🧲 Kalkulator Penentuan Reaktor
Tentukan ukuran reaktor seri atau shunt dari kVAR bank kapasitor dan rasio impedansi Anda, lalu dapatkan kVAR reaktor, model, dan harga FOB referensi.
⚙️ Bank Kapasitor
📊 Result
Untuk insinyur yang menambahkan reaktor detuned atau shunt ke bank faktor daya dan filter harmonisa.
Cara menghitungnya
· Kapasitas reaktor: kVAR_reaktor = kVAR_kapasitor × impedansi %.
· Rasio impedansi standar: 6% / 7% (detuned), 12% / 14% (filter harmonisa).
· Harga = basis × faktor tegangan × faktor impedansi × faktor koneksi.
Standar yang dirujuk
| Standard | Scope |
|---|---|
| IEC 60289 | Reaktor — persyaratan umum |
| GB/T 10229 | Setara Cina untuk reaktor |
Contoh perhitungan — bank 200 kVAR pada 7% → 14 kVAR
1. Bank kapasitor 200 kVAR, impedansi seri 7%.
2. kVAR reaktor = 200 × 7% = 14 kVAR.
3. Model CKSG-14/10 (seri, 10 kV); harga referensi dari tabel harga reaktor.
FAQ
What is the difference between a series and shunt reactor?
A series Reactor is connected in series with a capacitor bank to detune Harmonics (typically 6% or 7% impedance) and protect capacitors from inrush. A shunt reactor is connected to ground or across the line to absorb capacitive reactive power and limit overvoltage on long lines. The calculator prices both (CKSG series, BKSC shunt).
What detuning factor do I choose — 6% or 7%?
A 7% reactor shifts the resonant frequency below the 5th harmonic (250 Hz) to avoid resonance with the 5th and higher harmonics; 6% is used where only the 5th is present. 7% is the safer default for most industrial networks. The calculator sizes the reactor kVAR from the capacitor bank kVAR.
How is a reactor kVAR rating related to the capacitor bank?
The reactor kVAR is the detuning percentage of the capacitor kVAR. For a 100 kVAR bank at 7%, the reactor is 7 kVAR. The reactor must also carry the capacitor current plus harmonics, so it is rated for the bank current at the detuned frequency. The calculator computes the reactor rating automatically.
Why do capacitor banks need reactors?
Without a reactor, a capacitor bank can form a parallel resonance with the Transformer inductance near a harmonic frequency, amplifying harmonic current and overheating the bank. A 6-7% reactor detunes the circuit below the dominant harmonic. The calculator flags the detuning recommendation and prices the reactor.
What standard applies to power reactors?
Series and shunt reactors follow IEC 60076-6 (reactors) and GB/T 1094.6, with rated voltage, kvar and impedance as key parameters. Temperature Rise and insulation class follow the same transformer standards. The calculator's BOM cites the applicable standard for the selected reactor.
Sematkan kalkulator ini
Tambahkan kalkulator ini ke situs web Anda sendiri secara gratis. Iframe menyesuaikan dengan lebar apa pun dan berjalan sepenuhnya di peramban pengunjung Anda.
Alat terkait
Perkiraan referensi (FOB Qingdao, EXW) untuk desain awal saja — bukan penawaran final. Konfirmasikan ukuran terhadap proyek dan standar lokal Anda.
Send my complete design report
Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.
Your data stays private. No spam — only a reply to your enquiry.