🔗 PV Cable Voltage-Drop Calculator
Check the DC-side voltage drop and line loss of a PV string, verify cable ampacity (1.25 × Isc) and pick the minimum section that stays under the 2% drop guideline.
🔗 String & Cable
📊 Voltage-Drop Result
For solar installers sizing DC home-run cables and connectors.
How it is calculated
· Two-way resistance: R = 2 × ρ × L ÷ A (ρ copper 0.0175 Ω·mm²/m).
· Voltage drop: VD = I × R; VD% = VD ÷ V_string × 100.
· Ampacity check: required ≥ I × 1.25; connector (MC4) rating ≥ I × 1.25.
Referenced standards
| Standard | Scope |
|---|---|
| IEC 60364 | Low-voltage electrical installations (cable ampacity) |
| NEC 690 | Solar photovoltaic systems (conductor ampacity 1.25 × Isc) |
Worked example — 13 A over 50 m → 1.42% at 4 mm²
1. String current 13 A, distance 50 m, 4 mm², string voltage 400 V.
2. R = 2 × 0.0175 × 50 ÷ 4 = 0.44 Ω; VD = 13 × 0.44 = 5.7 V = 1.42%.
3. Ampacity: 13 × 1.25 = 16.3 A ≤ 32 A (4 mm²) OK.
4. 1.42% is within the 2% guideline — 4 mm² is sufficient.
FAQ
What voltage drop is acceptable in a PV DC cable?
Design practice limits total DC-side voltage drop to about 2% (IEC 60364 and common PV guidelines), split roughly 1% in the string cabling and 1% in the DC run to the inverter. Higher drop means lost energy — every 1% of drop is roughly 1% of lost annual yield. The calculator checks the drop and recommends the minimum cross-section.
How do I size a PV cable for ampacity?
PV DC cables must carry the string short-circuit current with a safety factor (usually 1.25x Isc, and 1.56x per NEC). For a 550 W module with Isc ~13.9 A and a two-parallel-string combiner, the combined current is ~35 A, so a 6 mm2 copper cable (rated ~40-45 A) is typical. The calculator verifies ampacity and derating.
Copper or aluminum for PV DC cabling?
PV string and DC cables are almost always copper because DC circuits are low-voltage and ampacity-sensitive; aluminium would need a much larger cross-section for the same drop. Copper is also easier to terminate on MC4 connectors. Aluminium appears only in long AC medium-voltage collector runs. The calculator defaults to copper for DC.
How long can a PV DC cable run be?
DC run length is limited by the 2% voltage-drop budget. For a 10 kW string at 500 V DC and 20 A, a 4 mm2 copper cable can run roughly 40-60 m before exceeding 2%. Longer runs need 6-10 mm2 cable or a higher system voltage. The calculator computes the maximum length for a given cross-section.
What DC cable type is used for solar arrays?
PV arrays use double-insulated, UV-resistant solar cable (H1Z2Z2-K / EN 50618, rated 1.5 kV DC and -40 to +90 deg C) for outdoor runs. Single-core copper, usually 4-6 mm2 for strings and 10-35 mm2 for DC mains. The calculator selects cable by ampacity and drop and cites the applicable standard.
Embed this calculator
Add this calculator to your own website for free. The iframe adapts to any width and runs entirely in your visitor's browser.