QDTB® Transformer
All figures are configurator-generated feasibility-level estimates; drawings are schematic deliverables pending refinement by a licensed design institute, not construction documents.
All Solutions

2000 kW PV+BESS+Diesel Microgrid: Grid-Tied/Islanding Transfer & Black-Start Deep-Read

PV 800 kWp · BESS 600 kW/1355 kWh · Diesel 500 kW · 2×S13-2000/10 N+1 · on/off-grid + black start

1 · TL;DR Conclusion

Conclusion: this 2000 kW PV+diesel+BESS microgrid combines 800 kWp PV + 600 kW/1355 kWh BESS + 500 kW diesel + a 10 kV grid feed with grid-tied/islanding transfer and diesel black-start, on 2×S13-2000/10 transformers (N+1) — configurator total ≈ $803,022, EPC ≈ $770,000, 5-yr payback, 24.57% IRR, 487.3 t CO2/yr avoided (feasibility-level).

  • •Four-source mix: 800 kWp PV (50% share) + 600 kW BESS (38%) + 500 kW diesel (13%), 3900 kW installed
  • •Grid-tied/islanding transfer + black-start (500 kW diesel auto-start, blackStartCheck verified)
  • •BESS 600 kW×4 h shaving saves ≈$113,880/yr (vs pure-diesel $245,280/yr)
  • •Economics: $770,000 EPC, 5-yr payback, 24.57% IRR, 492% 25-yr ROI, LCOE $0.0983/kWh
  • •N-1 redundancy passes: 2×2000 kVA at 84% loading after one unit trips; ≈487.3 t CO2/yr avoided

2 · Solution Overview

A PV+diesel+BESS microgrid integrates PV, storage, diesel generation and the grid into one self-healing microgrid that can transfer between grid-tied and islanded modes — built for mines, islands and remote base stations on weak or no grid. This 2000 kW design lets PV serve base load, BESS smooth fluctuation and shave peaks, and diesel provide black-start plus island backup, with renewable-first dispatch when grid-tied.

2×2000 kVA (S13-M-2000/10)
Transformer
800 kWp
PV
600 kW / 1355 kWh
BESS
500 kW prime · black-start
Diesel
10 kV
Grid
Grid-tie/island + black-start
Mode
1600 kW (2000 kW load)
Demand
Pass (2×2000 kVA)
N-1
SourceRoleShare kWShare
Grid 10 kVbase0 kW0%
Solar PV 800 kWpvariable800 kW50%
BESS 600 kW / 1200 kWhvariable600 kW38%
Diesel 500 kWbase200 kW13%

3 · Design Process & Rationale

1. Requirement identification

Mines/islands/base stations face weak or frequently-out grid supply, yet carry 800 kW of critical load that cannot drop. The design locks in islanding + black-start as hard requirements — which mandates diesel and BESS, not grid-tied PV alone.

2. Load grading & demand

2000 kW total → 1600 kW demand after demand factor; 800 kW critical, 1355 kW grade-2, 300 kW impact load (crusher/hoist) — the basis for sizing diesel and storage.

3. Source mix

800 kWp PV (daytime base) + 600 kW/1355 kWh BESS (2 h, fluctuation-smoothing + shaving) + 500 kW diesel (black-start + island backup) + 10 kV grid (main supply when tied), dispatched under one EMS.

4. Transformer sizing

1600 kW → ≈1684 kVA, so 2000 kVA tier with N+1 redundancy (redundancy=n1, 2 units) — a microgrid must survive one-unit trips and island heavy-load, so redundancy keeps critical load powered.

5. Transfer & black-start

gridMode=grid-tie-island + blackStart=yes: on grid loss the ATS transfers within 2 s, the diesel auto-starts for black-start (verified: 500 kW diesel can carry it). Anti-islanding prevents backfeed while islanded.

6. Distribution & protection

MV incomer → 2 transformers → MNS LV switchgear (with bus-tie) → feeders. LV fault 58.91 kA vs 80 kA breaking capacity; protection selectivity ratio 18.1×, grading satisfied.

7. Power quality & reactive

Impact load causes flicker and harmonics (THDi ≈20%); add SVG ±1 Mvar dynamic compensation + detuned reactors, and coordinate diesel with storage converters to avoid circulating current.

8. Economics check

BESS shaves 600 kW×4 h at a $0.13/kWh spread, saving ≈$113,880/yr; PV generates 812,160 kWh/yr. Overall 5-yr payback, 24.57% IRR, LCOE $0.0983/kWh.

