数 = 峰值/平均负荷,常为 1.3-1.5。当闪变超出 GB/T 12326 限值时,需加装响应 5-20 ms 的动态无功补偿(SVC/SVG)。计算器按冲击系数配置补偿容量。

电弧炉为什么需要 SVC 或 SVG 补偿?

电弧炉电流剧烈波动,闪变与谐波严重,熔化期功率因数低至 0.6-0.7。容量为炉子 30-50% 的 SVC/SVG 可恢复功率因数并抑制闪变,满足 GB/T 12326 与 IEEE 519。50 MW 电炉典型需 15-25 Mvar 动态补偿。

港口岸桥系统用多大电压供电?

大型岸桥(每台 500 kW-1.5 MW)以 10 kV 或 35 kV 供电,在泊位附近降压到 0.4/0.69 kV 供传动。沿码头布置 10 kV 环网(环网柜/开关柜)是标准做法。计算器默认 35 kV 模拟多泊位岸桥群,小港用 10 kV。

岸桥的谐波如何治理?

岸桥传动以变频为主,注入 5、7、11 次谐波,未治理时 THDi 常达 30%。采用有源前端(AFE)或去谐无源滤波 + APF 可将公共连接点 THD 控制在 IEEE 519 的 5-8% 限值内。计算器在 THDi 超阈值时配置谐波滤波。

岸桥供电选型用多大的典型工作制?

岸桥属断续工作制(起升/下降/行走),即便繁忙期平均需求也只有装机功率的 40-60%。供电变压器按最大同时需求加最大起升启动冲击选型,而非铭牌功率简单相加。计算器套用冲击系数与同时系数避免超配。

港口开关柜要耐受多大短路水平?

港口 35 kV 开关柜通常 25-31.5 kA,10 kV 柜 25-31.5 kA,低压柜 50-65 kA。额定值须大于各母线计算故障电流(IEC 60909)。岸桥传动也贡献故障电流,50 MVA 电源的 35 kV 母线至少需 25 kA。计算器校核柜体额定与故障水平。

嵌入此计算器

复制下方 iframe 代码,即可将此计算器嵌入任何网站。嵌入页面为 noindex,适配任意宽度。

相关计算器

结果为工程估算,仅供参考。最终设计须由当地持证工程师根据现场条件和适用规范确认。价格为 FOB 青岛(EXW),不含运费、关税及安装费。

Design the complete system

Move to the full Power System Configurator — 4 layers, 13 drawings, protection schedule, BOM and price.

Open Power System Configurator →

发送我的完整设计报告

免费获取完整设备清单(BOM)、单线图、计算步骤与 FOB 报价的 PDF 报告,无需注册。

💬 WhatsApp 咨询

您的信息仅用于回复询盘,不用于任何其他用途。