Lightning Impulse Test

Insulation & Testing

A high-voltage test simulating lightning surges to verify transformer insulation withstands transient overvoltages.

The lightning impulse test applies a 1.2/50 microsecond impulse wave to verify insulation withstands lightning/switching transients. Per IEC 60076-3 or IEEE C57.

Level determined by BIL requirements. Standard sequence: one at 50-70% (calibrating), two at 100%. Pass: no waveform change between impulses.

Mandatory for all transformers, most definitive insulation integrity verification.

QDTB performs full lightning impulse testing on every transformer as routine factory acceptance, with complete oscillographic records.