Pain Points → Solution → Evidence

Pain

A grid outage halts production (800 kW critical load can't drop)

Solution

Grid-tied/islanding transfer + diesel black-start: ATS transfers in 2 s, diesel auto-starts for critical load

Evidence

blackStartCheck verified (500 kW diesel) + N-1 pass (2×2000 kVA, 84% loading after a trip)

Pain

Diesel is expensive — $245k/yr fuel is unsustainable

Solution

PV+BESS shaving: 600 kW×4 h cuts diesel hours to a minimum

Evidence

economic.shaving: ≈$113,880/yr saved; pure-diesel $245,280 vs hybrid $174,300/yr

Pain

Backfeed / PV disconnection risk when islanded

Solution

Anti-islanding protection (81U/81O) + EMS source coordination

Evidence

microgrid drawing: PCC anti-islanding + transfer logic; compliance pass (no failures)

Pain

When does it pay back?

Solution

≈$770,000 EPC; PV+BESS save ≈$201,593/yr

Evidence

economic: 5-yr payback, 24.57% IRR, 492% 25-yr ROI, NPV $1,213,967

4 · Key Parameter Deep-Read

ParameterValueBasisImpact & Boundary
Transformer capacity2×2000 kVA (N+1)1600 kW → 1684 kVA → 2000 kVA tier + one spare84% loading; stays 84% after one unit trips (N-1 pass)
Step to 2500 kVA for growth or stricter redundancy
PV capacity800 kWp50% share; 812,160 kWh/yr generationServes base load in daytime, cutting diesel run-hours
Limited by site area and BESS absorption; more PV needs more storage
BESS capacity600 kW / 1355 kWh (2 h)Fluctuation-smoothing + shaving, 2 h durationShaves 600 kW×4 h, saving $113,880/yr
Island backup needs ≥8 h plus a black-start source
Diesel capacity500 kW prime · black-startCovers part of the 800 kW critical load + black-start (verified)The only reliable source for island backup and black-start
prime duty = continuous-rating, pricier than standby
Grid modegrid-tie-island + black-startWeak/no-grid sites must be able to island2 s ATS transfer; anti-islanding prevents backfeed
Grid approval per local grid code (gridCodeNote)
Reactive compensationSVG ±1 Mvar dynamic300 kW impact load causes flicker and reactive swingsStabilizes bus voltage and suppresses flicker
Add APF when THDi ~20% exceeds limits
EconomicsIRR 24.57% · 5 yr$770,000 EPC + $201,593/yr saving + 25-yr cashflowThe core investability metric
Diesel price, irradiation and load factor are the key sensitivities

5 · Drawing Deep-Read

Dwg 3/31Single-line diagram — 10 kV grid + 800 kWp PV + 600 kW/1355 kWh BESS + 500 kW diesel → 2×2000 kVA transformer → LV bus → feeders
Why: The SLD's job is showing how four sources connect: grid via MV incomer, PV via hybrid inverter, BESS via bidirectional PCS, diesel via ATS into the bus — the physical locus of the transfer and mix design.
Dwg 20/31Grid-tied / islanding transfer — PCC · ATS 2 s transfer · anti-islanding 81U/81O+32R
Why: This is the soul of the scheme: grid loss → ATS transfer → diesel black-start → critical load stays up. The transfer chain (IEC 62898 / IEEE 1547) structurally dissolves the 'grid outage halts production' pain.
Dwg 4/31System topology — Grid · PV (50%) · BESS (38%) · Diesel (13%) → transformer → distribution → load
Why: The topology lays out the energy hierarchy: four sources → MV bus → 2 transformers → LV bus → load, making dispatch visible — PV-first when tied, diesel+BESS backup when islanded.
Dwg 27/31Diesel + storage peak-shaving single-line — 600 kW/1355 kWh BESS via PCS to bus · 500 kW diesel via ATS · arbitrage/shaving
Why: This lands BESS+diesel as dispatch branches: BESS discharges at peak and charges at valley, diesel connects only when islanded or black-starting — the structural fix for 'diesel is expensive', saving ≈$113,880/yr.
Dwg 25/31Fuel oil system — DG-1000kVA container · day tank + 72 h storage · auto-start
Why: The last line of island reliability is the fuel system: 72 h autonomy sustains long islanding, and black-start depends on fast diesel auto-start — fuel-system redundancy is the precondition for a successful black-start.
Dwg 28/31Peak-shaving operation profile — 24h profile · PV daytime / BESS peak-valley / diesel backup
Why: This turns multi-source coordination into a 24h timeline: PV serves base by day, BESS discharges at peak and charges at valley, showing each source's share and the diesel fuel saved.

The following drawings are shown for reference (full set in the configurator “View design document”):

Dwg 1 · Electrical design basisDwg 5 · Distribution systemDwg 8 · Short-circuit calculationDwg 14 · Protection configurationDwg 15 · TCC coordination curveDwg 19 · Reactive & harmonic compensationDwg 16 · Grounding systemDwg 17 · Lightning & surge protectionDwg 24 · DC auxiliary powerDwg 29 · BMS communicationDwg 30 · Fire & thermal zoningDwg 31 · EMS state machineDwg 13 · SCADA architectureDwg 9 · Applicable standards

6 · Operation Demo (Deep-Read)

Energy flow

Grid-tied: PV 800 kW serves base first, surplus charges BESS; BESS discharges 600 kW at peak and charges at valley; grid fills the gap. Islanded: diesel 500 kW black-starts, then BESS+PV+diesel jointly feed the 800 kW critical load.

