PLTS utilitas 500 kW: 910 modul 550 Wp + 2 inverter string 250 kW + gardu induk box 630 kVA Ulasan Mendalam
910×550 Wp · 2 inverter string 250 kW · gardu induk box tingkat string 630 kVA (10 kV) · SVG ±1 Mvar · ekspor 10 kV
1 · TL;DR Conclusion
Kesimpulan: pembangkit listrik tenaga surya utilitas 500 kW ini menggunakan 910 modul 550 Wp (500 kWp) + 2 inverter string 250 kW → gardu induk kotak tingkat string 630 kVA (YB-630/10) → SVG ±1 Mvar → ekspor 10 kV — total konfigurator ≈ $390.830 (FOB), EPC ≈ $315.850, pengembalian modal 9 tahun, IRR 10,45%, ROI 25 tahun 178% (tingkat kelayakan).
- •Modul 910×550 Wp (500 kWp), 34 string (6–27 modul/string), Voc dingin 55,4 V / Vmp panas 36,6 V
- •2 inverter string 250 kW (MPPT 1500 V) paralel; gardu induk kotak tingkat string 630 kVA (YB-630/10)
- •SVG ±1 Mvar (PF ±0,95 kontinu) + switchgear HV KYN28A-12 + RMU-SF6; ekspor 10 kV
- •Pembangkitan 507.600 kWh/tahun (P50), P90 481.570 kWh, pendapatan $40.608/tahun @ $0,08/kWh PPA
- •Ekonomi: $315.850 EPC, pengembalian 9 tahun, IRR 10,45%, ROI 25 tahun 178%
2 · Solution Overview
Mega-base PV utilitas adalah kasus pembangkitan-ekspor 100%: modul memberi daya pada inverter string (tingkat string, vs inverter pusat) yang menaikkan tegangan ke gardu kotak, lalu mengekspor melalui SVG dan peralatan switchgear HV. Pada 500 kW, mesin memilih pengumpulan/ekspor 10 kV; pada ≥2500 kVA (multi-MW) beralih ke pengumpulan 35 kV — topologi standar basis utilitas.
3 · Design Process & Rationale
1. Identifikasi kebutuhan
Megabase PV utilitas 500 kW, ekspor 100%; flag generationExport eksplisit memicu mode ekspor pembangkitan.
2. Pemilihan modul
PERC mono 550 Wp: 500 kWp ÷ 550 W = 910 modul.
3. Desain string
Rentang string terkoreksi suhu 6–27 modul/string, diambil pada 27 → 34 string; Voc dingin 55,4 V, Vmp panas 36,6 V.
4. Pemilihan inverter
Tingkat string (vs sentral) 2×250 kW paralel, MPPT 1500 V, total 500 kW.
5. Gardu kotak tingkat string
500 kW ÷ 0,8 PF = 625 kVA → tingkat 630 kVA (YB-630/10); gardu kotak tingkat string adalah aset inti basis utilitas.
6. Reaktif & ekspor
SVG ±1 Mvar (PF ±0,95) + switchgear HV KYN28A-12 + RMU-SF6; 500 kW diekspor pada 10 kV.
7. Peningkatan tegangan kolektor
Pada step-up ≥2500 kVA (multi-MW) mesin otomatis beralih ke koleksi 35 kV — topologi standar basis utilitas.
Pain Points → Solution → Evidence
Salah memilih antara inverter sentral dan string menyebabkan kerugian mismatch MPPT — bayangan/gangguan menurunkan output seluruh lokasi.
Inverter string (2×250 kW) memberikan MPPT tingkat string; gangguan satu string hanya memengaruhi string tersebut.
INV-250kW ×2, MPPT 1500 V, gardu induk kotak tingkat string.
Fluktuasi output PV membuat batas reaktif/tegangan di titik grid terlampaui — risiko penalti grid atau trip.
SVG ±1 Mvar reaktif dinamis kontinu (PF ±0,95) + proteksi koneksi grid.
BOM mencakup SVG ±1 Mvar; sesuai GB/T 19964.
Tingkat gardu step-up kotak yang salah menyebabkan overload atau over-investasi.
500 kW ÷ 0,8 = 625 kVA → tingkat standar 630 kVA.
Gardu induk kotak tingkat string 630 kVA (YB-630/10).
