UPS Sizing & Battery Runtime Calculator
Size an uninterruptible power supply and its battery bank from the load, power factor and required autonomy — and see the actual runtime the installed battery delivers.
Result
Enter your load → get a full design & BOM in seconds
Sample output| Step | Value |
|---|---|
| Load apparent power | S = P ÷ PF = 50 kW ÷ 0.8 = 62.5 kVA |
| Required UPS (loading factor) | 62.5 ÷ 0.8 = 78.1 kVA → standard 80 kVA |
| Battery energy | E = P·t ÷ (ηinv·ηbat·DOD) = 50 kW × 0.50 h ÷ (0.94 × 0.9 × 0.5) = 59.10 kWh |
| Total battery capacity | 59.10 kWh ÷ 384 V = 154 Ah |
| Series blocks per string | 384 V ÷ 12 V = 32 |
| Parallel strings | 154 Ah ÷ 200 Ah = 1 |
| String voltage | 32 × 12 V = 384 V |
| Installed capacity | 1 × 200 Ah = 200 Ah |
| Actual runtime | (200 Ah × 384 V × 0.94 × 0.9 × 0.5) ÷ 50 kW = 39 min |
| Estimated recharge | 200 Ah ÷ 20 A (0.1C) × 1.1 ≈ 11.0 h |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Online double-conversion UPS | 80 kVA / 72 kW · 384 V DC bus | 1 | POA |
| VRLA lead-acid (12 V block) battery bank | 32S×1P (32 blocks, 200 Ah @ 384 V) | 1 | POA |
| Battery charger / rectifier | 20 A charging current | 1 | POA |
| Total equipment (UPS + charger) | POA |
For facility managers, data-center designers and electrical engineers sizing single- or three-phase UPS systems with VRLA or LiFePO₄ battery banks.
Use the calculator
Worked example
A pre-computed reference example (crawlable — no JavaScript required). Enter your own parameters above for a live result.
Example 1 — 50 kW data-center load, 30 minutes autonomy
| Step | Value |
|---|---|
| Load apparent power | S = P ÷ PF = 50 kW ÷ 0.8 = 62.5 kVA |
| Required UPS (loading factor) | 62.5 ÷ 0.8 = 78.1 kVA → standard 80 kVA |
| Battery energy | E = P·t ÷ (ηinv·ηbat·DOD) = 50 kW × 0.50 h ÷ (0.94 × 0.9 × 0.5) = 59.10 kWh |
| Total battery capacity | 59.10 kWh ÷ 384 V = 154 Ah |
| Series blocks per string | 384 V ÷ 12 V = 32 |
| Parallel strings | 154 Ah ÷ 200 Ah = 1 |
| String voltage | 32 × 12 V = 384 V |
| Installed capacity | 1 × 200 Ah = 200 Ah |
| Actual runtime | (200 Ah × 384 V × 0.94 × 0.9 × 0.5) ÷ 50 kW = 39 min |
| Estimated recharge | 200 Ah ÷ 20 A (0.1C) × 1.1 ≈ 11.0 h |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Online double-conversion UPS | 80 kVA / 72 kW · 384 V DC bus | 1 | POA |
| VRLA lead-acid (12 V block) battery bank | 32S×1P (32 blocks, 200 Ah @ 384 V) | 1 | POA |
| Battery charger / rectifier | 20 A charging current | 1 | POA |
| Total equipment (UPS + charger) | POA |
Example 2 — 120 kW load, 60 minutes, lithium battery
| Step | Value |
|---|---|
| Load apparent power | S = P ÷ PF = 120 kW ÷ 0.9 = 133.3 kVA |
| Required UPS (loading factor) | 133.3 ÷ 0.8 = 166.7 kVA → standard 200 kVA |
| Battery energy | E = P·t ÷ (ηinv·ηbat·DOD) = 120 kW × 1.00 h ÷ (0.94 × 0.95 × 0.9) = 149.31 kWh |
| Total battery capacity | 149.31 kWh ÷ 480 V = 311 Ah |
| Series blocks per string | 480 V ÷ 48 V = 10 |
| Parallel strings | 311 Ah ÷ 350 Ah = 1 |
| String voltage | 10 × 48 V = 480 V |
| Installed capacity | 1 × 350 Ah = 350 Ah |
| Actual runtime | (350 Ah × 480 V × 0.94 × 0.95 × 0.9) ÷ 120 kW = 68 min |
| Estimated recharge | 350 Ah ÷ 35 A (0.1C) × 1.1 ≈ 11.0 h |
| Equipment | Spec | Qty | Subtotal |
|---|---|---|---|
| Online double-conversion UPS | 200 kVA / 180 kW · 480 V DC bus | 1 | POA |
| LiFePO₄ lithium (48 V module) battery bank | 10S×1P (10 blocks, 350 Ah @ 480 V) | 1 | POA |
| Battery charger / rectifier | 35 A charging current | 1 | POA |
| Total equipment (UPS + charger) | POA |
How it was calculated
- · Load apparent power: S = P ÷ PF.
