HV/LV Bushing
High-voltage and low-voltage insulated conduits for transformer winding connections through the grounded tank.
HV/LV bushings provide insulated pathways for winding connections through the grounded tank wall while maintaining isolation and oil sealing.
HV bushings (>72.5 kV) use capacitance-graded OIP, RIP, or RIS insulation with concentric conducting layers for uniform voltage distribution. LV bushings use simpler solid or oil-filled designs.
Parameters: rated voltage/current, BIL, tan delta. Bushing failure is a leading outage cause.
QDTB supplies premium bushings matched to each transformer's requirements. See selection guide for type recommendations.
Related Products
Related Terms
Bushing
An insulated device allowing a conductor to pass through a grounded barrier while maintaining insulation integrity.
BIL (Basic Impulse Level)
The ability of transformer insulation to withstand high-voltage surges from lightning or switching, measured in kV peak.
Insulation Class (A/E/B/F/H)
Standardized temperature ratings for transformer insulation materials defining maximum operating temperatures.
More Terms Starting with “H”
Harmonics
Integer multiples of fundamental frequency from non-linear loads, causing increased transformer losses and overheating.
Hot-Spot Temperature
The highest temperature within transformer winding insulation, determining aging rate and loading capability.
Hysteresis Loss
Energy lost in core steel from repeated reversal of magnetic domains each AC cycle, a component of core loss.
More in “Components & Accessories”
Bushing
An insulated device allowing a conductor to pass through a grounded barrier while maintaining insulation integrity.
Busbar
A metallic strip conducting electricity within switchgear, transformers, and distribution equipment.
Load Tap Changer (LTC)
A mechanism allowing transformer tap ratio changes while energized and under load for real-time voltage regulation.
Need help with transformer selection?