4 · Key Parameter Deep-Read
| Parameter | Value | Basis | Impact & Boundary |
|---|---|---|---|
| Jumlah modul | 910 × 550 Wp | 500 kWp ÷ 550 W = 910 modul | Kapasitas DC 500 kWp Perubahan daya modul memerlukan perhitungan ulang |
| Desain string | 34 string · 27 modul/string | 6–27 modul/string dikoreksi suhu | Voc dingin 55,4 V / Vmp panas 36,6 V Dibatasi oleh jendela tegangan MPPT inverter |
| Inverter | 2 × 250 kW string | Tingkat ≤250 kW diparalelkan | MPPT 1500 V, pelacakan tingkat string Lanjutkan paralelisasi di atas 250 kW |
| Gardu induk kotak tingkat string | 630 kVA (YB-630/10) | 500 kW ÷ 0,8 PF = 625 → 630 kVA | Ekspor step-up 10 kV ≥2500 kVA beralih ke pengumpulan 35 kV |
| Rating SVG | ±1 Mvar | 25% dari 500 kW = 125 kvar → 1 Mvar | PF ±0,95, dukungan tegangan Batas minimum mesin ≥1 Mvar |
| P50 tahunan | 507.600 kWh | 500 kW × 1150 jam × PR 0,8 | $40.608/tahun @ $0,08/kWh P90 = 481.570 kWh (CV 0,04) |
5 · Drawing Deep-Read
| Parameter | Formula | Value |
|---|---|---|
| Array capacity | Ppv | 500 kWp |
| Modules | N = Ppv / Wmodule | 910 pcs |
| Strings | S = N / ns | 34 strings |
| Parameter | Formula | Value |
|---|---|---|
| Modules/string range | nMin - nMax | 6-27 |
| Cold Voc | Voc x ns @ Tmin | 55.4 V |
| Hot Vmp | Vmp x ns @ Tmax | 36.6 V |
| Parameter | Formula | Value |
|---|---|---|
| Performance ratio | PR | 0.846 |
| Annual yield (P50) | Ppv x H x 365 x PR | 507,600 kWh/yr |
| P90 (bankable) | P50 x (1 - 1.282CV) | 481,570 kWh/yr |
The following drawings are shown for reference (full set in the configurator “View design document”):
6 · Operation Demo (Deep-Read)
Aliran energi
Modul 500 kWp → inverter string → kotak 630 kVA → SVG → ekspor 10 kV, 100% online.
Desain string
910 modul dalam 34 string (27/string), Voc dingin 55,4 V, Vmp panas 36,6 V — jendela tegangan MPPT yang dikoreksi suhu.
Reaktif & kualitas daya
±1 Mvar SVG reaktif dinamis kontinu, PF ±0,95, dukungan tegangan di bawah fluktuasi PV.
Ekonomi
507.600 kWh/tahun, $40.608/tahun; $315.850 EPC, pengembalian 9 tahun, IRR 10,45%.
Other views (shown): LCC (biaya siklus hidup) · Kualitas daya & harmonisa · Profil tegangan · Fitur skema · Derating lingkungan
7 · Economics & Payback
Peralatan FOB ≈ $390.830 (modul $150.000 + inverter string $63.705 + pemasangan $75.000 + gardu induk kotak $29.500 + SVG $50.000 + switchgear HV $16.750 + RMU $5.875); EPC ≈ $315.850. Tahunan 507.600 kWh → $40.608/tahun @ $0,08/kWh PPA; pengembalian 9 tahun, IRR 10,45%, ROI 178% dalam 25 tahun.
8 · FAQ
Box substation step-up apa untuk 500 kW PV?
Inverter string vs central — bagaimana memilih?
Mengapa 10 kV dan bukan 35 kV?
Dari mana 910 modul berasal?
Berapa payback-nya?
Mengapa SVG diperlukan?
Berapa energi per tahun?
Apa yang dicakup $390.830?
Apa itu box substation tingkat string?
Special Considerations
- Pada 500 kW mesin memilih pengumpulan/ekspor 10 kV (gardu induk kotak tingkat string YB-630/10); pada step-up ≥2500 kVA (multi-MW) secara otomatis beralih ke pengumpulan 35 kV — "pengumpulan 35 kV" adalah standar basis utilitas, sedangkan skala demo 500 kW ini adalah 10 kV.
- "Gardu induk kotak tingkat string" mencerminkan topologi inverter string (vs sentral): 2 inverter string 250 kW memberikan pelacakan MPPT tingkat string, sehingga gangguan satu string hanya memengaruhi string tersebut.
- Perhitungan sisi penerima (hubung singkat 10/0,4 kV, aliran beban, busur api, N-1) sudah usang dalam mode ekspor pembangkitan — abaikan; data sisi pembangkit ada di genPlant.
- Daya modul dan kemiringan pemasangan (25,9°) adalah default mesin — konfirmasikan dengan institut desain terhadap iradiansi lokasi dan lintang.
- Pembangkitan tahunan menggunakan 1150 jam beban penuh × PR 0,8 (P50); aktual sangat bergantung pada iradiansi lokasi dan kotoran.
Turn this into your project
Open this exact scenario pre-loaded in the Power System Configurator, then generate the full design document or the operation & techno-economic assessment.
Open in Power System Configurator →Related Scenarios
Pasokan Peralatan Konvensional & Tenaga Surya Terpadu
Dari desain sistem distribusi tenaga listrik hingga energi surya — trafo, switchgear, gardu induk, dan peralatan tenaga surya, berukuran dan ditempatkan di satu tempat. Gunakan kalkulator kami untuk mendapatkan tagihan bahan lengkap dan harga FOB.