Transformer Model Number Decoder
Paste a transformer model number — such as S13-M-1000/10 or SCB13-1250/10/0.4 Dyn11 — and decode its type, loss level, capacity, voltage and connection group.
Result
Enter your load → get a full design & BOM in seconds
Sample output| Parameter | Value |
|---|---|
| Type | Three-phase oil-immersed transformer (fully sealed) |
| Phases | Three-phase |
| Efficiency level | Loss level 13 (S13/SCB13 — grade 3, high efficiency) |
| Rated capacity | 1000 kVA |
| HV winding voltage | 10 kV |
| Winding material | Copper (default — confirm on nameplate) |
| Tap changer | Off-circuit / no-load tap changer |
For procurement engineers, specifiers and technicians who need to read the meaning encoded in Chinese and IEC transformer model designations.
Use the calculator
Worked example
A pre-computed reference example (crawlable — no JavaScript required). Enter your own parameters above for a live result.
Example 1 — S13-M-1000/10 (oil-immersed, grade 2)
| Parameter | Value |
|---|---|
| Type | Three-phase oil-immersed transformer (fully sealed) |
| Phases | Three-phase |
| Efficiency level | Loss level 13 (S13/SCB13 — grade 3, high efficiency) |
| Rated capacity | 1000 kVA |
| HV winding voltage | 10 kV |
| Winding material | Copper (default — confirm on nameplate) |
| Tap changer | Off-circuit / no-load tap changer |
Example 2 — SCB13-1250/10/0.4 Dyn11 (dry-type)
| Parameter | Value |
|---|---|
| Type | Three-phase cast-resin dry-type transformer |
| Phases | Three-phase |
| Efficiency level | Loss level 13 (S13/SCB13 — grade 3, high efficiency) |
| Rated capacity | 1250 kVA |
| HV winding voltage | 10 kV |
| LV winding voltage | 0.4 kV |
| Connection group | Dyn11 (delta HV / star LV, LV neutral, 30° lag) — standard distribution |
| Winding material | Copper (default — confirm on nameplate) |
| Tap changer | Off-circuit / no-load tap changer |
How it was calculated
- · Prefix letter: S = three-phase oil-immersed, D = single-phase, SCB/SG = dry-type (cast-resin / air).
- · Loss-level digit: 9/10/11/13/15/18/20/22 = efficiency grade (higher = lower loss).
- · Suffix letters: M = fully sealed, Z = on-load tap changer, L = aluminium winding.
- · Numbers: capacity/HV[/LV] in kVA and kV.
- · Trailing group: Dyn11, Yyn0, YNd11, etc.
Referenced standards
| Standard | Scope |
|---|---|
| GB/T 6451 | Technical parameters and requirements for oil-immersed power transformers |
| JB/T 3837 | Method for compilation of transformer product model designations |
| GB/T 10228 | Technical parameters and requirements for dry-type power transformers |
Frequently asked questions
What does S13-M-500/10 mean in a transformer model?
S = three-phase oil-immersed, 13 = loss/efficiency grade, M = sealed (full-sealed) construction, 500 = capacity in kVA, 10 = HV voltage in kV. So it is a 500 kVA, 10 kV sealed oil-immersed S13 Transformer. The calculator decodes the full model string.
What does SCB13-1000/10 mean?
SCB = three-phase dry-type cast-resin, 13 = loss grade, 1000 = capacity in kVA, 10 = HV voltage in kV. The 'B' denotes foil/band Winding. It is a 1000 kVA, 10 kV cast-resin Dry-Type Transformer. The calculator decodes SCB, SC, SG and other prefixes.
How do I read a transformer connection group like Dyn11?
Dyn11 = HV delta (D), LV wye/star (y) with neutral (n), and an 11 o'clock phase shift meaning LV lags HV by 30 deg (11 x 30 = 330 deg lead). Yyn0 = star/star with neutral and 0 deg shift. The calculator explains the Vector Group in the decoded result.
What do the letters S9, S11, S13, S20, S22 mean?
These are Chinese oil-immersed transformer series by loss level: S9 is the legacy standard, S11 and S13 reduce no-load loss ~20-30% step by step, and S20/S22 meet the current GB 20052 grade-1/2 efficiency. Higher numbers = lower losses and higher price. The calculator maps the series to its efficiency grade.
Why do I need to decode a transformer model number?
The model number encodes type, cooling, capacity, voltage and loss grade in a compact string, so decoding it lets you verify a quote, compare tenders, or match a replacement. Misreading a digit can lead to a wrong-voltage or wrong-capacity purchase. The calculator decodes the string into plain fields.
Embed this calculator
Add this calculator to your own website for free. The iframe adapts to any width and runs entirely in your visitor's browser.
Related tools
Results are engineering estimates for preliminary design and reference only. Always verify with the applicable standards, the equipment nameplate and a licensed engineer before procurement or installation.