- · Required UPS rating: S_UPS = S ÷ loading factor (typical 0.8), rounded up to a standard size.
- · Battery energy: E = P · t ÷ (η_inv · η_bat · DOD).
- · Battery capacity: Ah = E ÷ V_dc; series blocks = V_dc ÷ V_block; parallel strings = required Ah ÷ block Ah.
- · Actual runtime: t = (installed Ah · V_dc · η_inv · η_bat · DOD) ÷ P.
Referenced standards
| Standard | Scope |
|---|---|
| IEC 62040-3 | Uninterruptible power systems — method of specifying performance and test requirements |
| IEEE 1184 | Guide for batteries for uninterruptible power supply systems |
| IEEE 485 | Recommended practice for sizing lead-acid batteries for stationary applications |
Frequently asked questions
How do I size a UPS for my load?
UPS kVA = load kW / Power Factor, plus 20-30% margin and future growth. A 40 kW IT load at 0.9 pf needs ~44 kVA, so select 60 kVA. Add margin for inrush and non-linear loads. The calculator sizes UPS kVA, battery Ah and runtime.
How is UPS battery runtime calculated?
Runtime depends on battery capacity (Ah), string voltage, load and efficiency. For a 40 kW load on a 240 V battery string, a 100 Ah bank gives roughly 20-30 minutes. The calculator computes actual runtime from battery blocks, DoD and load, and reports recharge time.
What is the difference between online and line-interactive UPS?
Online (double-conversion) UPS continuously rectifies and inverts, giving zero transfer time and full power conditioning — required for data centers. Line-interactive passes utility power and corrects only on events, cheaper but with a brief transfer. The calculator's sizing assumes online double-conversion for critical loads.
What battery type is used in UPS systems?
Valve-regulated lead-acid (VRLA) dominates UPS for low cost and maintenance-free operation, with a 3-5 year typical life. Lithium (LFP) is gaining share for longer life (10+ years), smaller footprint and higher cycle count, at 2-3x the upfront cost. The calculator sizes the battery bank for either chemistry.
How much runtime do I need before the generator starts?
Battery runtime must bridge to generator start, typically 5-15 minutes (generators reach full load in 30-60 s). Without a generator, size for 30-60 minutes for graceful shutdown. Longer runtime adds cost roughly linearly. The calculator lets you set runtime and sizes the battery accordingly.
Embed this calculator
Add this calculator to your own website for free. The iframe adapts to any width and runs entirely in your visitor's browser.
Related tools
Results are engineering estimates for preliminary design and reference only. Always verify with the applicable standards, the equipment nameplate and a licensed engineer before procurement or installation.
Send my complete design report
Get the full bill of materials, single-line diagram, calculation steps and FOB pricing as a PDF — free, no sign-up.
Your data stays private. No spam — only a reply to your enquiry.