🔗 Kalkulator Jatuh Tegangan Kabel PV

Periksa jatuh tegangan sisi DC dan rugi saluran string PV, verifikasi ampasitas kabel (1.25 × Isc), dan pilih penampang minimum yang tetap di bawah panduan jatuh tegangan 2%.

Mulai Menghitung
⚠️ DC drop guideline < 2% per IEC 60364 / 62548.

🔗 String & Cable

📊 Voltage-Drop Result

Enter the string current and distance — voltage drop and cable sizing appear here instantly.

Untuk pemasang tenaga surya yang menentukan ukuran kabel dan konektor DC home-run.

Cara menghitungnya

· Hambatan dua arah: R = 2 × ρ × L ÷ A (ρ tembaga 0.0175 Ω·mm²/m).

· Jatuh tegangan: VD = I × R; VD% = VD ÷ V_string × 100.

· Pemeriksaan ampasitas: yang diperlukan ≥ I × 1.25; rating konektor (MC4) ≥ I × 1.25.

Standar yang dirujuk

StandardScope
IEC 60364Instalasi listrik tegangan rendah (ampasitas kabel)
NEC 690Sistem fotovoltaik surya (ampasitas konduktor 1.25 × Isc)

Contoh perhitungan — 13 A sepanjang 50 m → 1.42% pada 4 mm²

1. Arus string 13 A, jarak 50 m, 4 mm², tegangan string 400 V.

2. R = 2 × 0.0175 × 50 ÷ 4 = 0.44 Ω; VD = 13 × 0.44 = 5.7 V = 1.42%.

3. Ampasitas: 13 × 1.25 = 16.3 A ≤ 32 A (4 mm²) OK.

4. 1.42% berada dalam panduan 2% — 4 mm² sudah mencukupi.

FAQ

What voltage drop is acceptable in a PV DC cable?

Design practice limits total DC-side voltage drop to about 2% (IEC 60364 and common PV guidelines), split roughly 1% in the string cabling and 1% in the DC run to the inverter. Higher drop means lost energy — every 1% of drop is roughly 1% of lost annual yield. The calculator checks the drop and recommends the minimum cross-section.

How do I size a PV cable for ampacity?

PV DC cables must carry the string short-circuit current with a safety factor (usually 1.25x Isc, and 1.56x per NEC). For a 550 W module with Isc ~13.9 A and a two-parallel-string combiner, the combined current is ~35 A, so a 6 mm2 copper cable (rated ~40-45 A) is typical. The calculator verifies ampacity and derating.

Copper or aluminum for PV DC cabling?

PV string and DC cables are almost always copper because DC circuits are low-voltage and ampacity-sensitive; aluminium would need a much larger cross-section for the same drop. Copper is also easier to terminate on MC4 connectors. Aluminium appears only in long AC medium-voltage collector runs. The calculator defaults to copper for DC.

How long can a PV DC cable run be?

DC run length is limited by the 2% voltage-drop budget. For a 10 kW string at 500 V DC and 20 A, a 4 mm2 copper cable can run roughly 40-60 m before exceeding 2%. Longer runs need 6-10 mm2 cable or a higher system voltage. The calculator computes the maximum length for a given cross-section.

What DC cable type is used for solar arrays?

PV arrays use double-insulated, UV-resistant solar cable (H1Z2Z2-K / EN 50618, rated 1.5 kV DC and -40 to +90 deg C) for outdoor runs. Single-core copper, usually 4-6 mm2 for strings and 10-35 mm2 for DC mains. The calculator selects cable by ampacity and drop and cites the applicable standard.

Sematkan kalkulator ini

Tambahkan kalkulator ini ke situs web Anda sendiri secara gratis. Iframe menyesuaikan dengan lebar apa pun dan berjalan sepenuhnya di peramban pengunjung Anda.

Alat terkait

Perkiraan referensi (FOB Qingdao, EXW) untuk desain awal saja — bukan penawaran final. Konfirmasikan ukuran terhadap proyek dan standar lokal Anda.

Send my complete design report

Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.

💬 Chat on WhatsApp

Your data stays private. No spam — only a reply to your enquiry.