Winding Resistance

Diagnostics & Maintenance

The DC resistance of transformer windings, measured for loss calculation and connection quality verification.

Winding resistance is the DC resistance of winding conductors. Serves multiple purposes: calculating I2R losses (load loss component), determining average temperature during heat run (+0.393%/deg C for copper), verifying connection quality (tap changer contacts, brazed joints).

Measured with micro-ohm meters. Corrected to reference temperature (75C per IEC): R2 = R1 x (235+T2)/(235+T1) for copper.

Changes >1-2% from baseline indicate: loose connections, contact degradation, strand breaks, shorted turns.

QDTB measures and documents for every transformer at factory, establishing baselines for maintenance.