ZGS-Z-10-250
ZGS Series • 250 kVA • 12/0.4 kV
TECHNICAL DRAWING
Model: ZGS-Z-10-250 | Type: Oil-immersed transformer | Capacity: 250 kVA
Product photo

FRONT ELEVATION
ELECTRICAL SCHEMATIC
TERMINAL BLOCK
LEGEND:
ZGS-Z-10-250 is a 250 kVA, 12/0.4 kV american pad-mounted transformer manufactured by Shandong Yaqing Electrical Technology Co., Ltd. (QDTB) in Qingdao, China, designed and tested in accordance with GB/T 17467, IEEE C57, ANSI C57, vector group Dyn11 (IEEE), short-circuit impedance 4%, approximate weight 2500 kg. Available on FOB Qingdao terms; datasheet, routine test report and GA drawing issued with each unit.
Technical Specifications
Full technical specification
Every value below is the guaranteed figure for this model. Where a parameter depends on the site, the design basis is stated.
Electrical data
| Rated power | 250 kVA |
|---|---|
| HV winding | 12 kV |
| LV winding | 0.4 kV |
| Frequency | 50 Hz |
| Impedance voltage at 75 °C | 4 % |
| Vector group | Dyn11 (IEEE) |
| Cooling method | ONAN |
| No-load loss | 400 W |
| Load loss at 75 °C | 3050 W |
| Efficiency at full load, unity power factor | S11 % |
| No-load current | 0.7 % |
| HV current | 12.03 A |
| LV current | 360.84 A |
| Tap changer | NLTC ±2×2.5% |
Insulation and dielectric
| BIL, HV winding | 95 kV |
|---|---|
| BIL, LV winding | 30 kV |
| Temperature rise, average winding | 65 K |
| Hot-spot allowance | 80 K |
| Insulation class | A (105°C) |
Mechanical
| Total weight | 2500 kg |
|---|---|
| Dimensions (L x W x H) | 1800×1400×2000 mm |
| Core construction | silicon-steel |
| Winding material | copper |
Compliance and standards
| Compliance and standards | GB/T 17467, IEEE C57, ANSI C57 |
|---|---|
| Loss tolerance | +10 % on total losses, +10 % on each component (guaranteed values) |
| Short-circuit withstand | 25 × rated current for 2 s · Category I (≤ 2.5 MVA) |
| Overload capability | 100 % of rating at 65 K rise, 40 °C ambient |
| Paint system | C4 (high durability, industrial / urban atmosphere) |
| Protection Level | IP54 |
Testing and acceptance
Routine tests — performed on every unit
- Winding resistance measurement
- Voltage ratio and polarity / phase relation
- No-load loss and excitation current
- Load loss and impedance voltage
- Applied potential test
- Induced potential test
- Insulation resistance
- Insulating oil dielectric strength
Type tests — design-proven, certificates available
- Temperature rise test
- Lightning impulse withstand (BIL)
- Sound level measurement
- Short-circuit withstand (IEC 60076-5)
Supply scope
Included in the supply
- Pressure relief valve
- Oil level gauge
- Dial-type oil thermometer
- Drain valve and filter valve
- Lifting lugs
- Earthing terminals (tank and neutral)
- Rating plate
- HV and LV bushings
- Transformer as specified
- Fittings listed above
- Routine test report
- Rating plate and outline drawing
- Packing for the agreed mode of transport
Not included
- Foundation and civil works
- Cable termination and glands
- Switchgear and protection relays
- Installation and commissioning labour
- Spare parts unless ordered
Installation and operating conditions
| Design ambient temperature | 40 °C |
|---|---|
| Design altitude | 1000 m |
| Pollution degree | Pollution degree III (outdoor), creepage per IEC 60815 |
Reference network study
Reference network, not a project-specific studyResults below come from a steady-state study of this transformer inside a standard reference network, computed at build time. They describe the reference case only — a real project depends on the actual grid strength, cable runs, load profile and protection settings.
