The answer first: fault current = rated current ÷ impedance voltage
The short-circuit current at the LV terminals of a distribution transformer is not something you look up in a curve — it is a one-line division. The symmetrical (steady-state) short-circuit current is:
Isc = In ÷ Uk% = (S ÷ (√3 × U)) ÷ (Uk ÷ 100)
where S is the rated power (kVA), U the rated LV voltage (kV), and Uk% the impedance (short-circuit) voltage. Take a 1,000 kVA, 10 ÷ 0.4 kV transformer with Uk = 6%: the rated LV current is 1,000,000 ÷ (1.732 × 400) = 1,443 A, so the fault current is 1,443 ÷ 0.06 = 24.1 kA. The first-cycle asymmetric peak is roughly 2.55 × that = 61 kA. Every LV main breaker, busbar and cable must be rated to interrupt and carry that number — which is why you calculate it before you buy, not after. If you are still choosing the kVA itself, start from the one-formula sizing guide; for the switchgear and feeders that must handle this fault, see How to Size a Distribution System.
Step 1 — Find the rated current
Rated (full-load) current on any winding is power divided by √3 and voltage. On the LV side of a 10/0.4 kV unit:
In = S ÷ (1.732 × 0.4)
| Rating (kVA) | LV rated current at 0.4 kV (A) |
|---|---|
| 400 | 577 |
| 630 | 909 |
| 800 | 1,155 |
| 1,000 | 1,443 |
| 1,250 | 1,804 |
| 1,600 | 2,309 |
| 2,000 | 2,887 |
Step 2 — Divide by Uk% (the impedance voltage)
Uk% is the voltage — as a percentage of rated — you must apply to the HV winding to circulate rated current with the LV terminals shorted. It is the transformer’s internal impedance, and it is the single lever that sets fault current. For standard distribution transformers it is typically 4%–6% (as of 2026):
| Uk% | Fault multiplier (1 ÷ Uk) | 1,000 kVA → LV fault (kA) |
|---|---|---|
| 4% | 25 × In | 36.1 |
| 5% | 20 × In | 28.9 |
| 6% | 16.7 × In | 24.1 |
| 8% | 12.5 × In | 18.0 |
A lower Uk% means lower losses and tighter voltage regulation, but a higher fault current — so your LV switchgear gets more expensive. This is the same impedance-versus-loss trade-off that drives the S11/S13/S20 grades; see the loss-grade comparison for how impedance and no-load loss move together.
Step 3 — Add the asymmetric peak
The 24.1 kA above is the symmetrical RMS value. During the first half-cycle a DC offset can push the instantaneous peak to about 2.55 × the symmetrical value (IEC 60909 / IEC 60076-5 apply this factor for distribution transformers). For the 1,000 kVA / 6% unit the peak is ≈ 61 kA. Breakers and busbars are specified for both the RMS interrupting rating and the peak (making) current, so specify both on the order.
The withstand rule: IEC 60076-5 (GB 1094.5)
IEC 60076-5 requires a transformer to withstand the thermal and dynamic (mechanical) effects of an external short circuit without damage, for a duration of 2 seconds by default (some specifications extend this to 3 s for larger units). The two failure modes are distinct: thermal — the copper heats toward a defined limit under the fault current — and dynamic — the electromagnetic forces between windings, which rise with the square of peak current, physically crush or distort the winding. That square law is why a low Uk% is a double-edged sword: it raises fault current, and force rises with I², so the mechanical design margin matters more than the thermal one. This is exactly what a competent factory verifies with a routine short-circuit withstand test — or, for critical units, a full type test.
How to specify it (and what to put on the order)
- Rated power, voltage ratio and vector group (e.g. 1,000 kVA, 10/0.4 kV, Dyn11).
- Uk% at the rated tap (e.g. 6%) and the tolerance you accept — IEC 60076-1 allows ±10% on the stated impedance.
- Short-circuit duration (2 s standard) and the system’s prospective fault level at the HV terminals.
- That the LV switchgear must interrupt the calculated Isc — typically a 36 kA or 50 kA LV breaker, depending on Uk%.
Get Uk% and the fault level wrong and you either under-spec the switchgear (a breaker that cannot interrupt 24 kA is a hazard) or over-pay for a low impedance you do not need. Send us your rating and the prospective HV fault level and we will calculate the exact LV fault current, pick a Uk% that balances regulation against switchgear cost, and quote matched units — oil-immersed or dry-type — with the IEC 60076-5 short-circuit withstand test report.
Worked table: LV fault current for common sizes (10/0.4 kV, Uk = 6%)
| Rating (kVA) | LV rated current (A) | Symmetrical Isc (kA) | Peak ≈ 2.55 × (kA) |
|---|---|---|---|
| 400 | 577 | 9.6 | 24.5 |
| 630 | 909 | 15.2 | 38.6 |
| 800 | 1,155 | 19.3 | 49.1 |
| 1,000 | 1,443 | 24.1 | 61.3 |
| 1,600 | 2,309 | 38.5 | 98.1 |
| 2,000 | 2,887 | 48.1 | 122.7 |
All values above assume a solid three-phase bolted fault at the LV terminals; real-world fault levels are slightly lower once cable impedance is added. The table is your specification check — if your LV gear cannot clear the number in the third column, raise Uk% or upgrade the switchgear before energizing.