SC-50/10/0.4

SC Series50 kVA • 10/0.4 kV

Product Image & Parameters

50kVASC

SC-50/10/0.4

SC Series

Capacity
50kVA
HV Voltage
10kV
LV Voltage
0.4kV
Efficiency
2Level
Amorphous Alloy CoreEnergy SavingLow Loss

TECHNICAL DRAWING

Model: SC-50/10/0.4 | Type: Dry-Type Transformer | Capacity: 50 kVA

FRONT VIEW

HVLV1U1V1W2U2V2W2N120mm150mm

SIDE VIEW

Ventilation90mm

TOP VIEW

1U1V1W2U2V2W2N120mm90mm

TERMINAL BLOCK

HV TERMINAL BLOCK1U1V1W1N1PELV TERMINAL BLOCK2U2V2W2N2PE2122Terminal Block ConfigurationTin-Plated Copper Busbar

ELECTRIC SCHEMATIC DIAGRAM

HV WINDING (Delta)1U1V1WLV WINDING (Star)2U2V2W2NVector GroupDyn11 (IEC)

SPECIFICATIONS

1. Model:SC-50/10/0.4
2. Type:Dry-Type Transformer
3. Capacity:50 kVA
4. Frequency:50 Hz
5. HV Voltage:10 kV
6. LV Voltage:0.4 kV
7. HV Current:2.89A
8. LV Current:72.17A
9. Vector Group:Dyn11 (IEC)
10. Impedance:4%
11. Insulation Level:H (180°C)
12. Temperature Rise:65K
13. No-Load Loss:2387W
14. Load Loss:5968W
15. No-Load Current:1.5%
16. Cooling Method:AN
17. Tap Changer:±5% 单档
18. Standard:IEC 60076
19. Dimensions:800×600×1000mm
20. Weight:-
LEGEND:
Iron Core
HV Winding/Bushing
LV Winding/Bushing
Dimension Line

Product Description

50kVA, 3-phase isolation, dry-type transformer, 50Hz, primary 10kV (HV 10kV), secondary 400V (LV 400V), Standard, insulation H, impedance 4%

Related Keywords

SC-50/10/0.4 isolation control transformer50kVA control transformerprimary 10kV secondary 0.4kVSC series 3-phase isolation transformer for solar power system

SC-50/10/0.4 FAQ

What are the main application scenarios for SC-50/10/0.4?
The SC-50/10/0.4 (SC series special/isolation/control transformers) with rated capacity of 50 kVA, HV side 10 kV, LV side 0.4 kV, is widely used in industrial distribution, commercial buildings, and power systems. It can be flexibly configured according to actual project requirements.
What are the technical specifications of SC-50/10/0.4?
Key specs: Capacity 50 kVA, HV 10 kV, LV 0.4 kV, Frequency 50 Hz, Impedance 4%, Vector Group Dyn11 (IEC), Cooling AN, Standard IEC 60076.
Can SC-50/10/0.4 be customized?
Yes. QDTB® offers comprehensive OEM/ODM customization. Parameters such as capacity, voltage ratio, cooling method, vector group, and protection class can be adjusted. 23+ years of manufacturing experience ensures consistent quality.
How to get a quote and technical documentation?
Contact us via the "Send Inquiry" button below, or reach our sales team at Alice@qdtb-transformer.com / +86 13698683193. We will provide detailed quotations and technical documentation within 24 hours.

Interested in SC-50/10/0.4?