600 kW / 630 kVA Port Terminal Power: 160 kW Quay Crane + SVG Dynamic Compensation Deep-Read
2×S13-M-630/10 N+1 · 160 kW crane VFD · SVG dynamic compensation
1 · TL;DR Conclusion
Conclusion: this 600 kW port terminal uses 2×S13-M-630/10 oil transformers (N+1) + a 160 kW quay-crane VFD + SVG dynamic reactive compensation — configurator total ≈ $156,706, 80% N-1 loading, THDi 42% mitigated by SVG, 160 kW crane dip 1.7% vs 8.2% DOL (feasibility-level).
- •2×630 kVA S13-M-630/10 oil transformers (N+1), 80% loading after one-unit loss, 480 kW demand
- •160 kW quay crane on VFD — 1.7% start dip vs 8.2% DOL; 300 kW impact load
- •SVG dynamic compensation ($32,200) for the crane's regenerating/impact load and 42% THDi
- •No backup source — grid-tied only; N-1 transformer covers crane + shore power
- •Economics: $156,706 total; SH15 upgrade saves $337/yr, ~3 yr payback; losses 161,197 kWh/yr ≈ $19,344
2 · Solution Overview
A container terminal is a VFD-dense, impact-heavy load: quay cranes and RTGs surge on pickup and regenerate on lowering, causing voltage flicker that can trip neighboring feeders. This scheme uses N+1 oil transformers plus a 160 kW crane VFD and SVG dynamic compensation to hold voltage steady and clean the bus.
| Source | Role | Share kW | Share |
|---|---|---|---|
| Grid 10 kV | base | 480 kW | 100% |
Port & Metallurgy Power System Calculator
Size and configure the power distribution system for port quay cranes and metallurgical loads - impact loads, reactive power and harmonic mitigation, BOM and single-line diagram.
3 · Design Process & Rationale
1. Requirement identification
600 kW terminal: 450 kW power, 300 kW impact (crane), 250 kW nonlinear, 160 kW largest motor on VFD.
2. Load character
Crane impact 300 + nonlinear 250; demand 480 kW (Kd 0.8); cyclic starts, no long-term critical standby load.
3. Source
10 kV grid only (grid-tied); cranes cycle, no grade-1 standby load, so no diesel/UPS.
4. Transformer sizing
480 kW ≈ 505 kVA → 630 kVA tier; N+1 → 2×S13-M-630/10, 80% loading after one-unit loss.
5. SVG & harmonics
42% THDi + 300 kW impact → SVG dynamic compensation ($32,200) for flicker + reactive + harmonic.
6. Crane drive
160 kW VFD (1.7% dip); regenerative drive returns braking energy to the DC bus (quay crane regenerative drive item).
7. Protection
MV 31.5 / LV 36 kA breaking; selectivity 10.71×; modbus SCADA.
Pain Points → Solution → Evidence
Crane starts cause voltage flicker that dims other feeders
SVG dynamic compensation responds in <10 ms to hold the bus
300 kW impact; SVG $32,200 auto-selected
VFD harmonics overheat the transformer
Detuned reactor + SVG active filtering
THDi 42% (V6 warn)
Regenerative crane braking backfeeds the DC bus
Regenerative drive + braking resistor
quay crane regenerative drive item (POA)
4 · Key Parameter Deep-Read
| Parameter | Value | Basis | Impact & Boundary |
|---|---|---|---|
| Transformer capacity | 630 kVA ×2 (S13-M) | 505 kVA → 630 tier; N+1 → 2 units | 80% loading, economical band 60–85% above ~540 kVA demand, step to 800 |
| SVG dynamic compensation | $32,200 | 300 kW impact + 42% THDi auto-selects SVG | <10 ms response; flicker + reactive + harmonic PFC capacitors can't handle flicker; only SVG can |
| Crane motor | 160 kW VFD, 1.7% dip | VFD kst 1.3 vs DOL 6.5 | no sag; DOL would be 8.2% confirm regenerative drive & braking resistor |
| Impact load | 300 kW | crane pickup/hoist instantaneous surge | sets SVG size & flicker suppression multi-crane coincidence factor to verify |
| Harmonics | THDi 42% | nonlinear 250 kW / 600 kW | needs SVG active filtering target THDi ≤8% |
| Demand factor | 0.8 → 480 kW | installed 600 kW × Kd 0.8 | sizes transformer at real demand verify against crane duty cycle |
5 · Drawing Deep-Read
The following drawings are shown for reference (full set in the configurator “View design document”):
6 · Operation Demo (Deep-Read)
Reliability
N+1 80% after one-unit loss; grid-tied with no backup — crane + shore power covered by dual-transformer redundancy.
Fault & protection
LV 22 kA / MV 28.9 kA, breaking LV 36 kA / MV 31.5 kA (1.3×); selectivity 10.71×.
Power quality
THDi 42% mitigated by SVG; crane VFD dip 1.7% (DOL 8.2%), bus 0.983 pu.
Economics
$156,706 total; SH15 upgrade ~3 yr payback ($337/yr); losses 161,197 kWh/yr ≈ $19,344.
Other views (shown): LCC (life-cycle cost) · Power quality & harmonics · Voltage profile · Scheme features · Arc flash
7 · Economics & Payback
Equipment total ≈ $156,706 (2×S13-M-630/10 + crane feeders + SVG dynamic compensation + modbus SCADA). No PV/BESS, so economics = capex + losses + transformer TCO: S13→SH15 amorphous upgrade saves ≈2,803 kWh/yr (≈$337/yr), ~3 yr payback; annual transformer+line losses ≈161,197 kWh (≈$19,344/yr). Crane regenerative drive and shore power are POA.
8 · FAQ
What transformer for a 600 kW terminal?
SVG vs plain capacitor compensation?
Does the crane need a VFD?
How is 42% THDi handled?
What does voltage flicker do?
Where does crane-lowering regenerative energy go?
Is a backup source needed?
What's the payback on a better transformer?
Is the price final?
Special Considerations
- THDi 42% is severely over the limit: PFC capacitors can't handle flicker, SVG dynamic compensation is mandatory (V6 remedy).
- This scheme is grid-tied with no backup; if cranes are critical continuous duty, evaluate diesel/UPS separately.
- Crane regenerative drive and shore power are POA; multi-crane coincidence factor must be verified.
- The 160 kW crane VFD is the largest motor; confirm regenerative braking resistor and DC bus rating.
- Feasibility-level estimate; drawings pending a licensed design institute; confirm grid Ssc (500 MVA assumed).
Turn this into your project
Open this exact scenario pre-loaded in the Power System Configurator, then generate the full design document or the operation & techno-economic assessment.
Open in Power System Configurator →Related Scenarios
One-Stop Supply of Conventional & Solar Power Equipment
From power distribution system design to solar energy — transformers, switchgear, substations and solar equipment, sized and quoted in one place. Use our calculators to get a complete bill of materials and FOB price.