Inrush Current

Electrical Fundamentals

A high transient current when a transformer is first energized, caused by core saturation, reaching 10-30x rated.

Inrush current flows when a transformer is first energized, caused by temporary core saturation. Flux may reach 2x normal peak, driving core deep into saturation.

During saturation, magnetizing inductance drops dramatically. Current: 8-15x rated for distribution, up to 30x for power transformers. Contains DC offset and 2nd harmonic content, decaying over cycles to seconds.

Can cause nuisance tripping, voltage dips, mechanical stress. Modern relays use 2nd harmonic restraint to distinguish from fault current.

QDTB provides energization guidance and controlled switching options for large installations.