| Prospective short-circuit current at LV busbar | 9.35 kA | three-phase at the LV terminals, computed from this transformer's uk alone; upstream grid impedance would reduce it further (conservative) |
|---|---|---|
| Voltage deviation at the reference load point | 2.20 % | min V = 97.80 % of nominal. Reference network only (10 m HV + 20 m LV copper cable); project cable runs will differ. Reference network only (10 m HV + 20 m LV copper cable); project cable runs will differ. |
| Hot-spot temperature at the reference load | 89.2 °C (limit 140 °C) | rise 49.2 K · winding avg 41.0 K · within limit · IEC 60076-7 exponential model, ambient 40 °C |
| Harmonic voltage distortion limit at this voltage level | 5 % THD | IEEE 519 Table 1 — system-side limit for the 12 kV level, not a transformer rating |
| Inrush current at energisation | 10× rated peak · 5.1 kA peak | decay τ 0.319 s · 2nd harmonic 43 % · harmonic restraint recommended for the protection relay · bus voltage dip 0.71 % · worst-case switching angle, IEC 60076-8 / IEEE C57.12.90 |
| Transformer loading in the reference network | 71.1 % | active power ÷ rated kVA (does not convert by power factor) |
| Short-circuit impedance used | 4 % | |
| Prospective short-circuit current at transformer LV terminals (uk only, no cable) | 9.02 kA | Sn/(√3·U·uk) at the terminals — the upper bound used for switchgear and breaker selection; the row above is the same quantity after 10 m HV + 20 m LV reference cable |
Reference network assumptions
- HV busbar reference; the reported short-circuit current is set by the transformer uk alone (upstream grid impedance not included)
- 10 m Cu cable, 120 mm², in air
- 20 m Cu cable, 240 mm², in air
- 80 % of transformer rating at cos φ = 0.90
- Steady-state reference network, not a project-specific study
- transformer model: ZGS-Z-10-250 (250 kVA, 12 kV / 0.4 kV, uk 4 %)
- losses used: P0 400 W, Pk 3050 W ((this product's nameplate values))
Study computed at build time 2026-11-16 · engine: ESH / IEC 60909
Open the working-point study — change load and ambient temperature
Hot-spot and winding temperature are recomputed on the reference network as you move the load between 40 % and 100 %. Short-circuit current stays fixed — it is set by the transformer impedance.
Product Description
ZGS-Z-10-250 American pad-mounted transformer substation. Dead-front SF6 load break switch, bayonet fuse, pressure relief valve. For residential and light commercial distribution.
ZGS-Z-10-250 - Frequently Asked Questions
QWhat is the impedance voltage of the ZGS-Z-10-250?
The ZGS-Z-10-250 has an impedance voltage of 4 % at rated current, measured at 75 °C. Tolerance is plus or minus 7.5 % unless otherwise agreed, per IEEE C57.12.00 Table 16.
QWhat is the efficiency of the ZGS-Z-10-250?
At full load and unity power factor the ZGS-Z-10-250 reaches S11 % efficiency, with 400 W no-load loss and 3050 W load loss at 75 °C.
QWhat insulation level does the ZGS-Z-10-250 have?
The HV winding is rated 95 kV BIL and the LV winding 30 kV BIL, per IEEE C57.12.00 Table 1 for the 12 kV / 0.4 kV voltage class.
QWhat tests are performed before shipment?
Every unit receives 8 routine tests per IEEE C57.12.90, including winding resistance, voltage ratio, no-load loss and excitation current, load loss and impedance, applied potential, induced potential and insulation resistance. The test report is issued with the unit.
QWhat is included in the supply of the ZGS-Z-10-250?
The transformer with its standard fittings, the routine test report, the rating plate and the outline drawing. Foundation, cable termination, switchgear, protection relays and installation labour are not included.
QWhat temperature rise and ambient conditions apply?
Average winding rise is 65 K with an 80 K hot-spot allowance, designed for 40 °C ambient at altitudes up to 1000 m. Above these values the rating is derated per IEEE C57.12.00.
QWhat are the main applications of ZGS-Z-10-250?
ZGS-Z-10-250 (ZGS series, American Pad-Mounted Transformers) is widely used in industrial power distribution, commercial buildings and utility power systems. Can be flexibly configured according to actual project requirements.
QCan ZGS-Z-10-250 be custom ordered?
Yes. QDTB® provides comprehensive OEM/ODM customization services. Parameters such as capacity, voltage ratio, cooling method, connection group and protection class can all be adjusted. Over 25 years of manufacturing experience ensures consistent quality.
QDoes ZGS-Z-10-250 stay within its temperature rise limit at rated load?
At rated load with 40 °C ambient, the hot-spot temperature of ZGS-Z-10-250 reaches 89.2 °C, which is within the 140 °C limit of IEC 60076-2 for this insulation class. The winding average temperature rise is 41.0 K. Values follow the IEC 60076-7 exponential thermal model at 80 % loading in a reference network; site ambient temperature and actual load profile must be verified for a specific project.
QWhat is the prospective short-circuit current at the LV busbar of ZGS-Z-10-250?
In the standard reference network used across this catalogue - 10 m Cu 120 mm² HV cable, 20 m Cu 240 mm² LV cable in air, load at 80 % of rating with cos φ = 0.90 - the prospective short-circuit current at the LV busbar of ZGS-Z-10-250 is 9.35 kA. It is set by this unit short-circuit impedance of 4 % alone; upstream grid impedance is not included, so it is a conservative upper bound. Voltage deviation at the reference load point is 2.20 % and transformer loading is 71.1 %. This is a reference-network result, not a project-specific study.