QDTB® Transformer

SBH15-M-250/20

SBH15-M Series • 250kVA • 20/0.4 kV

SBH15-M-250/20 is a 250 kVA, 20/0.4 kV amorphou alloy transformers manufactured by Shandong Yaqing Electric Power Technology Co., Ltd. (QDTB) in Qingdao, China, designed and tested in accordance with GB1094, JB/T10318, vector group Dyn11, short-circuit impedance 4%, approximate weight 1020 kg. Available on FOB Qingdao terms; datasheet, routine test report and GA drawing issued with each unit.

Technical Specifications

SBH15-M-250/20 technical specifications
ModelSBH15-M-250/20
Rated Capacity250kVA
HV Voltage20 kV
LV Voltage0.4 kV
Frequency50 Hz
Vector GroupDyn11
Short-circuit Impedance4%
CoolingONAN
InsulationA(105°C)
Temperature Rise65 K
No-load Loss87 W
Load Loss3200 W
Efficiency4
Weight1020 kg
Dimensions1190×1030×1300 mm
Applied StandardGB1094, JB/T10318

Product Image & Parameters

SBH15-M - QDTB

Images are for illustration purposes only

SBH15-M-250/20

SBH15-M Series

Capacity
250kVA
HV Voltage
20kV
LV Voltage
0.4kV
Frequency
50Hz
Short-circuit impedance
4%
Cooling method
ONAN
Efficiency
4
Applied standard
GB1094, JB/T10318
Connection
Dyn11
Amorphous Alloy CoreEnergy SavingLow Loss

TECHNICAL DRAWING

Model: SBH15-M-250/20 | Type: Amorphous alloy transformer | Capacity: 250 kVA

FRONT ELEVATION

Oil level1U1V1W2U2V2W2NTAPN.P.180mm240mm

ELECTRICAL SCHEMATIC

HV WINDING (Delta)1U1V1WLV WINDING (Star)2U2V2W2NDyn11

EFFICIENCY vs LOAD

90%95%98%99%0%25%50%75%100%≈99%load %efficiency %

SIDE VIEW

Oil level135mm

TOP VIEW

1U1V1W2U2V2W2N135mm

TERMINAL BLOCK

HV TERMINAL BLOCK1U1V1W1N1PELV TERMINAL BLOCK2U2V2W2N2PE2122Terminal block configurationTin-plated copper busbar

CORE & WINDING

OIL / TANKHV winding/bushingINSULATIONLV winding/bushingIron coreconcentric cross-section

Technical specifications

1. Model:SBH15-M-250/20
2. Type:Amorphous alloy transformer
3. Capacity:250 kVA
4. Frequency:50 Hz
5. HV voltage:20 kV
6. LV voltage:0.4 kV
7. HV current:7.22A
8. LV current:360.84A
9. Vector group:Dyn11
10. Impedance:4%
11. Insulation level:A(105°C)
12. Temperature rise:65K
13. No-load loss:87W
14. Load loss:3200W
15. No-load current:0.6%
16. Cooling method:ONAN
17. Tap changer:±2×2.5% or ±5%
18. Standard:GB1094, JB/T10318
19. Dimensions:1190×1030×1300 mm
20. Weight:1020kg
LEGEND:
Iron core
HV winding/bushing
LV winding/bushing
Dimension line

Product Description

250kVA amorphous alloy oil-immersed transformer, 20kV/0.4kV, 20kV class

SBH15-M 250kVA 20kV-class amorphous alloy distribution transformer. Ultra-low no-load loss for 20kV distribution network. Energy-saving, environmentally friendly.

Related Keywords

SBH15-M-250/20 amorphous alloy transformer250kVA amorphous distribution transformerSBH15-M oil immersed amorphous transformer ultra-low loss for solar power stationlow-loss amorphous metal core transformer for renewable energy

Instant Selection & Quote Calculator

Select your specifications to get an estimated price instantly.

1 · Configure
More options(2)
Certification
2 · Your price
Derived Ratings (calculated from the configuration)

The values below are computed from what you selected above. Anything that cannot be computed yet is shown as an em dash — never as zero.

Iₙ = S / (√3·U) · I_sc = 100·Iₙ / uₖ · S_sc = √3·U·I_sc · I_p = k·Iₖ

Inputs taken from the configuration
Capacity: — kVAfrom the configuration above
System voltage: not specified
Impedance voltage uₖ: not specified
Result
Rated current Iₙ—
Short-circuit current I_sc—
Short-circuit current I_sc—
Short-circuit power S_sc—
I_sc is calculated on the transformer impedance basis alone (system impedance neglected) — the same basis used in IEC 60076-5 short-circuit calculations.
System voltage → —

Still required to complete the calculation: rated capacity S, impedance voltage uₖ, short-time or peak withstand current.

Per-model values (P0 / Pk / uₖ declared by the factory, losses, noise, temperature rise, dimensions, weight) are not in the product library: those rows stay at an em dash until the factory parameter sheet is supplied. An em dash means the value is unavailable — it is never rendered as zero.

Derived losses (from the selected efficiency grade + capacity)
Oil amorphous
No-load loss P0 (kW)—
Load loss Pk (kW)—

Read-only: no price factor, not part of the sum — the loss-grade cost is already carried by the efficiency (subtype) base price, so charging here would double-bill. Values come from the product library type-test data, interpolated between published capacities; grades the library does not cover show an em dash, never zero.

油浸非晶(SBH15-M / SH16)

Reference prices are for estimation only and do not constitute a formal offer.

3 · Get this quote

We will reply with your latest quote instantly.

SBH15-M-250/20 - Frequently Asked Questions

QWhat are the main applications of SBH15-M-250/20?

SBH15-M-250/20 (SBH15-M series, Amorphous Alloy Transformers) is widely used in industrial power distribution, commercial buildings and utility power systems. Can be flexibly configured according to actual project requirements.

QWhat are the main technical specifications of SBH15-M-250/20?

Key specifications: Capacity: 250kVA, HV 20 kV, LV 0.4 kV, Frequency 50 Hz, Impedance 4%, Connection Dyn11, Cooling ONAN, Standard GB1094, JB/T10318.

QCan SBH15-M-250/20 be custom ordered?

Yes. QDTB® provides comprehensive OEM/ODM customization services. Parameters such as capacity, voltage ratio, cooling method, connection group and protection class can all be adjusted. Over 25 years of manufacturing experience ensures consistent quality.

QHow to get a quote and technical documentation?

Contact via the "Send Inquiry" button below, or contact sales at Alice@qdtb-transformer.com / +86 13698683193. We provide detailed quotations and technical documentation instantly.

Interested in SBH15-M-250/20?

Contact us for pricing, technical support, or custom requirements.