QDTB® Transformer

Motor Starting & Voltage Dip Calculator

Check the bus voltage dip when a motor starts — starting current, dip %, starting-method comparison and the minimum supply or transformer rating to stay within limits.

Start Calculating

Result

Enter your load → get a full design & BOM in seconds

Sample output
Bus voltage dip at start
6.8 %
90 kW motor · 380 V · Direct-on-line (DOL) · limit 15% · Within limit ✓
Rated current
178.7 A
Starting current
1162 A
Starting kVA
765 kVA
Bus short-circuit
10.5 MVA
Starting calculation
QuantityValue
Motor rated current InP ÷ (√3·U·cosφ·η) = 90 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 178.7 A
Starting current multiple6.5× (Direct-on-line (DOL))
Starting current Ist178.7 × 6.5 = 1162 A
Starting apparent power90 ÷ (0.9 × 0.85) × 6.5 = 765 kVA
Bus short-circuit capacity630 kVA ÷ 6% = 10.5 MVA
Voltage dipSstart ÷ (Sstart + Ssc) = 6.8% vs limit 15%
Starting-method comparison
MethodkstVoltage dipVerdict
Direct-on-line (DOL)6.5×6.8%OK
Star-delta (Y-Δ)2.2×2.4%OK
Soft starter3.0×3.3%OK
VFD (variable speed)1.3×1.4%OK
Recommendation
Direct-on-line (DOL)
Current method keeps the bus voltage dip within the limit.
Bill of materials
EquipmentSpecQtySubtotal
DOL starter cabinet90 kW · 380 V · Direct-on-line (DOL) (6.5× In)1POA
Total equipmentPOA

For electrical engineers and contractors sizing motor starters and checking voltage dip during motor starting on LV/MV systems.

Use the calculator

Worked example

A pre-computed reference example (crawlable — no JavaScript required). Enter your own parameters above for a live result.

Worked example — 90 kW motor, DOL starting, 630 kVA transformer

Bus voltage dip at start
6.8 %
90 kW motor · 380 V · Direct-on-line (DOL) · limit 15% · Within limit ✓
Rated current
178.7 A
Starting current
1162 A
Starting kVA
765 kVA
Bus short-circuit
10.5 MVA
Starting calculation
QuantityValue
Motor rated current InP ÷ (√3·U·cosφ·η) = 90 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 178.7 A
Starting current multiple6.5× (Direct-on-line (DOL))
Starting current Ist178.7 × 6.5 = 1162 A
Starting apparent power90 ÷ (0.9 × 0.85) × 6.5 = 765 kVA
Bus short-circuit capacity630 kVA ÷ 6% = 10.5 MVA
Voltage dipSstart ÷ (Sstart + Ssc) = 6.8% vs limit 15%
Starting-method comparison
MethodkstVoltage dipVerdict
Direct-on-line (DOL)6.5×6.8%OK
Star-delta (Y-Δ)2.2×2.4%OK
Soft starter3.0×3.3%OK
VFD (variable speed)1.3×1.4%OK
Recommendation
Direct-on-line (DOL)
Current method keeps the bus voltage dip within the limit.
Bill of materials
EquipmentSpecQtySubtotal
DOL starter cabinet90 kW · 380 V · Direct-on-line (DOL) (6.5× In)1POA
Total equipmentPOA

Worked example — 250 kW motor, soft starter, 20 MVA grid

Bus voltage dip at start
4.7 %
250 kW motor · 380 V · Soft starter · limit 15% · Within limit ✓
Rated current
496.5 A
Starting current
1490 A
Starting kVA
980 kVA
Bus short-circuit
20.0 MVA
Starting calculation
QuantityValue
Motor rated current InP ÷ (√3·U·cosφ·η) = 250 kW ÷ (√3 × 380 V × 0.85 × 0.9) = 496.5 A
Starting current multiple3.0× (Soft starter)
Starting current Ist496.5 × 3.0 = 1490 A
Starting apparent power250 ÷ (0.9 × 0.85) × 3.0 = 980 kVA
Bus short-circuit capacity20 MVA (grid) = 20.0 MVA
Voltage dipSstart ÷ (Sstart + Ssc) = 4.7% vs limit 15%
Starting-method comparison
MethodkstVoltage dipVerdict
Direct-on-line (DOL)6.5×9.6%OK
Star-delta (Y-Δ)2.2×3.5%OK
Soft starter3.0×4.7%OK
VFD (variable speed)1.3×2.1%OK
Recommendation
Soft starter
Current method keeps the bus voltage dip within the limit.
Bill of materials
EquipmentSpecQtySubtotal
Soft starter cabinet250 kW · 380 V · Soft starter (3.0× In)1POA
Total equipmentPOA

How it was calculated

  • · Rated current: In = P ÷ (√3 · U · cosφ · η).
  • · Starting current: Ist = In × kst, where kst is the starting-current multiple (≈6.5× DOL, ≈2.2× star-delta, ≈3× soft, ≈1.3× VFD).
  • · Starting apparent power: Sstart = P ÷ (cosφ · η) × kst.
  • · Bus voltage dip: ΔU% = Sstart ÷ (Sstart + Ssc) × 100, where Ssc is the short-circuit capacity at the bus.
  • · Minimum supply/transformer to meet a limit L: S ≥ Sstart × (1 − L) ÷ L × uk.

Referenced standards

StandardScope
IEC 60034Rotating electrical machines — rating and performance
GB/T 755Rating and performance of rotating electrical machines
IEEE 3002.7-2018Motor starting analysis for power systems

Frequently asked questions

What is an acceptable voltage dip during motor starting?

Most standards (IEC 60034, GB/T 755) allow a 15-20% voltage dip during motor starting, with the bus voltage staying above 80-85%. A dip below 80% can stall the motor or trip contactors. The calculator computes the starting dip and flags if it exceeds the limit.

How much current does a motor draw on direct-on-line starting?

Direct-on-line (DOL) starting draws 5-7 times rated current for a few seconds. A 100 kW motor at 0.4 kV (~180 A rated) draws 900-1260 A on start. This inrush causes the voltage dip; the calculator computes the dip and compares DOL, star-delta, soft-start and VFD.

How much does a soft-starter reduce starting current?

A soft-starter ramps voltage and typically limits starting current to 2.5-3.5 times rated (versus 5-7x DOL), reducing the voltage dip proportionally. The starting torque also drops roughly with the square of current, so soft-start suits centrifugal loads. The calculator compares starting methods.

What supply transformer size do I need for a big motor?

The Transformer must supply the motor starting kVA without excessive dip. For a 160 kW motor starting at 3x on soft-start, starting demand is ~480 kVA; a 630 kVA transformer keeps the dip near 10-12%. The calculator sizes the supply from the starting demand and dip limit.

What is star-delta starting and when is it used?

Star-delta starting connects the motor in star for start (reducing voltage to 58% and current/torque to one-third) then switches to delta for run. It cuts starting current to ~2-2.5x rated but the torque drop limits it to light-starting loads like fans and pumps. The calculator compares it against DOL and soft-start.

Embed this calculator

Add this calculator to your own website for free. The iframe adapts to any width and runs entirely in your visitor's browser.

Related tools

Reference estimates (FOB Qingdao, EXW) for preliminary design only — not a final quote. Confirm sizing against your project and local standards.

Send my complete design report

Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.

💬 Chat on WhatsApp

Your data stays private. No spam — only a reply to your enquiry.