🔗 Calculadora de Queda de Tensão em Cabo Fotovoltaico

Verifique a queda de tensão do lado CC e a perda de linha de uma string fotovoltaica, confirme a ampacidade do cabo (1,25 × Isc) e escolha a seção mínima que fica dentro da diretriz de queda de 2%.

Começar a Calcular
⚠️ DC drop guideline < 2% per IEC 60364 / 62548.

🔗 String & Cable

📊 Voltage-Drop Result

Enter the string current and distance — voltage drop and cable sizing appear here instantly.

Para instaladores solares que dimensionam cabos home-run CC e conectores.

Como é calculado

· Resistência de ida e volta: R = 2 × ρ × L ÷ A (ρ cobre 0,0175 Ω·mm²/m).

· Queda de tensão: VD = I × R; VD% = VD ÷ V_string × 100.

· Verificação de ampacidade: necessário ≥ I × 1,25; classificação do conector (MC4) ≥ I × 1,25.

Normas de referência

StandardScope
IEC 60364Instalações elétricas de baixa tensão (ampacidade de cabos)
NEC 690Sistemas fotovoltaicos solares (ampacidade do condutor 1,25 × Isc)

Exemplo resolvido — 13 A em 50 m → 1,42% em 4 mm²

1. Corrente da string 13 A, distância 50 m, 4 mm², tensão da string 400 V.

2. R = 2 × 0,0175 × 50 ÷ 4 = 0,44 Ω; VD = 13 × 0,44 = 5,7 V = 1,42%.

3. Ampacidade: 13 × 1,25 = 16,3 A ≤ 32 A (4 mm²) OK.

4. 1,42% está dentro da diretriz de 2% — 4 mm² é suficiente.

FAQ

What voltage drop is acceptable in a PV DC cable?

Design practice limits total DC-side voltage drop to about 2% (IEC 60364 and common PV guidelines), split roughly 1% in the string cabling and 1% in the DC run to the inverter. Higher drop means lost energy — every 1% of drop is roughly 1% of lost annual yield. The calculator checks the drop and recommends the minimum cross-section.

How do I size a PV cable for ampacity?

PV DC cables must carry the string short-circuit current with a safety factor (usually 1.25x Isc, and 1.56x per NEC). For a 550 W module with Isc ~13.9 A and a two-parallel-string combiner, the combined current is ~35 A, so a 6 mm2 copper cable (rated ~40-45 A) is typical. The calculator verifies ampacity and derating.

Copper or aluminum for PV DC cabling?

PV string and DC cables are almost always copper because DC circuits are low-voltage and ampacity-sensitive; aluminium would need a much larger cross-section for the same drop. Copper is also easier to terminate on MC4 connectors. Aluminium appears only in long AC medium-voltage collector runs. The calculator defaults to copper for DC.

How long can a PV DC cable run be?

DC run length is limited by the 2% voltage-drop budget. For a 10 kW string at 500 V DC and 20 A, a 4 mm2 copper cable can run roughly 40-60 m before exceeding 2%. Longer runs need 6-10 mm2 cable or a higher system voltage. The calculator computes the maximum length for a given cross-section.

What DC cable type is used for solar arrays?

PV arrays use double-insulated, UV-resistant solar cable (H1Z2Z2-K / EN 50618, rated 1.5 kV DC and -40 to +90 deg C) for outdoor runs. Single-core copper, usually 4-6 mm2 for strings and 10-35 mm2 for DC mains. The calculator selects cable by ampacity and drop and cites the applicable standard.

Incorporar esta calculadora

Adicione esta calculadora ao seu próprio site gratuitamente. O iframe se adapta a qualquer largura e roda inteiramente no navegador do visitante.

Ferramentas relacionadas

Estimativas de referência (FOB Qingdao, EXW) para projeto preliminar — não são uma cotação final. Confirme o dimensionamento com seu projeto e as normas locais.

Send my complete design report

Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.

💬 Chat on WhatsApp

Your data stays private. No spam — only a reply to your enquiry.