Load & Demand Calculation Calculator
Build a load schedule from connected loads and demand factors, then derive the calculated demand (kW/kVA), demand current and a recommended transformer rating.
Result
Enter your load → get a full design & BOM in seconds
Sample output| Load group | Connected kW | Demand factor | Demand kW |
|---|---|---|---|
| Lighting | 20.0 | 90% | 18.0 |
| HVAC / air conditioning | 40.0 | 80% | 32.0 |
| Motors & pumps | 60.0 | 70% | 42.0 |
| Sockets / general purpose | 15.0 | 40% | 6.0 |
| Other / special loads | 10.0 | 60% | 6.0 |
| Subtotal (diversified) | 145.0 | 104.0 | |
| Demand load (× Ks 0.8) | 83.2 kW |
| Demand kVA | 83.2 kW ÷ 0.85 = 97.9 kVA |
| Demand current | 97.9 kVA ÷ (√3 × 0.4 kV) = 141 A |
| Recommended transformer | 97.9 kVA ÷ 0.8 = 122 kVA → 160 kVA (load factor 61%) |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Distribution transformer (S13 oil-immersed) | 160 kVA · 10/0.4 kV · Dyn11 | 1 | POA |
| Low-voltage switchgear (GCK/GCS) | 98 kVA demand · 141 A | 1 | POA |
| Total equipment (transformer) | POA |
For electrical designers and consultants doing the first step of any distribution design — feeder, switchgear and transformer sizing from a load schedule.
Use the calculator
Worked example
A pre-computed reference example (crawlable — no JavaScript required). Enter your own parameters above for a live result.
Example 1 — office & light-industrial load schedule
| Load group | Connected kW | Demand factor | Demand kW |
|---|---|---|---|
| Lighting | 20.0 | 90% | 18.0 |
| HVAC / air conditioning | 40.0 | 80% | 32.0 |
| Motors & pumps | 60.0 | 70% | 42.0 |
| Sockets / general purpose | 15.0 | 40% | 6.0 |
| Other / special loads | 10.0 | 60% | 6.0 |
| Subtotal (diversified) | 145.0 | 104.0 | |
| Demand load (× Ks 0.8) | 83.2 kW |
| Demand kVA | 83.2 kW ÷ 0.85 = 97.9 kVA |
| Demand current | 97.9 kVA ÷ (√3 × 0.4 kV) = 141 A |
| Recommended transformer | 97.9 kVA ÷ 0.8 = 122 kVA → 160 kVA (load factor 61%) |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Distribution transformer (S13 oil-immersed) | 160 kVA · 10/0.4 kV · Dyn11 | 1 | POA |
| Low-voltage switchgear (GCK/GCS) | 98 kVA demand · 141 A | 1 | POA |
| Total equipment (transformer) | POA |
Example 2 — commercial building with high HVAC share
| Load group | Connected kW | Demand factor | Demand kW |
|---|---|---|---|
| Lighting | 30.0 | 90% | 27.0 |
| HVAC / air conditioning | 120.0 | 85% | 102.0 |
| Motors & pumps | 40.0 | 60% | 24.0 |
| Sockets / general purpose | 25.0 | 50% | 12.5 |
| Other / special loads | 20.0 | 70% | 14.0 |
| Subtotal (diversified) | 235.0 | 179.5 | |
| Demand load (× Ks 0.75) | 134.6 kW |
| Demand kVA | 134.6 kW ÷ 0.9 = 149.6 kVA |
| Demand current | 149.6 kVA ÷ (√3 × 0.4 kV) = 216 A |
| Recommended transformer | 149.6 kVA ÷ 0.8 = 187 kVA → 200 kVA (load factor 75%) |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Distribution transformer (S13 oil-immersed) | 200 kVA · 10/0.4 kV · Dyn11 | 1 | POA |
| Low-voltage switchgear (GCK/GCS) | 150 kVA demand · 216 A | 1 | POA |
| Total equipment (transformer) | POA |
How it was calculated
- · Connected load: P_conn = Σ P_i.
- · Diversified demand: P_d = Σ (P_i × Kd_i).
- · Calculated demand: P = P_d × Ks (simultaneity factor).
- · Demand apparent power: S = P ÷ PF; demand current: I = P ÷ (√3 · U).
- · Recommended transformer: S_tr = S ÷ target load factor (0.8), rounded up to a standard size.
Referenced standards
| Standard | Scope |
|---|---|
| IEC 60364 | Low-voltage electrical installations |
| IEEE 241 | Recommended practice for electric power systems in commercial buildings (Gray Book) |
| GB 50054 | Code for design of low-voltage electrical installations |
Frequently asked questions
What is the difference between connected load and demand load?
Connected load is the sum of all equipment nameplate ratings; demand load is the maximum power actually drawn simultaneously, equal to connected load x demand factor. A 500 kW connected load at 0.7 demand factor has a 350 kW demand. Transformers are sized to demand, not connected load. The calculator computes demand from connected load.
What demand factor should I use for different building types?
Typical demand factors: residential 0.3-0.5, commercial/office 0.4-0.6, industrial 0.6-0.8, continuous process 0.8-0.9. A hospital runs 0.7-0.8. Using the right factor prevents a 30-50% Transformer oversize. The calculator provides guidance and computes the recommended kVA.
How do I convert demand kW to transformer kVA?
kVA = demand kW / Power Factor. A 350 kW demand at 0.9 pf needs 389 kVA, so select 400 kVA. If power factor is uncorrected at 0.75, the same load needs 467 kVA — power factor correction shrinks the transformer. The calculator applies pf and selects the standard rating.
What is the NEC vs IEC demand factor difference?
NEC Article 220 gives table-based demand factors per appliance/load type; IEC/GB practice uses engineering judgment and experience factors per building type. Both aim to avoid oversizing. The calculator uses engineering demand factors aligned with GB 50052 and IEC practice.
How do I account for future growth in load demand?
Add 15-25% to the present demand for growth, then select the next standard transformer rating. If present demand is 350 kVA, plan for ~440 kVA and select 500 kVA (or 2x250 kVA). The calculator's margin guidance keeps the transformer loadable at 70-80% after growth.
Embed this calculator
Add this calculator to your own website for free. The iframe adapts to any width and runs entirely in your visitor's browser.
Related tools
Results are engineering estimates for preliminary design and reference only. Always verify with the applicable standards, the equipment nameplate and a licensed engineer before procurement or installation.
Send my complete design report
Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.
Your data stays private. No spam — only a reply to your enquiry.