CKSG Series Reactors

9 Models available

CKSG Reactors

Images are for illustration purposes only

CKSG Series - Three-Phase Series Reactors for Capacitor Banks

The CKSG series represents three-phase series reactors purpose-built for capacitor banks, protecting capacitors from inrush currents and harmonic resonance. Available with 6-12% impedance matching, these dry-type reactors ensure safe and reliable reactive power compensation.

Model Number Breakdown

CSeries (capacitor bank) connection
KReactor
SThree-phase
GDry-type

Applications

1

Capacitor bank series protection

2

Reactive power compensation systems

3

Harmonic resonance detuning

4

Power factor correction

Key Features

  • Designed for capacitor bank protection
  • 6-12% impedance for resonance detuning
  • Class F insulation, maintenance-free design
  • Compact dry-type construction

Specifications Range

All specifications and dimensions can be customized upon request

Model Selector

Key parametersModel Range
Capacity6–50 kvar
Rated current (A)8.98, 32.08, 7.7, 25.66, 64.15, 51.32…
Rated voltage (kV)0.45
Frequency (Hz)50
Impedance (%)12, 8, 6
StandardGB10229, IEC 60076-6
Select 2-3 models to compare
CompareModelSeriesCapacity (kVA)HV Voltage (kV)Current (A)Frequency (Hz)ReactanceTemp. rise (K)InsulationCoolingStandardWeightDimensions
CKSG-7KvarCKSG7kVA0.458.98501265F (155°C)ANGB10229, IEC 60076-665 kg345×230×315 mm
CKSG-25KvarCKSG25kVA0.4532.0850865F (155°C)ANGB10229, IEC 60076-6165 kg435×290×410 mm
CKSG-6KvarCKSG6kVA0.457.7501265F (155°C)ANGB10229, IEC 60076-660 kg330×225×310 mm
CKSG-20KvarCKSG20kVA0.4525.6650865F (155°C)ANGB10229, IEC 60076-6140 kg420×280×400 mm
CKSG-50KvarCKSG50kVA0.4564.1550665F (155°C)ANGB10229, IEC 60076-6270 kg480×320×450 mm
CKSG-40KvarCKSG40kVA0.4551.3250865F (155°C)ANGB10229, IEC 60076-6230 kg465×310×435 mm
CKSG-12.5KvarCKSG12.5kVA0.4516.04501265F (155°C)ANGB10229, IEC 60076-6100 kg390×260×365 mm
CKSG-14KvarCKSG14kVA0.4517.96501265F (155°C)ANGB10229, IEC 60076-6105 kg395×265×375 mm
CKSG-30KvarCKSG30kVA0.4538.4950865F (155°C)ANGB10229, IEC 60076-6190 kg450×300×420 mm

Product Drawing

Reactor - CKSG-20Kvar

APPEARANCE — AIR-CORE COIL
REACTORinsulator pedestalCKSG-20Kvar
CONNECTION — SERIES & SHUNT
REACTOR — SERIES & SHUNTSERIES (line)series reactorSHUNT (bus)shunt reactorCKSG-20Kvar
HARMONIC FILTER — LC BRANCH
DETUNED HARMONIC FILTER (LC)reactorcapacitorBUSCKSG-20Kvar

Note: This is a general product illustration. For detailed technical drawings and specifications, please contact our engineering team.

Instant Selection & Quote Calculator

Select your specifications to get an estimated price instantly.

1 · Configure
More options(2)
Reactor Inductance ↔ Rating (mH ↔ kvar)

Fill in any two of inductance L, rated current I and reactive power Q — the third is derived. The phase basis (single / three-phase) must be chosen, because the two bases differ by exactly a factor of three.

X = 2πfL · U_L = I·X · Q₁ = I²X (single-phase) · Q₃ = 3I²X (three-phase)

Inputs
Phase basis (required)
Result
Reactance X = 2πfL—
Inductance L—
Rated current I—
Voltage across the reactor U_L = I·X—
Reactive power, single-phase basis: Q₁ = I²X—
Reactive power, three-phase basis: Q₃ = 3I²Xyour basis—

Still required to complete the calculation: inductance L, rated current I, reactive power Q.

Worked example (the customer case)

L = 1 mH, I = 150 A, f = 50 Hz → X = 0.3142 Ω, U_L = 47.12 V, single-phase Q₁ = 7.07 kvar, three-phase Q₃ = 21.21 kvar.

Single-phase and three-phase differ by exactly a factor of three — always state which basis a kvar figure is quoted on.

Insulation level (IEC 60071-1)
Not specified — the factory parameter sheet is required.
Select a rated voltage in the configuration above to see the matching IEC class.
Non-IEC enquiry case:The enquired Um 15 kV / LI 105 kV / AC 52 kV is not an IEC standard combination (no 15 kV and no 105 kV in IEC lists); it belongs to regional systems such as JEC (Japan) / CNS (Taiwan), where a 15 kV class is about LI 95-110 / AC 50-55. Confirm the system before quoting and map to the nearest IEC class (17.5 kV).

The product library (quote-data) carries no per-model inductance or rated current, so no value is auto-filled for a model; the actual figures are confirmed on the factory parameter sheet. An em dash means the value is unavailable — it is never rendered as zero.