CKSC-35/150/7
CKSC Series • 150kVA • 35/35 kV
CKSC-35/150/7 is a 150 kVA, 35/35 kV reactor manufactured by Shandong Yaqing Electric Power Technology Co., Ltd. (QDTB) in Qingdao, China, designed and tested in accordance with GB10229, IEC 60076-6, vector group Series, short-circuit impedance 7%, approximate weight 580 kg. Available on FOB Qingdao terms; datasheet, routine test report and GA drawing issued with each unit.
Technical Specifications
| Model | CKSC-35/150/7 |
|---|---|
| Rated Capacity | 150kVA |
| HV Voltage | 35 kV |
| LV Voltage | 35 kV |
| Frequency | 50 Hz |
| Vector Group | Series |
| Short-circuit Impedance | 7% |
| Cooling | AN |
| Insulation | F (155°C) |
| Temperature Rise | 65 K |
| Weight | 580 kg |
| Dimensions | 600×400×550 mm |
| Applied Standard | GB10229, IEC 60076-6 |
Product Image & Parameters

Images are for illustration purposes only
CKSC-35/150/7
CKSC Series
Product Drawing
Reactor - CKSC-35/150/7
SPECIFICATIONS
Note: This is a general product illustration. For detailed technical drawings and specifications, please contact our engineering team.
Product Description
CKSC-35/150/7 medium voltage series reactor. Iron-core construction, F-class insulation, AN cooling. 7% reactance for 35kV power system.
Instant Selection & Quote Calculator
Select your specifications to get an estimated price instantly.
More options(2)
Fill in any two of inductance L, rated current I and reactive power Q — the third is derived. The phase basis (single / three-phase) must be chosen, because the two bases differ by exactly a factor of three.
X = 2πfL · U_L = I·X · Q₁ = I²X (single-phase) · Q₃ = 3I²X (three-phase)
Still required to complete the calculation: inductance L, rated current I, reactive power Q.
L = 1 mH, I = 150 A, f = 50 Hz → X = 0.3142 Ω, U_L = 47.12 V, single-phase Q₁ = 7.07 kvar, three-phase Q₃ = 21.21 kvar.
Single-phase and three-phase differ by exactly a factor of three — always state which basis a kvar figure is quoted on.
The product library (quote-data) carries no per-model inductance or rated current, so no value is auto-filled for a model; the actual figures are confirmed on the factory parameter sheet. An em dash means the value is unavailable — it is never rendered as zero.
Certification
Reference prices are for estimation only and do not constitute a formal offer.
3 · Get this quote
We will reply with your latest quote instantly.
CKSC-35/150/7 - Frequently Asked Questions
QWhat are the main applications of CKSC-35/150/7?
CKSC-35/150/7 (CKSC series, Reactors) is widely used in inverter protection, harmonic filtering and power factor improvement. Can be flexibly configured according to actual project requirements.
QWhat are the main technical specifications of CKSC-35/150/7?
Key specifications: Capacity: 150kVA, HV 35 kV, LV 35 kV, Frequency 50 Hz, Impedance 7%, Connection Series, Cooling AN, Standard GB10229, IEC 60076-6.
QHow to get a quote and technical documentation?
Contact via the "Send Inquiry" button below, or contact sales at Alice@qdtb-transformer.com / +86 13698683193. We provide detailed quotations and technical documentation instantly.
Related Products in CKSC Series
Interested in CKSC-35/150/7?
Contact us for pricing, technical support, or custom requirements.