Grid failure / black-start

Press 'Grid failure': ATS transfers within 2 s, diesel auto-starts for black-start, critical load stays up; in the N-1 case one transformer trips and the other continues at 84% loading.

Economics

812,160 kWh/yr generated, 0.8 self-use + surplus export; PV self-use ≈$201,593/yr (incl. BESS shaving); $770,000 invested, 5-yr payback, 24.57% IRR, LCOE $0.0983/kWh.

24h operation

A typical-day curve: daytime PV overlaps load, peak-time BESS discharge shaves the peak, overnight valley charging, diesel only during islanding/black-start — the four-source coordination in time order.

Other views (shown): Power quality & harmonics · Voltage profile · Scheme features · Environmental derating

7 · Economics & Payback

Equipment total ≈ $803,022, EPC ≈ $770,000 (incl. PV/BESS/diesel/distribution/installation). PV self-use saves ≈$201,593/yr (incl. BESS shaving); overall 5-yr payback, 24.57% IRR, 492% 25-yr ROI, LCOE $0.0983/kWh, NPV $1,213,967, 487.3 t CO2 avoided/yr.

$770,000
EPC investment
5 yr
Payback
24.57%
IRR
492%
25-yr ROI
$0.0983/kWh
LCOE
487.3 t/yr
CO2 avoided
Key assumptions driving these numbers
$0.12/kWh
Electricity price
$0.06/kWh
Feed-in tariff
812160 kWh
Annual generation (P50)
80%
Self-consumption
$0.13/kWh
Peak-valley spread

8 · FAQ

How big a diesel in a PV+diesel+BESS microgrid?
This scheme uses 500 kW prime, covering part of the 800 kW critical load and doing black-start (verified: 500 kW can carry it). Sized as a DG-1000kVA continuous-rating set.
How big a BESS, and how is duration computed?
600 kW / 1355 kWh = 2 h (1355÷600). 2 h covers shaving and smoothing; long-duration islanding needs ≥8 h plus a black-start check.
How is black-start implemented?
Grid loss → ATS transfers in 2 s → diesel auto-starts for black-start → critical load stays up. Anti-islanding (81U/81O) prevents backfeed while islanded.
How does grid-tied/islanding transfer work?
gridMode=grid-tie-island: when tied the grid is the main supply and PV is prioritized; when islanded BESS+PV+diesel jointly feed. ATS transfer is 2 s.
When does it pay back?
≈$770,000 EPC; PV self-use + BESS shaving save ≈$201,593/yr; ~5-yr payback, 24.57% IRR.
Pure diesel vs PV+diesel+BESS hybrid?
Pure diesel ≈$245,280/yr vs hybrid ≈$174,300/yr — about $113,880/yr saved (600 kW×4 h shaving basis).
Will impact load collapse the bus?
300 kW impact load is handled by SVG ±1 Mvar dynamic compensation; protection selectivity 18.1× with grading satisfied.
Is N+1 transformer redundancy necessary?
A microgrid must survive single-unit trips and island heavy-load; 2×2000 kVA at 84% after a trip (N-1 pass) keeps critical load powered.
How much PV should be installed?
This scheme uses 800 kWp (50% share) for 812,160 kWh/yr. More PV needs more storage to absorb, else curtailment or backfeed.
What grid-connection paperwork is needed?
Grid approval + anti-islanding/anti-backfeed/PF (gridCodeNote); the transfer scheme must be approved per the local grid code.

Special Considerations

  • Grid-tied/islanding transfer needs grid approval plus anti-islanding/anti-backfeed (gridCodeNote TBC); assumed grid-tie-island here.
  • Diesel duty=prime is continuous-rating (DG-1000kVA), pricier than standby; switch to standby to cut cost if only for emergencies.
  • 2 h storage covers shaving/smoothing; long-duration islanding needs ≥8 h plus a black-start capacity check.
  • 300 kW impact load causes flicker; SVG ±1 Mvar dynamic compensation is included; add APF if THDi ~20% exceeds limits.
  • Feasibility-level estimate; drawings pending refinement by a licensed design institute.

Turn this into your project

Open this exact scenario pre-loaded in the Power System Configurator, then generate the full design document or the operation & techno-economic assessment.

Open in Power System Configurator →

One-Stop Supply of Conventional & Solar Power Equipment

From power distribution system design to solar energy — transformers, switchgear, substations and solar equipment, sized and quoted in one place. Use our calculators to get a complete bill of materials and FOB price.